Plan Review Details - Permit 19071475
Plan Review Stops For Permit 19071475
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-07 Cont ID  
Sent By dbattles Date 2019-08-07 Time 08:42 Rev Time 0.00
Received By dbattles Date 2019-08-07 Time 08:42 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By jpearson Date 2019-11-25 Time 11:08 Rev Time 0.00
Received By jpearson Date 2019-11-25 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By jleahy Date 2019-08-20 Time 08:37 Rev Time 0.00
Received By jleahy Date 2019-08-20 Time 08:37 Sent To  
Notes
2019-08-20 08:43:24FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE TO LOW SUBMIT DOCUMENTATION SIGNED CONTRACT
 FOR WORK INVOLVED PLEASE READ FBC SECTION BELOW.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SITE PLAN NOT INCLUDED WITH THIS APPLICATION. ONE
 INCLUDED WITH PERMIT 19071465 SHOWS FOUR SIGNS HOW MANY
 ARE COVERED BY THIS PERMIT?
  
 3) ELECTRICAL DISCONNECT PER 600.6(A)(1) NOT SHOWN.
  
 4) ELECTRICAL PERMIT FOR TIMECLOCK AND/OR PHOTOCELL NOT
 INCLUDED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-25 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-20 Time 14:08 Sent To  
Notes
2019-11-20 14:08:23RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By jleahy Date 2019-08-20 Time 08:38 Rev Time 0.00
Received By jleahy Date 2019-07-29 Time 14:58 Sent To  
Notes
2019-07-30 14:58:41ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-01 Cont ID  
Sent By ajones Date 2019-08-01 Time 11:50 Rev Time 0.00
Received By ajones Date 2019-08-01 Time 11:50 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved