Plan Review Details - Permit 19080426
Plan Review Stops For Permit 19080426
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 07:07 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 06:08 Sent To  
Notes
2019-08-20 07:07:14BUILT IN 1988.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By pvalenti Date 2019-09-10 Time 10:48 Rev Time 0.00
Received By pvalenti Date 2019-09-10 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 07:05 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 06:08 Sent To  
Notes
2019-08-20 07:05:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080426
 ADD: 1400 CENTREPARK BLVD. SUITE: 130
 CONT: CHANDLER CONSTRUCTION CO.
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MON. 20/2019
 ACTION: DENIED
  
 1) SHEET A-2SHOWS A CONFERENCE ROOM # 311, WITH 2
 MANUALLY SLIDING DOORS. THE ROOM IS 525 SQUARE FEET /
 15 SQ. FT. PER OCC. = 35 OCCUPANTS. PLEASE NOTE
 EXCEPTION # 9 IN OTHER THAN GROUP H OCCUPANCIES,
 MANUALLY OPERATED HORIZONTAL SLIDING DOORS ARE
 PERMITTED IN A MEANS OF EGRESS FROM SPACES WITH AN
 OCCUPANT LOAD OF 10 OR LESS. 2017 FBC-B 1010.1.2. DOOR
 SWING.
 IT WOULD APPEAR THAT AT LEAST ONE OF THE CONFERENCE
 ROOM DOORS (EGRESS DOOR) WILL NEED TO BE A SWING DOOR
 TO SHOW COMPLIANCE WITH THE CODE.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-11 Cont ID  
Sent By jpearson Date 2019-08-11 Time 10:26 Rev Time 0.00
Received By jpearson Date 2019-08-11 Time 10:26 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-08-11 Cont ID  
Sent By jpearson Date 2019-08-11 Time 10:23 Rev Time 0.00
Received By jpearson Date 2019-08-11 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By pleduc Date 2019-09-09 Time   Rev Time 0.00
Received By pleduc Date 2019-09-09 Time 13:13 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By pleduc Date 2019-08-13 Time   Rev Time 0.00
Received By pleduc Date 2019-08-13 Time 15:10 Sent To  
Notes
2019-08-13 15:28:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE A CONFERENCE ROOM WITH AN ENTIRE
 GLASS WALL WITH SLIDING GLASS DOORS ON EACH END.
  
 PER NFPA 101, CH 12 AND CH 7 HOW WILL THE GLASS BE
 PROTECTED FROM BEING CONFUSED WITH A DOOR?
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL
 ENTRANCE THAT IS
 REQUIRED TO SERVE AS AN EXIT SHALL BE DESIGNED AND
 CONSTRUCTED SO
 THAT THE PATH OF EGRESS TRAVEL IS OBVIOUS AND DIRECT.
 WINDOWS THAT,
 BECAUSE OF THEIR PHYSICAL CONFIGURATION OR DESIGN AND
 THE MATERIALS
 USED IN THEIR CONSTRUCTION, HAVE THE POTENTIAL TO BE
 MISTAKEN FOR
 DOOR OPENINGS SHALL BE MADE INACCESSIBLE TO THE
 OCCUPANTS BY
 BARRIERS OR RAILINGS.
  
  
  
 2) TWO SLIDING GLASS DOORS ARE INDICAED AT THE
 CONFERENCE ROOM.
  
 THE DOOR SCHEDULE INDICATES HARDWARE AS TBD
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.1.4 SWING AND FORCE TO OPEN.
 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY
 DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR
 PIVOTED-SWINGING TYPE, AND SHALL BE INSTALLED TO BE
 CAPABLE OF
 SWINGING FROM ANY POSITION TO THE FULL REQUIRED WIDTH
 OF THE
 OPENING IN WHICH IT IS INSTALLED, UNLESS OTHERWISE
 SPECIFIED AS
 FOLLOWS:
  
 (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE
 PERMITTED UNDER
 ANY OF THE FOLLOWING CONDITIONS:
 (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND
 CORRECTIONAL OCCUPANCIES, AS PROVIDED IN CHAPTERS 22
 AND 23, SHALL BE PERMITTED.
 (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR
 FOLDING DOOR ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL
 BE PERMITTED.
 (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43,
 HORIZONTAL-SLIDING DOOR ASSEMBLIES SERVING A ROOM OR
 AREA WITH AN OCCUPANT LOAD OF FEWER THAN 10 SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE
 MET:
 I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH
 HAZARD CONTENTS.
 II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER
 SIDE WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN
 THE DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30
 LBF (133 N) TO SET THE DOOR LEAF IN MOTION AND IS NOT
 MORE THAN 15 LBF (67 N) TO CLOSE THE DOOR ASSEMBLY
 OR OPEN IT TO THE MINIMUM REQUIRED WIDTH.
 IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE
 PROTECTION RATING, AND, WHERE RATED, IS SELF-CLOSING
 OR AUTOMATIC-CLOSING BY MEANS OF SMOKE DETECTION
 IN ACCORDANCE WITH 7.2.1.8 AND IS INSTALLED IN
 ACCORDANCE WITH NFPA 80, STANDARD FOR FIRE
 DOORS AND OTHER OPENING PROTECTIVES.
 V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE SELFLATCHING
 HAVE A LATCH OR OTHER MECHANISM THAT
 ENSURES THAT THE DOOR LEAF WILL NOT REBOUND INTO A
 PARTIALLY OPEN POSITION IF FORCEFULLY CLOSED.
  
 PLEASE PROVIDE DETAILS AND/OR A NOTE OF COMPLIANCE WITH
 FUTURE SPECIFICATIONS TO BE SUBMITTED IN COMPLIANCE.
  
  
  
 3) THE DOOR SCHEDULE INDICATES HARDWARE AS TBD
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 PLEASE PROVIDE DETAILS AND/OR A NOTE OF COMPLIANCE WITH
 FUTURE SPECIFICATIONS TO BE SUBMITTED IN COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-10 Cont ID  
Sent By pvalenti Date 2019-09-10 Time 10:49 Rev Time 0.00
Received By pvalenti Date 2019-09-05 Time 11:40 Sent To  
Notes
2019-09-06 11:40:24RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-26 Cont ID  
Sent By tklarge Date 2019-08-26 Time 14:53 Rev Time 0.00
Received By tklarge Date 2019-08-08 Time 15:02 Sent To  
Notes
2019-08-09 15:02:49B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 07:05 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 06:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-08-23 Cont ID  
Sent By hmoser Date 2019-08-23 Time 13:11 Rev Time 0.00
Received By hmoser Date 2019-08-22 Time 12:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-26 Cont ID  
Sent By tklarge Date 2019-08-26 Time 14:53 Rev Time 0.00
Received By tklarge Date 2019-08-26 Time 13:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-20 Cont ID  
Sent By jroach Date 2019-08-20 Time 10:23 Rev Time 0.00
Received By jroach Date 2019-08-20 Time 10:23 Sent To  
Notes
***NONE***