Plan Review Details - Permit 19080447
Plan Review Stops For Permit 19080447
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-22 Cont ID  
Sent By rmcdouga Date 2019-11-22 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2019-11-22 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-21 Cont ID  
Sent By rmcdouga Date 2019-10-21 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2019-10-21 Time 10:33 Sent To  
Notes
2019-10-21 11:17:40ADDRESS MECHANICAL COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By shill Date 2019-08-13 Time 14:56 Rev Time 0.00
Received By rmcdouga Date 2019-08-13 Time 14:11 Sent To  
Notes
2019-08-13 14:56:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (THRESHOLD BUILDING) SUBMIT THREE SETS OF REVISED
 DRAWINGS FOR ALL ARCHITECTURAL AND MECHANICAL SHEETS
 THAT ARE AFFECTED BY THE PROPOSED USE OF THE FLAMEBAR
 PRODUCT. THE PLANS ARE TO BE DRAWN TO A MINIMUM 1/8
 INCH SCALE AND CLEARLY SHOW THE LOCATION, SIZE,
 CONNECTION DETAILS AND ALL OTHER PERTINENT INFORMATION.
 FBC 107.2, 107.2.1.2 & 107.2.1.3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-20 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-21 Cont ID  
Sent By rmcdouga Date 2019-10-21 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2019-10-08 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-13 Cont ID  
Sent By rmcdouga Date 2019-08-13 Time 14:57 Rev Time 0.00
Received By rmcdouga Date 2019-08-08 Time 15:44 Sent To  
Notes
2019-08-13 13:03:11TO RM
  
2019-08-09 15:44:34REVISION ROUTED TO SHILL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-12-05 Cont ID  
Sent By ccole Date 2019-12-05 Time 12:29 Rev Time 0.00
Received By ccole Date 2019-11-22 Time 08:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-10-18 Cont ID  
Sent By rmcdouga Date 2019-10-18 Time 11:16 Rev Time 0.00
Received By ccole Date 2019-10-18 Time 11:16 Sent To  
Notes
2019-10-18 11:23:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080447
 10/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A REVISON APPLICATION AND A DETAILED
 NARRATIVE TO CLARIFY THE SCOPE OF WORK FOR THIS
 SUBMITTAL- SECTION 107.2.1 WPB.
  
 2) THE ALTERNATE APPROVAL LETTER REQUEST TITLED "IBC
 104.11 ALTERNATE MEANS AND METHODS- FIRE RATED
 VENTILATION DUCT THE CANOPY HOTEL BY HILTON- PERMIT
 #16061443 BY STEVEN FELLER P.E. SHALL BE ELECTRONICALLY
 SIGNED AND SEALED- SECTION 61G15-23.005 FAC.
  
 3) IBC 104.11 ALTERNATE MEANS AND METHODS- FIRE RATED
 VENTILATION DUCT THE CANOPY HOTEL BY HILTON- SHEET
 AC-2-4 LEVEL-2 WEST: THE FLAMEBAR LAUNDRY EXHAUST DUCTS
 PENETRATING THE INTERIOR EXIT STAIR #2 APPEAR TO BE NOT
 IN COMPLIANCE WITH SECTION 1023.5 FBC B WHICH PROHIBITS
 PENETRATIONS INTO AND THROUGH THE STAIRWAY ENCLOSURE.
 PLEASE NOTE THAT NO DETAIL FOR THIS ALTERNATE
 INSTALLATION HAS BEEN PROVIDED IN THE PACKAGE, AND THE
 USE OF FLAMEBAR FOR THE INSTALLATION IS NOT INCLUDED IN
 THE FLORIDA BUILDING COMMISSION DECALARATORY STATEMENT
 DS 2016-078 THAT WAS SUBMITTED WITH THE ALTERNATE
 APPROVAL LETTER.
  
 4) SHEET M2.08A: THERE ARE VARIOUS FLAMEBAR/NON-RATED
 DUCT CONNECTORS CALLED OUT IN THE ENLARGED PENETRATION
 DETAIL. PLEASE SELECT ONE SPECIFIC CONNECTOR AND
 SUBMIIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CONNECTOR. PLEASE INDICATE WHERE
 THE CONNECTORS ARE SHOWN AND INCLUDED IN THE
 ALTERNATIVE APPROVAL SUBMITTAL PACKAGE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By ccole Date 2019-08-13 Time 14:57 Rev Time 0.00
Received By rmcdouga Date 2019-08-13 Time 14:57 Sent To  
Notes
2019-08-13 15:05:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REVISED MECHANICAL PLANS. FBC 107.2.1SEE
 BUILDING COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-12-05 Cont ID  
Sent By ccole Date 2019-12-05 Time 12:29 Rev Time 0.00
Received By ccole Date 2019-12-05 Time 12:29 Sent To  
Notes
2019-11-22 10:55:05ELECTRONIC SEAL AND SIGNATURE ON ENGINEER'S ALTERNATE
 APPROVAL LETTER IS GOOD.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-10-21 Cont ID  
Sent By rmcdouga Date 2019-10-21 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2019-10-21 Time 11:18 Sent To  
Notes
2019-10-21 11:22:02FLAMEBAR PACKAGE IS REQUIRED TO BE DIGITALLY SIGNED.
 SIGNATURES ON THE THREE PLAN DRAWINGS ARE ACCEPTABLE.