2019-08-05 14:51:32 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19071570 ROOFING SUB FOR MASTER |
| #18060562 |
| REVIEWED: AUGUST 5, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| [RAS 117]PROVIDE ENGINEERING FOR ENHANCED ATTACHMENT AS |
| STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS |
| #11. ZONE 3 WILL EXCEED THE MAXIMUM DESIGN PRESSURE OF |
| -67.5 AND THAT IS WHY ENGINEERING IS REQUIRED FOR THE |
| MECHANICAL ATTACHMENT OF INSULATION IN THAT ZONE. |
| ALSO, PROVIDE THE PRODUCT APPROVAL FOR THE INSULATION |
| BOARDS WITH INSTALLATION INSTRUCTIONS. |
| |
| INFORMATIONAL: |
| I REVIEWED PLANS AND ENERGY CALCULATIONS FROM MASTER |
| PERMIT 18060562 TO SEE HOW INSULATION WAS PROVIDED, THE |
| PLANS CALL FOR R-30 ABOVE THE DECK, BUT THE ENERGY |
| CALCULATIONS CALL FOR R-19 BATT. PLEASE REVIEW AND |
| REVISE THE PLANS OR ENERGY CALC FOR WHAT IS BEING |
| INSTALLED IN 18060562. THIS COULD CAUSE THE BUILDING |
| FINALS TO FAIL. |
| |
| NOTES: |
| ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |