Plan Review Details - Permit 19071544
Plan Review Stops For Permit 19071544
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By rmcdouga Date 2019-09-13 Time 18:21 Rev Time 0.00
Received By rmcdouga Date 2019-09-13 Time 18:21 Sent To  
Notes
2019-09-13 18:22:41ASBESTOS REPORT WAS NEGATIVE FOR ALL MATERIALS THAT
 WERE TESTED.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 13:46 Sent To  
Notes
2019-08-05 13:46:30ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By jwitmer Date 2019-09-16 Time 06:40 Rev Time 0.00
Received By jwitmer Date 2019-09-13 Time 18:27 Sent To  
Notes
2019-09-16 06:40:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071544
 ADD: 777 S FLAGLER DR. 19TH FLOOR
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 16/2019
 ACTION: BUILDING PROVISO
  
 I SPOKE WITH CHIEF MECHANICAL INSPECTOR HAROLD MOSER
 ABOUT THE ELEVATOR PRESSUREIZATION PERMIT.
 HE INDICATED WORK IN PROGRESS FOR THIS PERMIT. A
 PROVISO THAT THE ELEVATOR PRESSUREIZATION PERMIT TO
 BE FINALED OUT BEFORE THE TENANT FIT UP CAN GET A
 CERTIFICATE OF COMPLETION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 13:45 Sent To  
Notes
2019-08-05 14:28:112017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071544
 ADD: 777 S FLAGLER DR. 19TH FLOOR
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 05/2019
 ACTION: DENIED
  
 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 2) SHEET A119 19TH FLOOR DEMOLITION PLAN IT WOULD
 APPEAR THE ELEVATOR LOBBY DOORS ARE BEING REMOVED. THE
 SYMBOLS SHEET A001 GENERAL NOTES AND SYMBOLS DOES NOT
 HAVE A SYMBOL FOR DOOR REMOVAL BUT A DOUBLE DASHED LINE
 DOES REPRESENT THE REMOVAL OF WALLS.
 2017 EXISTING BUILDING CODE 803.2.2 SUPPLEMENTAL SHAFT
 AND FLOOR OPENING ENCLOSURE REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF
 THAT FLOOR AREA, THE ENCLOSURE REQUIREMENTS OF SECTION
 803.2 SHALL APPLY TO VERTICAL OPENINGS OTHER THAN
 STAIRWAYS THROUGHOUT THE FLOOR.
  
 2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 1.EXIT ACCESS THROUGH AN ENCLOSED ELEVATOR LOBBY IS
 PERMITTED. ACCESS TO NOT LESS THAN ONE OF THE REQUIRED
 EXITS SHALL BE PROVIDED WITHOUT TRAVEL THROUGH THE
 ENCLOSED ELEVATOR LOBBIES REQUIRED BY SECTION 3006.
 WHERE THE PATH OF EXIT ACCESS TRAVEL PASSES THROUGH AN
 ENCLOSED ELEVATOR LOBBY, THE LEVEL OF PROTECTION
 REQUIRED FOR THE ENCLOSED ELEVATOR LOBBY IS NOT
 REQUIRED TO BE EXTENDED TO THE EXIT UNLESS DIRECT
 ACCESS TO AN EXIT IS REQUIRED BY OTHER SECTIONS OF THIS
 CODE.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By jpearson Date 2019-09-13 Time 14:46 Rev Time 0.00
Received By jpearson Date 2019-09-13 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By jpearson Date 2019-08-13 Time 15:43 Rev Time 0.00
Received By jpearson Date 2019-08-13 Time 15:43 Sent To  
Notes
2019-08-13 15:43:44ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO
 [email protected] AND CC [email protected] AND
 [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-04 Cont ID  
Sent By pleduc Date 2019-09-04 Time   Rev Time 0.00
Received By pleduc Date 2019-09-04 Time 10:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-06 Cont ID  
Sent By pleduc Date 2019-08-06 Time   Rev Time 0.00
Received By pleduc Date 2019-08-06 Time 10:46 Sent To  
Notes
2019-08-06 10:59:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE AN ELEVATOR LOBBY WITH THE DOORS
 TO THE LOBBY BEING REMOVED.
  
 PLEASE CONDUCT A BUILDING LIFE SAFETY FEATURE REVIEW TO
 DETERMINE IF REMOVING THE ELEVATOR LOBBY DOES NOT
 NEGATIVELY AFFECT THE LIFE SAFETY OF THE REMAINDER OF
 THE BUILDING.
  
 IS THE ELEVATOR AND STAIRWELL PRESSURIZED?
  
 THE LOBBY MAY NEED TO MAINTAINED UNTIL NEW CONSTRUCTION
 IS BEGUN AND CREATE THE NEW LOBBY IMMEDIATELY.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-28 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-08-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-30 Time 10:34 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 14:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By jpearson Date 2019-09-13 Time 14:47 Rev Time 0.00
Received By jpearson Date 2019-09-13 Time 14:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By jpearson Date 2019-08-13 Time 15:42 Rev Time 0.00
Received By jpearson Date 2019-08-13 Time 15:42 Sent To  
Notes
2019-08-13 15:43:24DIGITAL SIGNATURES FOR THIS SUBMISSION OK. NEXT
 SUBMISSION WILL NEED TO BE REVIEWED. WPB FBC 107.1