Plan Review Details - Permit 19080670
Plan Review Stops For Permit 19080670
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-02-04 Cont ID  
Sent By pvalenti Date 2020-02-04 Time 17:42 Rev Time 0.00
Received By pvalenti Date 2020-02-04 Time 17:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-18 Cont ID  
Sent By pvalenti Date 2020-01-18 Time 09:09 Rev Time 0.00
Received By pvalenti Date 2020-01-18 Time 08:55 Sent To  
Notes
2020-01-18 09:09:35***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD BUILDING REVIEW DENIED:
  
 PLEASE SEE THE BELOW UPDATED LIST FROM THE COMMENTS OF
 PRIOR REVIEW:
  
 1) OK, PALM BEACH COUNTY IMPACT FEE REVIEW # MU 2020
 1711
  
 2) OK
  
 3) (FAIL) THE (WINDOW) IN
 THE HALF BATH ARE NOT SHOWN ON THE PLANS FOR PERMIT
 #18120531 OR
 ON THE PREVIOUS REVISIONS. THEREFORE THEY ARE NOT
 EXISTING AND WILL REQUIRE PRODUCT APPROVALS AND IMPACT
 PROTECTION. SUBMIT TWO SETS OF PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD AS REQUIRED BY CITY AMENDMENTS FBC 107.3.4.
  
 4) OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By pvalenti Date 2020-01-13 Time 14:05 Rev Time 0.00
Received By pvalenti Date 2020-01-13 Time 14:05 Sent To  
Notes
2020-01-13 14:10:37***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD BUILDING REVIEW DENIED:
  
 PLEASE SEE THE BELOW UPDATED LIST FROM THE COMMENTS OF
 PRIOR REVIEW:
  
  
 1) (FAILED) THIS REVISION TO PERMIT #18120531, SHOWS
 THAT THE
 ENCLOSED REAR PORCH LAUNDRY AND THE ADDED HALF BATH ARE
 OPEN TO THE KITCHEN. THIS ADDED HABITABLE SPACE
 REQUIRES AN IMPACT FEE REVIEW BY PALM BEACH COUNTY.
  
 2) (OK)
  
 3) (FAIL) THE DOOR TO THE EXTERIOR AND THE WINDOW IN
 THE HALF
 BATH ARE NOT SHOWN ON THE PLANS FOR PERMIT #18120531 OR
 ON THE PREVIOUS REVISIONS. THEREFORE THEY ARE NOT
 EXISTING AND WILL REQUIRE PRODUCT APPROVALS AND IMPACT
 PROTECTION. SUBMIT TWO SETS OF PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD AS REQUIRED BY CITY AMENDMENTS FBC 107.3.4.
  
 4) (FAIL) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT
 HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 ROOFING MATERIALS THAT WILL BE INSTALLED ON THE
 ADDITION.
 CITY AMENDMENTS FBC 107.3.4
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By pvalenti Date 2019-11-14 Time 17:50 Rev Time 0.00
Received By pvalenti Date 2019-11-14 Time 17:50 Sent To  
Notes
2019-11-14 17:59:29***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) THIS REVISION TO PERMIT #18120531, SHOWS THAT THE
 ENCLOSED REAR PORCH LAUNDRY AND THE ADDED HALF BATH ARE
 OPEN TO THE KITCHEN. THIS ADDED HABITABLE SPACE
 REQUIRES AN IMPACT FEE REVIEW BY PALM BEACH COUNTY.
  
 2) FBC 107.2.1 PROVIDE NEW EXTERIOR WALL SECTION DETAIL
 AT TOILET ROOM.
  
 3) THE DOOR TO THE EXTERIOR AND THE WINDOW IN THE HALF
 BATH ARE NOT SHOWN ON THE PLANS FOR PERMIT #18120531 OR
 ON THE PREVIOUS REVISIONS. THEREFORE THEY ARE NOT
 EXISTING AND WILL REQUIRE PRODUCT APPROVALS AND IMPACT
 PROTECTION. SUBMIT TWO SETS OF PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD AS REQUIRED BY CITY AMENDMENTS FBC 107.3.4.
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 ROOFING MATERIALS THAT WILL BE INSTALLED ON THE
 ADDITION.
 CITY AMENDMENTS FBC 107.3.4
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By jleahy Date 2019-09-27 Time 16:16 Rev Time 0.00
Received By jleahy Date 2019-09-27 Time 16:16 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-29 Cont ID  
Sent By jleahy Date 2019-08-29 Time 11:13 Rev Time 0.00
Received By jleahy Date 2019-08-29 Time 11:13 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-10-23 Cont ID  
Sent By tklarge Date 2019-10-23 Time 09:51 Rev Time 0.00
Received By tklarge Date 2019-10-23 Time 09:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-10-01 Cont ID  
Sent By tklarge Date 2019-10-01 Time 13:09 Rev Time 0.00
Received By tklarge Date 2019-10-01 Time 13:09 Sent To  
Notes
2019-10-01 13:09:011) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. 2ND REQUEST.
 2) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS
 OR WINDOWS IN RELATION TO THE TANKLESS WATER HEATER.
 THE LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND.
 TO FBC SEC. 107.2.1. 2ND REQUEST.
 3) A SEPARATE PERMIT IS REQUIRED FOR THE GAS
 INSTALLATION.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By tklarge Date 2019-08-30 Time 14:14 Rev Time 0.00
Received By tklarge Date 2019-08-30 Time 14:05 Sent To  
Notes
2019-08-30 14:14:471) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO
 FBC SEC. 107.2.1.3
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 7) SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1
 8) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS
 OR WINDOWS IN RELATION TO THE TANKLESS WATER HEATER.
 THE LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND.
 TO FBC SEC. 107.2.1.
 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 10) A SEPARATE PERMIT IS REQUIRED FOR THE GAS
 INSTALLATION.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-02-04 Cont ID  
Sent By pvalenti Date 2020-02-04 Time 17:43 Rev Time 0.00
Received By pvalenti Date 2020-02-03 Time 13:20 Sent To  
Notes
2020-02-04 13:20:31RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-01-18 Cont ID  
Sent By pvalenti Date 2020-01-18 Time 09:09 Rev Time 0.00
Received By pvalenti Date 2020-01-17 Time 11:40 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-13 Cont ID  
Sent By pvalenti Date 2020-01-13 Time 14:28 Rev Time 0.00
Received By pvalenti Date 2020-01-06 Time 14:21 Sent To  
Notes
2020-01-07 14:21:19RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-14 Cont ID  
Sent By pvalenti Date 2019-11-14 Time 17:59 Rev Time 0.00
Received By pvalenti Date 2019-10-23 Time 09:46 Sent To  
Notes
2019-10-21 13:57:02RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-01 Cont ID  
Sent By tklarge Date 2019-10-01 Time 13:11 Rev Time 0.00
Received By tklarge Date 2019-09-23 Time 14:59 Sent To I
Notes
2019-09-24 14:59:58RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-30 Cont ID  
Sent By tklarge Date 2019-08-30 Time 14:14 Rev Time 0.00
Received By tklarge Date 2019-08-14 Time 14:35 Sent To  
Notes
2019-08-15 14:36:14REVISION ROUTED TO ELECTRICAL INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-23 Cont ID  
Sent By tklarge Date 2019-10-23 Time 09:46 Rev Time 0.00
Received By tklarge Date 2019-10-23 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-10-01 Cont ID  
Sent By tklarge Date 2019-10-01 Time 13:00 Rev Time 0.00
Received By tklarge Date 2019-10-01 Time 12:25 Sent To  
Notes
2019-10-01 13:05:081) THE 2 INCH WASHING MACHINE DRAIN SHALL CONNECT TO A
 MINIMUM 3 INCH WASTE STACK.2017 FBC-PLUMBING TABLE
 709.1 FOOTNOTE G.2ND REQUEST.
 2) THE HOT WATER LINE ON THE TANKLESS WATER HEATER
 SHALL BE INSUKATED. 2017 FBC-ENERGY SEC.R403.5.3.2ND
 REQUEST
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATER.WPB AMEND.
 TO FBC SEC. 107.2.1. 2ND REQUEST
 4) THE MAIN PERMIT WAS FOR THE REPAIR OF THE BACK PORCH
 AND THE REVISION SHOWS A PARTIAL WALL ON THE INTERIOR
 AND A POCKET DOOR. SUBMIT COMPLETE PLANS FOR THE
 BUILDOUT OF THIS TOILET ROOM WPB AMEND. TO FBC SEC.
 107.2.1. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By tklarge Date 2019-08-30 Time 14:05 Rev Time 0.00
Received By tklarge Date 2019-08-30 Time 13:20 Sent To  
Notes
2019-08-30 13:26:401) THE 2 INCH WASHING MACHINE DRAIN SHALL CONNECT TO A
 MINIMUM 3 INCH WASTE STACK.2017 FBC-PLUMBING TABLE
 709.1 FOOTNOTE G.
 2) THE HOT WATER LINE ON THE TANKLESS WATER HEATER
 SHALL BE INSUKATED. 2017 FBC-ENERGY SEC.R403.5.3.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATER.WPB AMEND.
 TO FBC SEC. 107.2.1.
 4) SHOW LENGTH AND WIDTH DIMENSIONS OF THE POWDER ROMM.
 PLUMBING FIXTURES SHALL BE LOCATED IN ACCORDANCE WITH
 2017 FBC-PLUMBING SEC. 405.3.1.
 5) THE MAIN PERMIT WAS FOR THE REPAIR OF THE BACK PORCH
 AND THE REVISION SHOWS A PARTIAL WALL ON THE INTERIOR
 AND A POCKET DOOR. SUBMIT COMPLETE PLANS FOR THE
 BUILDOUT OF THIS TOILET ROOM WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  