Plan Review Details - Permit 19080396
Plan Review Stops For Permit 19080396
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2019-10-03 Cont ID  
Sent By pvalenti Date 2019-10-03 Time 16:17 Rev Time 0.00
Received By pvalenti Date 2019-10-03 Time 16:17 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-09-30 Cont ID  
Sent By jwitmer Date 2019-09-30 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2019-09-30 Time 12:35 Sent To  
Notes
2019-09-30 13:10:092ND REVIEW: , ASBESTOS COMMERCIAL: PLEASE PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON
 LETTERHEAD, STATING THAT THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE FOLLOWED
 AND THAT NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
  
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 837-5900 ASBESTOS PROGRAM COORDINATOR
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2019-08-26 Time 12:01 Sent To  
Notes
2019-08-26 13:30:10IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO
 ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY
 TO COMPLY WITH THE STATE & FEDERAL ASBESTOS
 REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61-
 NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS
 SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: *
 DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-03 Cont ID  
Sent By pvalenti Date 2019-10-03 Time 16:17 Rev Time 0.00
Received By pvalenti Date 2019-10-03 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-30 Cont ID  
Sent By jwitmer Date 2019-09-30 Time 13:08 Rev Time 0.00
Received By jwitmer Date 2019-09-30 Time 12:36 Sent To  
Notes
2019-09-30 13:08:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080396
 ADD: 2425 PRESIDENTIAL WAY SUITE: 403
 CONT: USHER AND ASSOCIATES
 TEL: 561-543-2185
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 30/ 2019
 ACTION: DENIED
  
 1A-B) COMPLIED.
  
 2) 2ND REVIEW SAME COMMENTS. SPOKE WITH THE CONTRACTOR
 TODAY ABOUT THE PRODUCT SAM 90 VERSES SUPER SAM 125.
 SAM 90 DOES NOT MEET THE IIC RATING OF 50 ON A 6 INCH
 CONCRETE SLAB, NO DROPPED CEILING. PLEASE NOTE THE
 SUBMITTED SALES BROCHURE DOES NOT HAVE THE CORRECT DATA
 AND TESTING RESULTS TO OBTAIN A PERMIT. WE HAVE TO DATE
 NOT PERMITTED THE PRODUCT SAM 90 CONTROL MEMBRANE. WE
 DO HAVE THE ACTUAL TEST RESULT THAT HAVE PASSED FOR
 SUPER SAM125.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO
 ADVISE YOU OF THE OWNERS OR OPERATORS RESPONSIBILITY TO
 COMPLY WITH THE STATE & FEDERAL ASBESTOS REGULATIONS,
 INCLUDING SECTION 376.60 F. S. AND CFR 61- NESHAP
 REQUIREMENTS. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT
 FROM THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 837-5900 ASBESTOS PROGRAM COORDINATOR
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2019-08-26 Time 12:01 Sent To  
Notes
2019-08-26 13:29:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080396
 ADD: 2425 PRESIDENTIAL WAY SUITE: 403
 CONT: O & D TOTAL HOME REPAIR CORP.
 TEL: 561-969-3121
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 26/ 2019
 ACTION: DENIED
  
 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA:
 1A) THE PLAN INDICATES THE CONSTRUCTION TYPE AS V-B.
 PLEASE NOTE THIS SUITE IS LOCATED IN A HIGHRISE
 BUILDING AND BUILDING TYPE IS TYPE I-A. SEE THE 2017
 FBC-B TABLE 504.4.
  
 1B) THE SHEET 1-1 UNDER THE HEADING OF DESIGN CRITERIA
 LIST THE OCCUPANCY TYPE AS A R-3. PLEASE NOTE MOST R-3
 ARE SINGLE FAMILY RESIDENCES. FEW R-3 ARE A MIXED
 OCCUPANCY WHERE IS A BUSINESS OR MERCANTILE ON THE 1ST
 FLOOR AND A SINGLE DWELLING UNIT ON THE 2ND FLOOR.
 APARTMENT BUILDINGS AND CONDOMINIUMS THAT ARE PRIMARILY
 PERMANENT IN NATURE ARE CONSIDERED OCCUPANCY TYPE R2.
 PLEASE REVIEW THE 2017 FBC-B 310.2.
  
 2) PLEASE NOTE THE SUBMITTED SALES BROCHURE DOES NOT
 HAVE THE CORRECT DATA AND TESTING RESULTS TO OBTAIN A
 PERMIT. WE HAVE TO DATE NOT PERMITTED THE PRODUCT SAM
 90 CONTROL MEMBRANE. WE DO HAVE THE ACTUAL TEST RESULT
 THAT HAVE PASSED FOR SUPER SAM125.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO
 ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY
 TO COMPLY WITH THE STATE & FEDERAL ASBESTOS
 REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61-
 NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS
 SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: *
 DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By jpearson Date 2019-08-28 Time 15:06 Rev Time 0.00
Received By jpearson Date 2019-08-28 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By pleduc Date 2019-09-20 Time   Rev Time 0.00
Received By pleduc Date 2019-09-20 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-13 Cont ID  
Sent By pleduc Date 2019-08-13 Time   Rev Time 0.00
Received By pleduc Date 2019-08-13 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-03 Cont ID  
Sent By pvalenti Date 2019-10-03 Time 16:18 Rev Time 0.00
Received By pvalenti Date 2019-10-02 Time 12:29 Sent To  
Notes
2019-10-03 12:29:28RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-18 Time 14:27 Sent To  
Notes
2019-09-25 06:18:45TO HM DESK
  
2019-09-19 14:27:47B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-29 Cont ID  
Sent By jesmith Date 2019-08-29 Time 15:39 Rev Time 0.00
Received By jesmith Date 2019-08-29 Time 15:39 Sent To  
Notes
2019-08-08 13:57:52B06

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-09-25 Cont ID  
Sent By cmontell Date 2019-09-25 Time 06:23 Rev Time 0.00
Received By cmontell Date 2019-09-25 Time 06:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By jesmith Date 2019-09-24 Time 16:11 Rev Time 0.00
Received By jesmith Date 2019-09-24 Time 15:59 Sent To  
Notes
2019-09-24 16:11:44PLUMBING COMMEMTS: APPROVED W/PROVISO
 REFERENCE PLAN SHEET P-1:
 1. HORIZONTAL FIXTURE DRAIN FROM WASHER TO EXISTING
 WASTE STACK SHALL BE 3 INCH DIAMETER PER STUDOR DESIGN
 MANUAL, FIGURE 11, OR PROVIDE A CONVENTIONAL INDIVIDUAL
 VENT AND CONNECT TO VENT STACK IN LIEU OF STUDOR VENT.
 2. PROVIDE VERTICAL RISE ON RELIEF (BACK) VENT PER FBC
 PL 905.3 AND 905.4.
 3. A 1ST ROUGH PLUMBING INSPECTION IS REQUIRED PRIOR TO
 SHOWER PAN INSTALLATION TO DETERMINE THAT FLOOR
 PENETRATIONS ARE PROPERLY FIRE SAFED. SEE REDLINED
 COMMENTS.
 4. WASHER SHUT OFF VALVES SHALL BE ACCESSIBLE PER FBC
 PL 606.2.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-29 Cont ID  
Sent By jesmith Date 2019-08-29 Time 15:37 Rev Time 0.00
Received By jesmith Date 2019-08-29 Time 14:02 Sent To  
Notes
2019-08-29 15:37:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMEMTS: DENIED
  
 1 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 2. RE: PLAN SHEET P-1; SANITARY RISER DIAGRAM. IF THE
 EXISTING WASHER IS CONNECTED TO A TWO STACK WITH REVENT
 SYSTEM THEN (1) NEW WASHER DRAIN SHALL CONNECT TO
 EXISTING WASTE STACK, NOT TO THE VENT AND (2) A VENT
 SHALL BE PROVIDED AT THE POINT THAT THE TRAPPED WASHER
 DRAIN CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL
 CONNECT TO THE EXISTING VENT STACK (FBC PL 905.1). IF
 THE EXISTING WASHER CONNECTS TO A SINGLE PIPE WASTE
 STACK VENT FBC PL 913), THEN A VENT SHALL BE PROVIDED
 AT THE POINT THAT THE TRAPPED CLOTHES WASHER DRAIN
 CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL CONNECT
 TO AN EXISTING BRANCH VENT OR VENT STACK (FBC PL
 905.1). IF AN EXISTING BRANCH VENT OR VENT STACK IS NOT
 AVAILABLE, THE NEW HORIZONTAL DRAIN SHALL BE SIZED 3?
 (AS REQUIRED BY MANUFACTURER OF AIR ADMITTANCE VALVE
 INSTALLATION GUIDE) TO THE POINT OF HORIZONTAL TO
 VERTICAL THEN CAN BE 2? SIZE. AN AIR ADMITTANCE VALVE
 SHALL BE INSTALLED ABOVE THE POINT THAT THE TRAPPED
 CLOTHES WASHER DRAIN CHANGES FROM HORIZONTAL TO
 VERTICAL. PER WPB FBC 107.2.1, CONFIRM WHICH TYPE OF
 WASTE AND VENT SYSTEM IS INVOLVED, THE SIZES OF THE
 EXISTING AND SHOW ON THE SANITARY RISER DIAGRAM.
 SPECIFY THE TYPE OF MATERIAL USED FOR NEW AND EXISTING
 PIPING, I.E. PVC DWV, CAST IRON, ETC.
  
 3. RE: PLAN SHEET P-1; SHOWER DETAIL. PROVIDE ON THE
 ELEVATION CUT THROUGH DETAIL OF THE SHOWER COMPARTMENT
 (FBC PL 417.5 THROUGH 417.5.2.6) THE TYPE OF LINER, THE
 HEIGHT ABOVE THE CURB IT EXTENDS, EXISTING SLAB
 THICKNESS AND THE TYPE OF MATERIAL USED FOR NEW AND
 EXISTING PIPING, I.E. PVC DWV, CAST IRON, ETC.
  
 4. PROVIDE UL FIRE SAFING DETAIL(S) FOR THROUGH THE
 FLOOR PIPE PENETRATIONS. COMPLY WITH THE REQUIREMENTS
 OF FBC CHAPTER 7.
  
 5. PROVIDE ANTI-SCALD VALVES IN ALL SHOWERS PER FBC PL
 424.3.
  
 6. PROVIDE WATER HAMMER ARRESTORS CONFORMING TO ASSA
 1010 AT DISHWASHER, REFRIGERATOR ICE LINE AND CLOTHES
 WASHER PER FBC PL 604.9
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080396 2425 PRESIDENTIAL WAY 403
  