Plan Review Stops For Permit 19080670 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2020-02-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-04 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-04 |
Time |
17:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2020-01-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-01-18 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-01-18 |
Time |
08:55 |
Sent To |
|
|
Notes |
2020-01-18 09:09:35 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 3RD BUILDING REVIEW DENIED: | | | | PLEASE SEE THE BELOW UPDATED LIST FROM THE COMMENTS OF | | PRIOR REVIEW: | | | | 1) OK, PALM BEACH COUNTY IMPACT FEE REVIEW # MU 2020 | | 1711 | | | | 2) OK | | | | 3) (FAIL) THE (WINDOW) IN | | THE HALF BATH ARE NOT SHOWN ON THE PLANS FOR PERMIT | | #18120531 OR | | ON THE PREVIOUS REVISIONS. THEREFORE THEY ARE NOT | | EXISTING AND WILL REQUIRE PRODUCT APPROVALS AND IMPACT | | PROTECTION. SUBMIT TWO SETS OF PRODUCT APPROVALS THAT | | HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF | | RECORD AS REQUIRED BY CITY AMENDMENTS FBC 107.3.4. | | | | 4) OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-01-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-01-13 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-01-13 |
Time |
14:05 |
Sent To |
|
|
Notes |
2020-01-13 14:10:37 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 3RD BUILDING REVIEW DENIED: | | | | PLEASE SEE THE BELOW UPDATED LIST FROM THE COMMENTS OF | | PRIOR REVIEW: | | | | | | 1) (FAILED) THIS REVISION TO PERMIT #18120531, SHOWS | | THAT THE | | ENCLOSED REAR PORCH LAUNDRY AND THE ADDED HALF BATH ARE | | OPEN TO THE KITCHEN. THIS ADDED HABITABLE SPACE | | REQUIRES AN IMPACT FEE REVIEW BY PALM BEACH COUNTY. | | | | 2) (OK) | | | | 3) (FAIL) THE DOOR TO THE EXTERIOR AND THE WINDOW IN | | THE HALF | | BATH ARE NOT SHOWN ON THE PLANS FOR PERMIT #18120531 OR | | ON THE PREVIOUS REVISIONS. THEREFORE THEY ARE NOT | | EXISTING AND WILL REQUIRE PRODUCT APPROVALS AND IMPACT | | PROTECTION. SUBMIT TWO SETS OF PRODUCT APPROVALS THAT | | HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF | | RECORD AS REQUIRED BY CITY AMENDMENTS FBC 107.3.4. | | | | 4) (FAIL) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT | | HAVE BEEN | | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE | | ROOFING MATERIALS THAT WILL BE INSTALLED ON THE | | ADDITION. | | CITY AMENDMENTS FBC 107.3.4 | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-11-14 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-11-14 |
Time |
17:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-11-14 |
Time |
17:50 |
Sent To |
|
|
Notes |
2019-11-14 17:59:29 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | 1) THIS REVISION TO PERMIT #18120531, SHOWS THAT THE | | ENCLOSED REAR PORCH LAUNDRY AND THE ADDED HALF BATH ARE | | OPEN TO THE KITCHEN. THIS ADDED HABITABLE SPACE | | REQUIRES AN IMPACT FEE REVIEW BY PALM BEACH COUNTY. | | | | 2) FBC 107.2.1 PROVIDE NEW EXTERIOR WALL SECTION DETAIL | | AT TOILET ROOM. | | | | 3) THE DOOR TO THE EXTERIOR AND THE WINDOW IN THE HALF | | BATH ARE NOT SHOWN ON THE PLANS FOR PERMIT #18120531 OR | | ON THE PREVIOUS REVISIONS. THEREFORE THEY ARE NOT | | EXISTING AND WILL REQUIRE PRODUCT APPROVALS AND IMPACT | | PROTECTION. SUBMIT TWO SETS OF PRODUCT APPROVALS THAT | | HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF | | RECORD AS REQUIRED BY CITY AMENDMENTS FBC 107.3.4. | | | | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN | | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE | | ROOFING MATERIALS THAT WILL BE INSTALLED ON THE | | ADDITION. | | CITY AMENDMENTS FBC 107.3.4 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-09-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-09-27 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-09-27 |
Time |
16:16 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2019-08-29 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-08-29 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-08-29 |
Time |
11:13 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2019-10-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-23 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-10-23 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2019-10-01 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-01 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-10-01 |
Time |
13:09 |
Sent To |
|
|
Notes |
2019-10-01 13:09:01 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | SEC.G2408.1. 2ND REQUEST. | | 2) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS | | OR WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. | | THE LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY | | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE | | HOUSE PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. | | TO FBC SEC. 107.2.1. 2ND REQUEST. | | 3) A SEPARATE PERMIT IS REQUIRED FOR THE GAS | | INSTALLATION. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2019-08-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-30 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-30 |
Time |
14:05 |
Sent To |
|
|
Notes |
2019-08-30 14:14:47 | 1) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE | | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 | | FBC-R SEC. G2413.4.1, G2413.4.2. | | 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO | | FBC SEC. 107.2.1.3 | | 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | G2413.4 (1 ) THROUGH G2413.4 (21). | | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 | | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. | | SEC. G 2413.4.1, G2413.4.2. | | 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR | | 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES | | DRYERS). | | 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | 7) SUBMIT TWO COPIES OF THE MANUFACTURER?S | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | SEC.G2408.1 | | 8) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS | | OR WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. | | THE LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY | | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE | | HOUSE PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | G2413.1, G2413.2, & G2413.3. | | 10) A SEPARATE PERMIT IS REQUIRED FOR THE GAS | | INSTALLATION. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2020-02-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-04 |
Time |
17:43 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-03 |
Time |
13:20 |
Sent To |
|
|
Notes |
2020-02-04 13:20:31 | RESUB ROUTED TO PVALENTI |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2020-01-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-01-18 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-01-17 |
Time |
11:40 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2020-01-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-01-13 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-01-06 |
Time |
14:21 |
Sent To |
|
|
Notes |
2020-01-07 14:21:19 | RESUB ROUTED TO PVALENTI |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-11-14 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-11-14 |
Time |
17:59 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-10-23 |
Time |
09:46 |
Sent To |
|
|
Notes |
2019-10-21 13:57:02 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-10-01 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-01 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-09-23 |
Time |
14:59 |
Sent To |
I |
|
Notes |
2019-09-24 14:59:58 | RESUB ROUTED TO JLEAHY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-08-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-30 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-14 |
Time |
14:35 |
Sent To |
|
|
Notes |
2019-08-15 14:36:14 | REVISION ROUTED TO ELECTRICAL INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-10-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-23 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-10-23 |
Time |
09:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2019-10-01 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-01 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-10-01 |
Time |
12:25 |
Sent To |
|
|
Notes |
2019-10-01 13:05:08 | 1) THE 2 INCH WASHING MACHINE DRAIN SHALL CONNECT TO A | | MINIMUM 3 INCH WASTE STACK.2017 FBC-PLUMBING TABLE | | 709.1 FOOTNOTE G.2ND REQUEST. | | 2) THE HOT WATER LINE ON THE TANKLESS WATER HEATER | | SHALL BE INSUKATED. 2017 FBC-ENERGY SEC.R403.5.3.2ND | | REQUEST | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE TANKLESS WATER HEATER.WPB AMEND. | | TO FBC SEC. 107.2.1. 2ND REQUEST | | 4) THE MAIN PERMIT WAS FOR THE REPAIR OF THE BACK PORCH | | AND THE REVISION SHOWS A PARTIAL WALL ON THE INTERIOR | | AND A POCKET DOOR. SUBMIT COMPLETE PLANS FOR THE | | BUILDOUT OF THIS TOILET ROOM WPB AMEND. TO FBC SEC. | | 107.2.1. 2ND REQUEST. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-08-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-30 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-30 |
Time |
13:20 |
Sent To |
|
|
Notes |
2019-08-30 13:26:40 | 1) THE 2 INCH WASHING MACHINE DRAIN SHALL CONNECT TO A | | MINIMUM 3 INCH WASTE STACK.2017 FBC-PLUMBING TABLE | | 709.1 FOOTNOTE G. | | 2) THE HOT WATER LINE ON THE TANKLESS WATER HEATER | | SHALL BE INSUKATED. 2017 FBC-ENERGY SEC.R403.5.3. | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE TANKLESS WATER HEATER.WPB AMEND. | | TO FBC SEC. 107.2.1. | | 4) SHOW LENGTH AND WIDTH DIMENSIONS OF THE POWDER ROMM. | | PLUMBING FIXTURES SHALL BE LOCATED IN ACCORDANCE WITH | | 2017 FBC-PLUMBING SEC. 405.3.1. | | 5) THE MAIN PERMIT WAS FOR THE REPAIR OF THE BACK PORCH | | AND THE REVISION SHOWS A PARTIAL WALL ON THE INTERIOR | | AND A POCKET DOOR. SUBMIT COMPLETE PLANS FOR THE | | BUILDOUT OF THIS TOILET ROOM WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|