Plan Review Details - Permit 19071411
Plan Review Stops For Permit 19071411
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-11 Cont ID  
Sent By dbattles Date 2019-09-11 Time 15:52 Rev Time 0.00
Received By dbattles Date 2019-09-11 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 09:55 Sent To  
Notes
2019-08-05 13:36:532017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071411
 ADD: 307 EVERNIA ST. SUITE: 200
 CONT: 489 EXEMPT. NO WORK/ CHANGE OF OCCUPANCY
 TEL: 970-903-5721
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 05/ 2019
 ACTION: DENIED
  
 1) SHEET A-201:
  
 1A) DISCREPANCIES IN THE PLAN, OCCUPANT LOADS:
 1A)(1) ON THE LEFT SIDE OF THE PLAN THERE ARE 2
 CLASSROOMS WITH 265 SQ. FT. OF CLASSROOM, ONE IS LARGER
 THAN THE OTHER AND ONE HAS 13 OCCUPANTS AND THE OTHER 6
 OCCUPANTS. DISCREPANCY, 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. IT APPEARS THIS MAYBE A STAFF
 AREA WITH SINK IN A BREAK ROOM?
  
 1A)(2) THE CLASSROOM ON THE RIGHT SIDE OF THE SHEET
 INDICATES 275 SQ. FT. AND OCCUPANT LOAD OF 14. THE
 ACTUAL OCCUPANT LOAD IS 13.75, NEED TO BE ROUNDED DOWN
 TO THE NEXT WHOLE NUMBER SINCE THERE IS NO PARTS OF
 OCCUPANTS. TABLE 1004.1.2.
  
 1A)(3) THERE IS NO OCCUPANT LOAD GIVEN FOR THE LIBRARY
 AT ALL. PLEASE REFER TO THE 2017 FBC-B TABLE
 1004.1.2.
  
 1A)(4) NO OCCUPANT LOADS HAVE BEEN GIVEN TO THE
 RECEPTION AREA, WAITING AREA NOR EXISTING STORAGE ROOM,
 OR THE FILE/ COPY ROOM. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. FBC-B TABLE 1004.1.2.
  
 1B) THE PERMIT APPLICATION INDICATES THIS IS A CHANGE
 IN OCCUPANCY. SHEET A-201 INDICATES THAT THIS SPACE WAS
 USED AS A BUSINESS OCCUPANCY AND NOW IS TO BE A SCHOOL.
 PLEASE PROVIDE THE AGE OF THE STUDENTS THAT ARE GOING
 TO ATTENDING THIS SCHOOL SEE THE 2017 FBC-B SECTION
 305.1 FOR AGE GROUP FOR AN EDUCATIONAL OCCUPANCY.
  
 1C)UNDER THE HEADING OF APPLICABLE CODES LIST THE 2017
 EXISTING BUILDING CODE, LEVEL I ALTERATION. FOR A
 CHANGE OF OCCUPANCY THE CODE REQUIRES US TO USE THE
 2017 EXISTING BUILDING CODE CHAPTER 10 FOR CHANGE OF
 OCCUPANCY. SEE 2017 FBC-EXISTING BUILDING CODE SECTION
 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY.
 WHERE THE OCCUPANCY CLASSIFICATION OR GROUP OF A
 PORTION OF AN EXISTING BUILDING IS CHANGED, SECTION
 1012 SHALL APPLY.
  
 1D) THE PLAN IS SILENT AS TO OCCUPANCY SEPARATION
 REQUIREMENTS UNDER THE 2017 FBC-EXISTING BUILDING CODE
 SECTIONS 1012.1.1 WITHOUT SEPARATION OR 1012.1.1.2 WITH
 SEPARATION.
  
 1E) 2017 EXISTING BUILDING CODE 1012.1.3 CHANGE OF
 OCCUPANCY CLASSIFICATION BASED ON HAZARD CATEGORY.
  
 THE RELATIVE DEGREE OF HAZARD BETWEEN DIFFERENT
 OCCUPANCY CLASSIFICATIONS SHALL BE DETERMINED IN
 ACCORDANCE WITH THE CATEGORIES SPECIFIED IN TABLES
 1012.4, 1012.5 AND 1012.6. SUCH A DETERMINATION SHALL
 BE THE BASIS FOR THE APPLICATION OF SECTIONS 1012.4
 THROUGH 1012.7.
 PLEASE REVIEW IN THE 2017 EXISTING BUILDING CODE TABLE
 1012.4. YOU ARE GOING FROM A HIGHER HAZARD CATEGORY
 FROM BUSINESS TO AN EDUCATIONAL OCCUPANCY. THE LOWER
 THE NUMBER THE HIGHER THE HAZARD. BUSINESS BEING A 4
 TYPE HAZARD CATEGORY AND EDUCATIONAL BEING A 2 A HIGHER
 HAZARD CATEGORY.
  
 1F) 2017 EXISTING BUILDING CODE 1012.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF
 OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT
 FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER
 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES
 A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS IN ACCORDANCE WITH SECTION 907 OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED FOR NEW
 CONSTRUCTION.
  
 1G) 2017 EXISTING BUILDING CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 2017 EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
 2017 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1H) 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER
 HAZARD CATEGORY.
  
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 1012.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 EXCEPTIONS:
 1H)(1).STAIRWAYS SHALL BE ENCLOSED IN COMPLIANCE WITH
 THE APPLICABLE PROVISIONS OF SECTION 903.1.
 2017 EXISTING BUILDING CODE SECTION 903.1 EXISTING
 SHAFTS AND VERTICAL OPENINGS. EXISTING STAIRWAYS THAT
 ARE PART OF THE MEANS OF EGRESS SHALL BE ENCLOSED IN
 ACCORDANCE WITH SECTION 803.2.1 FROM THE HIGHEST WORK
 AREA FLOOR TO, AND INCLUDING, THE LEVEL OF EXIT
 DISCHARGE AND ALL FLOORS BELOW.
 1H)(2).EXISTING STAIRWAYS INCLUDING HANDRAILS AND
 GUARDS COMPLYING WITH THE REQUIREMENTS OF CHAPTER 9
 SHALL BE PERMITTED FOR CONTINUED USE SUBJECT TO
 APPROVAL OF THE CODE OFFICIAL.
 1H)(3).ANY STAIRWAY REPLACING AN EXISTING STAIRWAY
 WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE
 REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL NOT BE
 REQUIRED TO COMPLY WITH THE MAXIMUM RISER HEIGHT AND
 MINIMUM TREAD DEPTH REQUIREMENTS.
 1H)(4).EXISTING CORRIDOR WALLS CONSTRUCTED ON BOTH
 SIDES OF WOOD LATH AND PLASTER IN GOOD CONDITION OR
 1/2- INCH-THICK (12.7 MM) GYPSUM WALLBOARD SHALL BE
 PERMITTED. SUCH WALLS SHALL EITHER TERMINATE AT THE
 UNDERSIDE OF A CEILING OF EQUIVALENT CONSTRUCTION OR
 EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF NEXT
 ABOVE.
 1H)(5).EXISTING CORRIDOR DOORWAYS, TRANSOMS AND OTHER
 CORRIDOR OPENINGS SHALL COMPLY WITH THE REQUIREMENTS IN
 SECTIONS 805.5.1, 805.5.2 AND 805.5.3.
 1H)(6) .EXISTING DEAD-END CORRIDORS SHALL COMPLY WITH
 THE REQUIREMENTS IN SECTION 805.6.
  
 2) 2017 FBC-B SPECIAL DETAILED REQUIREMENTS BASED ON
 USE AND OCCUPANCY.
 401.1 DETAILED USE AND OCCUPANCY REQUIREMENTS. IN
 ADDITION TO THE OCCUPANCY AND CONSTRUCTION REQUIREMENTS
 IN THIS CODE, THE PROVISIONS OF THIS CHAPTER APPLY TO
 THE SPECIAL USES AND OCCUPANCIES DESCRIBED HEREIN.
 401.2 ADDITIONAL DESIGN CRITERIA./ 401.2.1 SCOPE.
 401.1 DETAILED USE AND OCCUPANCY REQUIREMENTS. IN
 ADDITION TO THE PROVISIONS OF THIS CHAPTER, THE
 FOLLOWING SPECIAL OCCUPANCIES, STANDARDS, REQUIREMENTS
 AND CODES SHALL CONFORM TO THE FOLLOWING SECTIONS:
 SECTION 468: SCHOOLS.
  
 2A) 2017 FBC-B 468.3.2 GLARE FROM NATURAL LIGHT.
 SOURCES OF NATURAL LIGHT IN INSTRUCTIONAL SPACES SHALL
 BE GLAZED WITH GLARE REDUCING MATERIALS OR SHALL BE
 SHIELDED TO PREVENT GLARE THAT CAN INTERFERE WITH
 SEEING TASKS WITHIN THE INSTRUCTIONAL SPACE.
 468.3.7.5 GLARE ELIMINATION. ILLUMINATION OF
 PERMANENTLY INSTALLED MARKERBOARDS, CHALKBOARDS, AND
 OTHER INSTRUCTION AIDS SHALL BE DESIGNED TO ELIMINATE
 GLARE AND SHADOWS.
  
 2B) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE
 IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM)
 ABOVE THE FLOOR.
  
 2C) 468.3.5.7.2 SOAP DISPENSERS FOR LIQUID, FOAM, OR
 POWDERED SOAP SHALL BE PROVIDED AT ALL HANDWASHING
 BASINS.
  
 2D) 468.3.7.1 ILLUMINATION LEVEL IN
 CLASSROOMS/INSTRUCTIONAL SPACES. ILLUMINATION AT THE
 NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION
 SPACE SHALL BE A MINIMUM OF 40 FOOTCANDLES (400 LUX).
  
 2E) 468.3.7.2 ILLUMINATION UNIFORMITY IN CLASSROOMS/
 INSTRUCTION SPACES. LUMINARIES SHALL HAVE A CEILING
 ARRANGEMENT OR BE POSITIONED AROUND THE WALLS SUCH THAT
 A UNIFORMED ILLUMINATION LEVEL, WITHIN 10 FOOTCANDLES
 (100 LUX), IS MAINTAINED AT THE STUDENTS REQUIRED
 NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION
 SPACE.
  
 2F) 468.3.7.3 BRIGHTNESS RATIO IN
 CLASSROOMS/INSTRUCTIONAL SPACES. THE BRIGHTNESS RATIO
 BETWEEN THE STUDENT TASK LEVEL AND THE INSTRUCTION AREA
 OR AREAS OR VISUAL DISPLAY LOCATION SHALL BE ONE TO
 FIVE OR LESS.
  
 2G) 468.3.7.4 ILLUMINATION FAILURE OF GENERAL AND MEANS
 OF EGRESS LUMINARIES. ILLUMINATION SYSTEMS SHALL BE
 DESIGNED AND MAINTAINED SO THAT THE FAILURE OF ANY
 SINGLE LIGHTING UNIT, SUCH AS AN ELECTRIC LUMINARY,
 DOES NOT LEAVE ANY OCCUPIED SPACE OR MEANS OF EGRESS IN
 THE DARK. (SEE SECTION 1008 FOR ADDITIONAL MEANS OF
 EGRESS REQUIREMENTS.)
  
 3) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2019-07-30 Cont ID  
Sent By jpearson Date 2019-07-30 Time 07:49 Rev Time 0.00
Received By jpearson Date 2019-07-30 Time 06:39 Sent To  
Notes
2019-07-30 07:49:51NO ELECTRICAL WORK SHOWN ON PLAN. IF ANY ELECTRICAL
 WORK IS TO BE INSTALLED, A PERMIT WITH PLAN REVIEW WILL
 BE REQUIRED. AT THIS TIME, BASED ON CHANGE OF OCCUPANCY
 ONLY PER FBC EXISTING BUILDING SECTION 1008, NO
 ELECTRICAL IS REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By pleduc Date 2019-09-09 Time   Rev Time 0.00
Received By pleduc Date 2019-09-09 Time 13:10 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-29 Cont ID  
Sent By pleduc Date 2019-07-29 Time   Rev Time 0.00
Received By pleduc Date 2019-07-29 Time 13:25 Sent To  
Notes
2019-07-29 13:50:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFORMATION PROVIDE TO
 COMPLETE A THOROUGH LIFE SAFETY REVIEW.
  
  
  
 2) SHEET A 201 - THERE IS NO REFERENCE OF REVIEW OR
 COMPLIANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101;
 SPECIFICALLY, CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES.
  
 PLEASE REVIEW. ENSURE COMPLIANCE AND PROVIDE THE
 REFERENCE.
  
  
  
 3) SHEET A 201 - THERE ARE NO AGE GROUPD INDICATED.
  
 PER NFPA 101, CH 14
  
 14.1.2.2 EDUCATIONAL OCCUPANCIES SHALL INCLUDE
 PRESCHOOLS,
 KINDERGARTENS, AND OTHER SCHOOLS MEETING BOTH OF THE
 FOLLOWING
 CRITERIA:
 (1) THE PURPOSE IS PRIMARILY EDUCATIONAL, EVEN THOUGH
 THE
 CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL AGE.
 (2) THE CHILDREN ARE ALL 24 MONTHS OF AGE OR OLDER.
  
 PLEASE PROVIDE THE AGE GROUPS.
  
  
  
 4) THERE IS NO DOOR SCHEDULE INDICATED SHOWING LOCKS
 AND HARDWARE.
  
 PER NFPA 14
  
 14.2.2.2 DOORS.
 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7.
  
 PLEASE PROVIDE DETAILS AND A DOOR SCHEDULE.
  
  
  
 5) THE PROPOSED OCCUPANCY IS INDICATED ON THE 2ND FLLOR
  
 PER NFPA 14
  
 14.2 MEANS OF EGRESS REQUIREMENTS.
 14.2.1 GENERAL.
 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH
 CHAPTER 7
 AND SECTION 14.2.
 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL,
 KINDERGARTEN, OR
 FIRST-GRADE STUDENTS SHALL BE LOCATED ON A LEVEL OF
 EXIT DISCHARGE,
 UNLESS OTHERWISE PERMITTED BY 14.2.1.4.
 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE
 STUDENTS SHALL
 NOT BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF
 EXIT DISCHARGE,
 UNLESS OTHERWISE PERMITTED BY 14.2.1.4.
 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER
 THAN AS
 SPECIFIED IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED
 TO BE USED
 WHERE PROVIDED WITH INDEPENDENT MEANS OF EGRESS
 DEDICATED FOR
 USE BY THE PRESCHOOL, KINDERGARTEN, FIRST-GRADE, OR
 SECOND-GRADE
 STUDENTS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 6) THERE ARE NO INDICATIONS OF THE CORRIDOR WIDTH.
  
 PER NFPA 101, CH 14
  
 14.2.3 CAPACITY OF MEANS OF EGRESS.
 14.2.3.1 GENERAL. CAPACITY OF MEANS OF EGRESS SHALL BE
 IN
 ACCORDANCE WITH SECTION 7.3.
 14.2.3.2 MINIMUM CORRIDOR WIDTH. EXIT ACCESS CORRIDORS
 SHALL
 HAVE NOT LESS THAN 6 FT (1830 MM) OF CLEAR WIDTH.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 7) SHEET A 201 - THERE IS A DOOR FROM THE EXISTING
 WAITING AREA THAT OPENS INTO THE EXIT CORRIDOR
  
 PER NFPA 101, CH 14
  
 14.2.5.6 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE
 ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL.
 (SEE ALSO
 7.2.1.4.3.)
  
 PLEASE REVIEW AND CORRECT OF PROVIDE DETAILS IN
 COMPLIANCE.
  
  
  
 8) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING.
  
 PER NFPA 14
  
 14.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE
  
  
  
 9) THERE ARE NO INDICATIONS OF A COMPLETE FIRE ALARM
 SYSTEM
  
 PER NFPA 101, CH 14
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6.
 14.3.4.2 INITIATION.
 14.3.4.2.1 GENERAL. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM,
 OTHER THAN AS PERMITTED BY 14.3.4.2.3, SHALL BE BY
 MANUAL MEANS IN
 ACCORDANCE WITH 9.6.2.1(1).
 14.3.4.2.2 AUTOMATIC INITIATION. IN BUILDINGS PROVIDED
 WITH
 AUTOMATIC SPRINKLER PROTECTION, THE OPERATION OF THE
 SPRINKLER
 SYSTEM SHALL AUTOMATICALLY ACTIVATE THE FIRE ALARM
 SYSTEM IN
 ADDITION TO THE INITIATION MEANS REQUIRED IN
 14.3.4.2.1.
  
 14.3.4.3.1 OCCUPANT NOTIFICATION.
 14.3.4.3.1.1 OCCUPANT NOTIFICATION SHALL BE
 ACCOMPLISHED
 AUTOMATICALLY IN ACCORDANCE WITH 9.6.3.
 14.3.4.3.1.2 THE OCCUPANT NOTIFICATION REQUIRED BY
 14.3.4.3.1.1
 SHALL UTILIZE AN EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN
 ACCORDANCE WITH 9.6.3 WHERE THE BUILDING HAS AN
 OCCUPANT LOAD OF
 MORE THAN 100.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
  
 10) SHEET A 201 - THERE ARE MULTIPLE CLASSROOMS THAT
 REQUIRE EXIT THROUGH AN AJOINING ROOM OR SPACE.
  
 PER NFPA 101, CH 14
  
 14.2.5.5 EVERY ROOM THAT IS NORMALLY SUBJECT TO STUDENT
 OCCUPANCY
 SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN
 EXIT ACCESS
 CORRIDOR OR EXIT, UNLESS OTHERWISE PERMITTED BY ONE OF
 THE
 FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY WHERE AN EXIT DOOR
 OPENS
 DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR BALCONY OR
 CORRIDOR AS
 DESCRIBED IN 14.2.5.9.
 (2) ONE ROOM SHALL BE PERMITTED TO INTERVENE BETWEEN A
 NORMALLY
 OCCUPIED STUDENT ROOM AND AN EXIT ACCESS CORRIDOR,
 PROVIDED
 THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (A) THE TRAVEL FROM A ROOM SERVED BY AN INTERVENING
 ROOM
 TO THE CORRIDOR DOOR OR EXIT SHALL NOT EXCEED 75 FT (23
 M).
 (B) CLOTHING, PERSONAL EFFECTS, OR OTHER MATERIALS
 DEEMED
 HAZARDOUS BY THE AUTHORITY HAVING JURISDICTION SHALL BE
 STORED IN METAL LOCKERS, PROVIDED THAT THEY DO NOT
 OBSTRUCT THE EXIT ACCESS, OR THE INTERVENING ROOM SHALL
 BE
 SPRINKLERED IN ACCORDANCE WITH SECTION 9.7.
 (C) ONE OF THE FOLLOWING MEANS OF PROTECTION SHALL BE
 PROVIDED:
 I. THE INTERVENING ROOM SHALL HAVE APPROVED FIRE
 DETECTION THAT ACTIVATES THE BUILDING ALARM.
 II. THE BUILDING SHALL BE PROTECTED BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
  
 PLEASE REVIEW AND PROVIDE TRAVEL DISTANCES AND OTHER
 REQUIRED DETAILS IN COMPLIANCE.
  
  
  
 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-11 Cont ID  
Sent By dbattles Date 2019-09-11 Time 15:59 Rev Time 0.00
Received By dbattles Date 2019-09-06 Time 08:08 Sent To  
Notes
2019-09-06 08:08:45RESUB ROUTED TO FIRE PER SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By hmoser Date 2019-08-19 Time 15:15 Rev Time 0.00
Received By hmoser Date 2019-07-26 Time 16:00 Sent To  
Notes
2019-08-14 16:41:28ROUTED FROM ZONING TO PERMIT LIBRARIAN 8/15/19 EL
2019-07-26 16:00:38C12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-10-29 Cont ID  
Sent By skennedy Date 2019-10-29 Time 16:10 Rev Time 0.00
Received By skennedy Date 2019-10-29 Time 16:10 Sent To  
Notes
2019-10-29 16:11:01MU 2019 0295540000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-09-11 Cont ID  
Sent By dbattles Date 2019-09-11 Time 15:52 Rev Time 0.00
Received By dbattles Date 2019-09-11 Time 15:52 Sent To  
Notes
2019-09-11 15:59:51PLEASE CHECK OUT ONE SET OF PLANS TO BRING TO THE PBC
 FOR IMPACT FEE REVIEW.
 2300 N. JOG ROAD, 2ND FLOOR
 WEST PALM BEACH, FL 33411-2741

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 09:55 Sent To  
Notes
2019-08-05 13:37:34IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By hmoser Date 2019-08-19 Time 15:09 Rev Time 0.00
Received By hmoser Date 2019-08-19 Time 14:37 Sent To I
Notes
2019-08-19 15:15:15NO AIR CONDITIONING OR VENTILATION ON PLAN.
 IF ANY AIR CONDITIONING OR VENTILATION WORK IS GOING
 TO BE DON APPLICATION, PLAN AND PERMIT WILL BE REQUIRED
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-08-26 Cont ID  
Sent By gjohnson Date 2019-08-15 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2019-08-15 Time 15:10 Sent To  
Notes
2019-08-15 15:38:38FULLY ACCESSIBLE BATHROOM DONE UNDER PERMIT# 12090565
 NO PLUMBING WORK UNDER THIS PERMIT.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-11 Cont ID  
Sent By skennedy Date 2019-09-11 Time 10:41 Rev Time 0.00
Received By skennedy Date 2019-09-11 Time 10:41 Sent To  
Notes
2019-09-11 10:42:17REVIEW BY AAPONTE.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-14 Cont ID  
Sent By aaponte Date 2019-08-14 Time 16:39 Rev Time 0.00
Received By elevesqu Date 2019-08-14 Time 16:39 Sent To  
Notes
2019-08-14 16:39:57PROVISO: NO PICKUP/DROPOFF SHALL OCCUR ALONG THE
 ADJACENT STREETS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]