Plan Review Details - Permit 19080023
Plan Review Stops For Permit 19080023
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By rmcdouga Date 2019-09-17 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2019-09-17 Time 16:45 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By rmcdouga Date 2019-08-13 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2019-08-13 Time 07:33 Sent To  
Notes
2019-08-13 07:44:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) AT LEAST ONE OF THE GENERATOR PAD ENGINEERED
 DRAWINGS IS REQUIRED TO HAVE THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL AFFIXED TO THE DRAWING.
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND
 SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MUST BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-16 Cont ID  
Sent By jleahy Date 2019-08-16 Time 08:09 Rev Time 0.00
Received By jleahy Date 2019-08-16 Time 08:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-10-10 Cont ID  
Sent By lcrespo Date 2019-10-10 Time 17:55 Rev Time 0.00
Received By lcrespo Date 2019-10-10 Time 17:55 Sent To  
Notes
2019-10-10 17:56:4510/10/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-09-16 Cont ID  
Sent By lcrespo Date 2019-09-16 Time 13:10 Rev Time 0.00
Received By lcrespo Date 2019-09-16 Time 13:09 Sent To  
Notes
2019-09-16 13:17:5409/16/2019 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. THE SECOND REQUEST, THIS COPY FOR THE TIE-DOWN OF
 SIGNATURE OR SEAL IS NOT IN ACCORDANCE WITH FLORIDA
 ADMINISTRATIVE CODE PER 61G15-23.001, FLORIDA STATUTE
 471. THE PROVIDED DOCUMENT FOR YOUR TIE-DOWN HAS SEAL
 AND SIGNATURE IS A COPY SIGNATURE AND NOT AN ORIGINAL
 WET STAMP.
  
 2. THE METHOD OF REQUIRED PROTECTION FOR THE LP TANK
 AND APPURTENANCES PER NFPA 58 IS MISSING INFORMATION.
 THE DETAIL ONLY SHOWS A COVER AND MUST SUBMIT A BASE
 AND COVER FOR VEHICLE TRAFFIC PROTECTION AS IT IS BELOW
 GROUND IT SHALL BE CONSTRUCTED AND PROTECTED PER NFPA
 58 SEC.3-2.2.7 (H). THE HOUSING FOR THE LID IS ALSO
 REQUIRED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP
 TANK TIE-DOWN METHOD AND IF YOU ARE USING FLAT STRAPS
 OR ISOLATION CABLES, IF ISOLATION CABLES, PLEASE
 CLARIFY HOW IS IT PROTECTED FOR THE LP TANK AND
 APPURTENANCES PER THE NFPA 58. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE DOCUMENT SUBMITTED ARE NOT TO CODE COMPLIANCE
 AND CONTINUE TO HAVE NO SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES, AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. PLEASE MAKE AN APPOINTMENT TO DISCUSS THESE
 ITEMS THAT SHALL CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-08-09 Cont ID  
Sent By lcrespo Date 2019-08-09 Time 15:49 Rev Time 0.00
Received By lcrespo Date 2019-08-09 Time 15:49 Sent To  
Notes
2019-08-09 16:01:2008/09/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. THE COPY OF SIGNATURE OR SEAL IS NOT IN ACCORDANCE
 WITH FLORIDA ADMINISTRATIVE CODE PER 61G15-23.001,
 FLORIDA STATUTE 471. PLEASE PROVIDE THE DOCUMENT FOR
 YOUR TIE DOWN WITHOUT A SEAL AND SIGNATURE, NO COPIES.
  
 2. TABLE FOR NFPA IS NOT LEGIBLE, PLEASE PROVIDE COPIES
 THAT ARE NOT GRAYED OUT WHICH MAKE THE DIFFICULT TO
 READ, WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SPECIFICATIONS FOR REGULATOR ARE DIFFICULT TO READ
 AS THEY ARE BLURRY AND FADED OUT, PLEASE PROVIDE CLEAR
 COPIES, IDENTIFY WHICH REGULATOR PLEASE, WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. THE LP TANK IS BELOW GROUND, PLEASE SHOW THE METHOD
 OF REQUIRED PROTECTION FOR THE LP TANK AND
 APPURTENANCES PER NFPA 58. THE TANK WILL NEED A COVER
 FOR VEHICLE TRAFFIC PROTECTION AS IT IS BELOW GROUND IT
 SHALL BE CONSTRUCTED AND PROTECTED PER NFPA 58
 SEC.3-2.2.7 (H). WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE.
 COMPLY WITH NFPA 58 SEC. 6.6.6.1.
  
 6. PLEASE SHOW UNION ON THE REGULATOR ON ISOMETRIC,
 UNION / 1' OF EITHER SIDE 2017 PBC FG SEC. 410.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-10 Cont ID  
Sent By lcrespo Date 2019-10-10 Time 17:56 Rev Time 0.00
Received By lcrespo Date 2019-10-10 Time 15:55 Sent To  
Notes
2019-10-10 15:55:36RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-17 Cont ID  
Sent By rmcdouga Date 2019-09-17 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2019-09-12 Time 13:44 Sent To  
Notes
2019-09-13 13:44:17RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-16 Cont ID  
Sent By jleahy Date 2019-08-16 Time 08:09 Rev Time 0.00
Received By jleahy Date 2019-08-01 Time 13:44 Sent To  
Notes
2019-08-02 13:44:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-07 Cont ID  
Sent By ajones Date 2019-08-07 Time 11:41 Rev Time 0.00
Received By ajones Date 2019-08-07 Time 11:41 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved