2019-08-09 16:39:51 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19080085 |
| REVIEWED: AUGUST 9, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 1006.2.1 FBC TABLE[B] MAXIMUM COMMON PATH OF EGRESS |
| TRAVEL DISTANCE. |
| -SHOW THE MAXIMUM COMMON PATH FROM TABLE 1006.2.1. ON |
| THE LIFE SAFETY SHEET. |
| |
| 2) 3006.3 HOISTWAY OPENING PROTECTION. |
| ARE THE ELEVATORS IN AN ELEVATOR LOBBY, OR ARE THEY |
| PRESSURIZED? |
| IF THIS IS AN ELEVATOR LOBBY PLEASE ADD DETAILS OF HOW |
| IT COMPLIES. |
| |
| 801.2 ALTERATION LEVEL 1 COMPLIANCE. IN ADDITION TO THE |
| REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY |
| WITH THE |
| REQUIREMENTS OF CHAPTER 7. |
| 701.2 CONFORMANCE. AN EXISTING BUILDING OR PORTION |
| THEREOF |
| SHALL NOT BE ALTERED SUCH THAT THE BUILDING BECOMES |
| LESS SAFE |
| OR ENERGY EFFICIENT THAN ITS EXISTING CONDITION. |
| -THE REASON I BRING UP EGRESS IS THAT THE DEMO PLAN AND |
| PROPOSED FLOOR PLAN HAVE SOME VARIATION FROM WHAT WAS |
| PERMITTED IN PERMIT #07050509 WHEN THE WHOLE FLOOR WAS |
| RENOVATED. I DO NOT SEE ANY PERMITS AFTER THAT ONE SO I |
| AM USING THOSE PERMIT DRAWINGS AS A BASE FOR THE |
| CURRENT CHANGES. THOSE PLANS SHOW MORE OPTIONS FOR |
| EGRESS AND HAD A DOOR FROM THE BREAK ROOM INTO CORRIDOR |
| WHERE EXIT STAIR IS LOCATED. |
| |
| THE BUILDING OFFICIAL CAN ACCEPT VARIATIONS FROM CODE |
| ON EXISTING BUILDINGS, BUT HE IS FOCUSED ON AREAS WHERE |
| ELEVATORS ARE IN THE PATH OF EGRESS AND IN THIS CASE |
| THE POINT WHERE TWO OPTIONS FOR EGRESS OCCURS IS RIGHT |
| NEXT TO THE ELEVATORS. |
| PLEASE REVIEW AND FEEL FREE TO CALL AND DISCUSS OR |
| SET-UP A MEETING WITH THE BUILDING OFFICIAL. |
| |
| ALSO, I NOTICED THAT YOU DON?T SHOW THE WATER FOUNTAINS |
| THAT ARE SHOWING IN PERMIT #07050509 OUTSIDE OF |
| BATHROOMS. |
| PLEASE SHOW IF THEY ARE THERE SINCE WE DID NOT INCLUDE |
| A PLUMBING STOP OR LET ME KNOW WHY THERE ARE NONE. I |
| FIGURED THAT THE FOCUS WAS OFFICES AND NOT ALL DETAILS |
| WERE INCLUDED, BUT THIS AREA IS IMPORTANT BECAUSE WE |
| ARE LOOKING AT THAT AREA FOR CONFLICTS IN APPROVED |
| PLANS VERSES WHAT SHOWS ON THE NEW PLANS. |
| |
| WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |