Plan Review Details - Permit 19071374
Plan Review Stops For Permit 19071374
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-21 Cont ID  
Sent By pvalenti Date 2020-02-21 Time 07:32 Rev Time 0.00
Received By pvalenti Date 2020-02-19 Time 13:49 Sent To  
Notes
2020-02-20 13:49:45RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-09 Cont ID  
Sent By pvalenti Date 2019-10-09 Time 12:04 Rev Time 0.00
Received By pvalenti Date 2019-10-07 Time 13:37 Sent To  
Notes
2019-10-08 13:37:45RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 13:04 Rev Time 0.00
Received By pvalenti Date 2019-07-26 Time 15:00 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-02-21 Cont ID  
Sent By pvalenti Date 2020-02-21 Time 07:32 Rev Time 0.00
Received By pvalenti Date 2020-02-21 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-10-09 Cont ID  
Sent By pvalenti Date 2019-10-09 Time 11:59 Rev Time 0.00
Received By pvalenti Date 2019-10-09 Time 11:58 Sent To  
Notes
2019-10-09 12:04:05***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 THE CONTRACTOR'S REP. (DAVID) INFORMED ME THAT A
 CENTRAL SPLIT SYSTEM IS GOING TO BE INSTALLED.
 FBC B 107.2.1 THE CONTRACTOR NEEDS TO SUBMIT ALL OF THE
 ENGINEER APPROVED PLANS AND SPECIFICATIONS FOR THE NEW
 EQUIPMENT THAT IS GOING TO BE INSTALLED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 13:04 Rev Time 0.00
Received By pvalenti Date 2019-08-05 Time 12:52 Sent To  
Notes
2019-08-05 13:04:28***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 MECHANICAL REVIEW DENIED:
  
 FBC B 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. A FLOOR PLAN SHOWING LOCATIONS OF INTERIOR AND
 EXTERIOR A/C UNITS.
 2. INDICATE ON PLAN HOW AIR/HEAT SUPPLIES BEDROOMS.
 3. PROVIDE AN APPROVED TIE DOWN DETAIL FOR EXTERIOR
 CONDENSING UNITS.