Plan Review Details - Permit 19080441
Plan Review Stops For Permit 19080441
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-27 Cont ID  
Sent By dbattles Date 2019-11-27 Time 14:20 Rev Time 0.00
Received By dbattles Date 2019-11-27 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By dbattles Date 2019-10-25 Time 10:15 Rev Time 0.00
Received By dbattles Date 2019-10-18 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-27 Cont ID  
Sent By jwitmer Date 2019-08-27 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2019-08-27 Time 12:59 Sent To  
Notes
2019-08-27 13:46:182017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080441
 ADD: 505 S. FLAGLER DR.
 CONT: ANDERSON MOORE CONTRACTING
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: TUES. AUGUST 27/ 2019
 ACTION: DENIED
  
 1) 002-SITE DEV. PLAN. PLEASE PROVIDE AN EXPLANATION AS
 TO WHY THERE IS A NEW DRIVEWAY AND STAIRS BEING CUT
 INTO S. FLAGLER DR. WHEN THE ENTRY TO THE BUILDING IS
 ON THE WEST FACE OF THE BUILDING? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) 002-SITE DEV. PLAN. IS THIS NEW DRIVE AND STAIRWAY
 PART OF A VALET SERVICE OR DOES THE PROPOSED NEW DRIVE
 HAVE A DROP OFF ZONE (PASSENGER LOADING ZONE) TO BE
 INCORPORATED INTO THE DRIVE? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3A) THERE ARE MANY ELEVATION MARKERS ON THE DRIVE PLAN
 002-SITE DEV. PLAN. THE ELEVATION MARKERS DO NOT MAKE
 IT CLEAR IF THEY ARE THE TOP OF THE D CURB OR THE TOP
 OF THE DRIVEWAY? 107.2.1.2 ADDITIONAL INFORMATION
 REQUIRED. PLEASE NOTE DIRECTLY IN FRONT OF THE NEW
 STAIR AND LANDING THERE IS A 0.84 FT. CROSS SLOPE DROP
 IF THERE IS TO BE A DROP OFF ZONE (PASSENGER LOADING
 ZONE)? 2017 FBC-ACCESS. CODE 503.4 SLOPES NOT STEEPER
 THAN 1:48 SHALL BE PERMITTED.
  
 3B) VEHICLE PULL UP SPACE IS TO COMPLY WITH ACCESS.
 CODE REQUIREMENTS 503.2-503.4.
  
 4) SHEET 002 SITE DEV. PLAN IF THERE IS NOT A PASSENGER
 DROP OFF ZONE, THE PLANS DO NOT STATE THERE IS A
 DROPPED CURB AT THE STAIR AND LANDING YOU WOULD HAVE TO
 WHEEL A WHEELCHAIR SOUTH OUT INTO THE TRAFFIC LANE FOR
 THE PARKING GARAGE TO GET TO THE SIDEWALK. 107.2.1.2.
 ADDITIONAL INFORMATION REQUIRED. IT WOULD APPEAR THIS
 NEW DRIVEWAY AND STAIR ARE NOT ACCESSIBLE TO THE UPPER
 LANDING, IF NOT PLEASE PROVIDE SIGNAGE WHERE THE
 ACCESSIBLE ENTRANCE IS LOCATED. PLEASE SHOW COMPLIANCE
 WITH:
 2017 FBC-ACCESSIBILITY CODE SECTION 216.6 ENTRANCES.
  
 WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES
 COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT
 INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING
 WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT
 COMPLY WITH 404.
  
 5) SHEET 002 SITE DEV. PLAN INDICATES THE REMOVAL OF A
 PORTION OF A RETAINING WALL. THERE IS ALSO A NOTE
 STAIRS BY OTHERS. WHAT IS NOT CLEAR, ARE THE STAIRS TO
 BE PART OF SEPARATE PERMIT? THE SHEET 007L1 INDICATES
 GRANITE STEP TREADS AND ALUMINUM HANDRAIL BUT NO PLANS
 HAVE BEEN SUBMITTED FOR THE STAIR LAYOUT, STEEL
 RE-ENFORCING NOR AND INFORMATION ON A HANDRAIL/
 GUARDRAIL SYSTEM. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2019-12-13 Cont ID  
Sent By rrossano Date 2019-12-13 Time   Rev Time 0.00
Received By   Date 2019-12-13 Time   Sent To  
Notes
2019-12-13 10:34:39UNDER FORMAL ENGINEERING REVIEW E19020034.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-11-13 Cont ID  
Sent By rrossano Date 2019-11-13 Time   Rev Time 0.00
Received By rrossano Date 2019-11-13 Time   Sent To  
Notes
2019-11-13 09:22:29PASSED WITH PROVISO:
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. MORE INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX:
 (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By rrossano Date 2019-09-09 Time   Rev Time 0.00
Received By rrossano Date 2019-09-09 Time   Sent To  
Notes
2019-09-09 07:28:19PLEASE ADDRESS BUILDING AND ZONING COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-30 Cont ID  
Sent By shill Date 2019-12-30 Time 11:07 Rev Time 0.00
Received By shill Date 2019-11-15 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-15 Cont ID  
Sent By lmarchan Date 2019-11-15 Time 12:33 Rev Time 0.00
Received By lmarchan Date 2019-10-02 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-09 Cont ID  
Sent By cpuell Date 2019-09-09 Time 11:49 Rev Time 0.00
Received By cpuell Date 2019-08-08 Time 07:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-11-27 Cont ID  
Sent By dbattles Date 2019-11-27 Time 14:20 Rev Time 0.00
Received By dbattles Date 2019-11-27 Time 14:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-18 Cont ID  
Sent By dbattles Date 2019-10-18 Time 08:06 Rev Time 0.00
Received By dbattles Date 2019-10-18 Time 08:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By shill Date 2019-09-13 Time 05:22 Rev Time 0.00
Received By shill Date 2019-09-13 Time 05:22 Sent To  
Notes
2019-09-13 05:23:316/21/19, 9/13/19 (FOLLOW UP) EMAILED Z.TODD, PE RE:
 DIGITAL SIGNATURE, PENDING RESPONSE
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-12-30 Cont ID  
Sent By aaponte Date 2019-12-30 Time 10:50 Rev Time 0.00
Received By aaponte Date 2019-12-30 Time 10:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-11-06 Cont ID  
Sent By aaponte Date 2019-11-06 Time 11:41 Rev Time 0.00
Received By aaponte Date 2019-11-06 Time 11:41 Sent To  
Notes
2019-11-06 11:43:521. NOT SATISFIED, SURVEY NOT INCLUDED IN RESUBMITTAL -
 PLEASE PROVIDE A SRUVEY OF THE PROPERTY, SURVEY SHALL
 INDICATE ALL EXISTING ELEMENTS AROUND THE WORK AREA
 (POLES, TREES, UTILITIES, ETC).
 2. NOT SATISFIED, DRWINGS INDICATE THE APRON STILL
 ENCROACHING INTO THE SIDEWALK AREA. PLEASE ADJUST APRON
 TO BE CONTAINED WITHIN THE LANDSCAPE AREA AND MAINTAIN
 THE SIDEWALK ELEVATION ACROSS THE DRIVEWAY. -SIDEWALK
 ELEVATION SHALL BE MAINTAINED CONSTANT AT THE POINT OF
 THE DRIVEWAY CROSSING. PLEASE PROVIDE A DETAIL TO
 CONFIRM DRIVEWAY WILL BE BUILT CONSIDERING THAT DETAIL.
 3. IS THE PROPOSED WORK IMPACTING ANY OF THE EXISTING
 LANDSCAPE ON SITE OR ON RIGHT-OF-WAY?
 4. NOT SATISFIED, PLEASE INSTALL A HEDGE BETWEEN THE
 DRIVEWAY AND THE SIDEWALK TO SCREEN VEHICULAR USE AREA.
 - ARE THERE ANY LANDSCAPE IMPROVEMENTS PROPOSED WITH
 THE WORK? STAFF RECOMMENDS A SMALL HEDGE TO BE LOCATED
 BETWEEN THE DROP-OFF AREA AND THE SIDEWALK TO SCREEN
 THE VEHICULAR USE AREA.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By aaponte Date 2019-08-30 Time 09:00 Rev Time 0.00
Received By aaponte Date 2019-08-30 Time 09:00 Sent To  
Notes
2019-08-30 09:25:151. PLEASE PROVIDE A SRUVEY OF THE PROPERTY, SURVEY
 SHALL INDICATE ALL EXISTING ELEMENTS AROUND THE WORK
 AREA (POLES, TREES, UTILITIES, ETC).
 2. SIDEWALK ELEVATION SHALL BE MAINTAINED CONSTANT AT
 THE POINT OF THE DRIVEWAY CROSSING. PLEASE PROVIDE A
 DETAIL TO CONFIRM DRIVEWAY WILL BE BUILT CONSIDERING
 THAT DETAIL.
 3. IS THE PROPOSED WORK IMPACTING ANY OF THE EXISTING
 LANDSCAPE ON SITE OR ON RIGHT-OF-WAY?
 4.ARE THERE ANY LANDSCAPE IMPROVEMENTS PROPOSED WITH
 THE WORK? STAFF RECOMMENDS A SMALL HEDGE TO BE LOCATED
 BETWEEN THE DROP-OFF AREA AND THE SIDEWALK TO SCREEN
 THE VEHICULAR USE AREA.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.