Plan Review Details - Permit 19071222
Plan Review Stops For Permit 19071222
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-08-12 Cont ID  
Sent By jwitmer Date 2019-08-12 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2019-08-12 Time 06:27 Sent To  
Notes
2019-08-12 06:29:47PROVISO: ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F.
 S. THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-23 Cont ID  
Sent By shill Date 2019-09-23 Time 07:11 Rev Time 0.00
Received By shill Date 2019-09-23 Time 07:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-12 Cont ID  
Sent By shill Date 2019-09-12 Time 15:18 Rev Time 0.00
Received By shill Date 2019-09-12 Time 15:18 Sent To  
Notes
2019-09-12 15:23:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS REVIEW; REGARDING FLOORING UNDERLAYMENT,
 NOT ADDRESSED. ANOTHER PRODUCT CAN BE PROPOSED VIA
 EMAIL ([email protected])
  
 3) PLEASE NOTE THAT QEP 72000Q/ 72003Q & 72008Q DO HAVE
 PRODUCT TESTING REPORTS ON FILE WITH THE CITY OF WEST
 PALM BEACH BUILDING DIVISION FOR TILE ON 6 INCH
 CONCRETE SLAB, NONE HAVE EVER BEEN SUBMITTED FOR WOOD
 FLOORING. ACOUSTICORK A DIVISION OF AMORIM CORK
 COMPOSITES WHO ALSO OWNS QEP UNDERLAYMENT?S DOES SHOW
 ONLINE A TEST NUMBER NGC 7008139/40- NGC 5008072 FOR
 GLUED WOOD SYSTEM ON A 6 INCH CONCRETE FLOOR SYSTEM,
 BUT NONE HAS EVER BEEN SUBMITTED. WE HAVEN?T SEEN A
 FLAME TEST WITH WOOD PRODUCTS AND THE UNDERLAYMENT
 EITHER PLEASE PROVIDE TEST RESULTS FOR THE FOLLOWING:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR WOOD AND WOOD LAMINATE FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By jwitmer Date 2019-08-12 Time 07:09 Rev Time 0.00
Received By jwitmer Date 2019-08-12 Time 06:27 Sent To  
Notes
2019-08-12 07:09:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071222
 ADD: 3800 WASHINGTON RD. SUITE: 1003
 CONT: NARUS MODERN CONCEPTS LLC
 TEL: 561-360-6589
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY/ AUGUST 12/2019
 ACTION: DENIED
  
 1) PLEASE NOTE SHEET A-001 IN THE TITLEBLOCK THE PLAN
 STATES THE PLANS WERE CREATED UNDER THE OFFICE OF
 LABERGE & MENARD INC. AN ARCHITECTURAL C OA
 (AA26003344) BUT NO SIGNATURE AN SEAL.
  
 61G1-16.004 TITLE BLOCK. ARCHITECT.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
  
 2) THE SUITE NUMBER IS 1003, IT IS NOT CLEAR IF THIS
 UNIT IS ON THE 1ST FLOOR OR THE 10TH FLOOR. FOR THIS
 REVIEW IT IS ASSUMED THE 10TH FLOOR.
  
 2) SHEET A-001 IT WOULD APPEAR THAT SOMEONE HAS HAND
 DRAWN ELECTRICAL SYSTEMS ON WHAT APPEARS TO BE AN
 ARCHITECTS PLAN SINCE THERE IS AN ARCHITECTURAL FIRMS
 NAME IN THE TITLE BLOCK BUT NOT SIGNED AND SEALED. WITH
 THE ARCHITECTS FIRM NAME AND LICENSE NUMBER IT IS
 ASSUMED THIS PLAN WAS A DESIGN OF THE ARCHITECTURAL
 FIRM AND CANNOT BE WRITTEN OR DRAWN ON WITH THE
 EXCEPTION OF THE ARCHITECT OF RECORD.
  
 FL ADMIN CODE 61G16.003(1) ARCHITECTS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003.
  
 3) PLEASE NOTE THAT QEP 72000Q/ 72003Q & 72008Q DO HAVE
 PRODUCT TESTING REPORTS ON FILE WITH THE CITY OF WEST
 PALM BEACH BUILDING DIVISION FOR TILE ON 6 INCH
 CONCRETE SLAB, NONE HAVE EVER BEEN SUBMITTED FOR WOOD
 FLOORING. ACOUSTICORK A DIVISION OF AMORIM CORK
 COMPOSITES WHO ALSO OWNS QEP UNDERLAYMENT?S DOES SHOW
 ONLINE A TEST NUMBER NGC 7008139/40- NGC 5008072 FOR
 GLUED WOOD SYSTEM ON A 6 INCH CONCRETE FLOOR SYSTEM,
 BUT NONE HAS EVER BEEN SUBMITTED. WE HAVEN?T SEEN A
 FLAME TEST WITH WOOD PRODUCTS AND THE UNDERLAYMENT
 EITHER PLEASE PROVIDE TEST RESULTS FOR THE FOLLOWING:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR WOOD AND WOOD LAMINATE FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By jpearson Date 2019-09-13 Time 09:32 Rev Time 0.00
Received By jpearson Date 2019-09-13 Time 09:32 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By jpearson Date 2019-08-14 Time 13:32 Rev Time 0.00
Received By jpearson Date 2019-08-14 Time 10:50 Sent To  
Notes
2019-08-14 13:32:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. THE ARCHITECT SHOWN IN THE TITLE BLOCK DID
 NOT SIGN/SEAL THE SHEET. ADDITIONAL MARKS ON THE SHEET
 ARE NOT PERMITTED UNLESS APPROVED BY THE ARCHITECT AND
 INITIALED. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. THE ELECTRICAL SHEETS PROVIDED APPEAR TO BE FOR THE
 PANEL CHANGE ONLY AND DOES NOT INCLUDE THE REMAINDER OF
 THE ELECTRICAL WORK. PROVIDE ELECTRICAL PLAN FOR
 REVIEW, SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By pleduc Date 2019-09-10 Time   Rev Time 0.00
Received By pleduc Date 2019-09-10 Time 11:16 Sent To  
Notes
2019-09-10 11:16:52THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE REMOVAL AND/OR RE -CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF ANY EXISTING
 SMOKE DETECTORS AND/OR FIRE ALARM DEVICES FOR CODE
 COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY
 CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-29 Cont ID  
Sent By pleduc Date 2019-07-29 Time   Rev Time 0.00
Received By pleduc Date 2019-07-29 Time 13:11 Sent To  
Notes
2019-07-29 13:20:23THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE REMOVAL AND/OR RE -CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF ANY EXISTING
 SMOKE DETECTORS AND/OR FIRE ALARM DEVICES FOR CODE
 COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY
 CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-13 Cont ID  
Sent By gjohnson Date 2019-09-13 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2019-09-06 Time 09:00 Sent To  
Notes
2019-09-09 09:00:40B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 13:08 Rev Time 0.00
Received By gjohnson Date 2019-07-24 Time 13:42 Sent To  
Notes
2019-07-25 13:42:54B22

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By gjohnson Date 2019-09-13 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2019-09-13 Time 13:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 12:54 Rev Time 0.00
Received By gjohnson Date 2019-08-19 Time 12:54 Sent To  
Notes
2019-08-19 13:08:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. ALL THE PLAN SHEETS ARE NUMBERED THE SAME PLEASE
 LABEL PLAN SHEETS SEPARATELY. PER WPB AMEND TO FBC
 107.2.1
  
 2. PLAN SHEETS SHALL BE SIGNED AND SEALED SEE BUILDING
 AND ELECTRICAL COMMENTS. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]