Plan Review Details - Permit 19071504
Plan Review Stops For Permit 19071504
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-28 Cont ID  
Sent By jwitmer Date 2020-01-28 Time 13:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 10:04 Sent To  
Notes
2019-08-20 10:30:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071504
 ADD: 600 BANYAN
 CONT: GAST
 TEL: 561-281-1001
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) THE SUBMITTED PERMIT IS VEHICLE GAT MODIFICATIONS.
 SHEET 002-A-101:
 1A) NEW CONSTRUCTION NOTE # 6 INDICATES NEW GATE
 ASSEMBLIES. THE NEW GATE ASSEMBLIES WILL NEED TO SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 3110.3.
 VEHICULAR GATES INTENDED FOR AUTOMATION SHALL BE
 DESIGNED, CONSTRUCTED AND INSTALLED TO COMPLY WITH THE
 REQUIREMENTS OF ASTM F2200. PLEASE PROVIDE DETAILED
 DRAWINGS SHOWING HOW COMPLIANCE WITH THIS STANDARD WILL
 BE ACHIEVED.
  
 1B) NEW CONSTRUCTION NOTE # 3 INDICATES NEW SLIDE GATE
 OPERATORS. THE PROPOSED NEW OPERATORS WILL NEED TO SHOW
 COMPLIANCE WITH 2017 FBC-B SECTION 3110.4 VEHICULAR
 GATE OPENERS. VEHICULAR GATE OPENERS, WHERE PROVIDED,
 SHALL BE LISTED IN ACCORDANCE WITH UL 325.
  
 2) NEW CONSTRUCTION NOTE # 3 INDICATES NEW SLIDE GATE
 OPERATORS WILL NEED AN ADDITIONAL ELECTRICAL PERMIT AS
 WELL AS THE BUILDING PERMIT. PERMITS REQUIRED. W 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 ADMINISTRATIVE CODE 105.1 REQUIRED
 PERMITS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-01 Cont ID  
Sent By fgiaquin Date 2020-02-01 Time 11:29 Rev Time 0.00
Received By fgiaquin Date 2020-01-30 Time 07:36 Sent To  
Notes
2020-02-01 11:30:12SEPARATE ACCESS CONTROL PERMIT REQUIRED FBC 105.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-11 Cont ID  
Sent By fgiaquin Date 2019-08-11 Time 11:20 Rev Time 0.00
Received By fgiaquin Date 2019-08-11 Time 10:33 Sent To  
Notes
2019-08-11 11:20:04ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. REMOVAL AND RELOCATION/REINSTALLATION OF CARD
 READERS FOR ACCESS CONTROL WILL REQUIRE A SEPARATE
 ACCESS CONTROL PERMIT. FBC 105.1
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 NO ELECTRICAL PLAN SUBMITTED FOR REPLACEMENT OF NEW
 GATE.
  
 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF GATE AND
 ALL ASSOCIATED MATERIALS AND EQUIPMENT. FBC 107.2.1 NEC
 90.7, 110.2, 110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-06 Cont ID  
Sent By pleduc Date 2019-08-06 Time   Rev Time 0.00
Received By pleduc Date 2019-08-06 Time 16:23 Sent To  
Notes
2019-08-06 16:24:25A FIRE KNOX KEY SWITCH IS RECOMMENDED FOR 24HR
 EMERGENCY ACCESS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-01 Cont ID  
Sent By fgiaquin Date 2020-02-01 Time 11:31 Rev Time 0.00
Received By fgiaquin Date 2020-01-17 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-29 Cont ID  
Sent By lmarchan Date 2019-08-29 Time 16:40 Rev Time 0.00
Received By lmarchan Date 2019-08-02 Time 16:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 10:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2019-08-29 Cont ID  
Sent By aaponte Date 2019-08-29 Time 16:36 Rev Time 0.00
Received By aaponte Date 2019-08-29 Time 16:36 Sent To  
Notes
***NONE***