Plan Review Details - Permit 19071025
Plan Review Stops For Permit 19071025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-15 Cont ID  
Sent By pvalenti Date 2019-08-15 Time 10:22 Rev Time 0.00
Received By pvalenti Date 2019-08-15 Time 10:22 Sent To  
Notes
2019-08-15 10:26:45 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW APPROVED:
  
 THE VALUATION HAS BEEN ADJUSTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-25 Cont ID  
Sent By shill Date 2019-07-25 Time 15:57 Rev Time 0.00
Received By shill Date 2019-07-25 Time 15:57 Sent To  
Notes
2019-07-25 16:00:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 2. PROVIDE THE VALUE OF THE JOB, INCLUDING MATERIALS
 PROVIDED BY OTHERS, FBC 109.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-25 Cont ID  
Sent By shill Date 2019-07-25 Time 16:00 Rev Time 0.00
Received By shill Date 2019-07-19 Time 12:35 Sent To  
Notes
2019-07-22 12:35:39BLDG<5K