Plan Review Details - Permit 19071004
Plan Review Stops For Permit 19071004
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-18 Cont ID  
Sent By pvalenti Date 2019-08-18 Time 12:14 Rev Time 0.00
Received By pvalenti Date 2019-08-18 Time 12:14 Sent To  
Notes
2019-08-18 12:16:38PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED W/PROVISOS:
  
 ALL PRODUCT APPROVALS ARE STILL REQUIRED PRIOR TO
 INSPECTION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-19 Cont ID  
Sent By jpearson Date 2019-11-19 Time 10:30 Rev Time 0.00
Received By jpearson Date 2019-11-19 Time 10:30 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-11 Cont ID  
Sent By ppetty Date 2019-08-11 Time 12:12 Rev Time 0.00
Received By jpearson Date 2019-08-09 Time 13:32 Sent To  
Notes
2019-08-11 12:12:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION FOR PANEL B SHOWS DEMAND FACTORS
 THAT ARE NOT PERMITTED. BECAUSE THIS IS ONLY A 60 AMP
 FEED, DEMAND FACTORS CANNOT BE USED. DEMAND FACTORS ARE
 ONLY PERMITTED WHEN THE FEEDERS ARE RATED 100 AMPS OR
 MORE. THERFORE, THE CIRCUIT BREAKER FOR THIS WOULD BE
 OVERLOADED. PROVIDE CORRECTION. NEC 220.82; FBC RE
 E3602.2.1
 2. ORIGINAL RISER DIAGRAM SHOWS A PANEL BEING INSTALLED
 FOR THE POOL EQUIPMENT. THIS HAS BEEN REMOVED FROM THIS
 DRAWING. WITH THE POOL EQUIPMENT NOW BEING FED FROM
 PANEL B, HOW WILL THIS EQUIPMENT HAVE THE REQUIRED
 DISCONNECT WITHIN SIGHT OF THE EQUIPMENT? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-12-22 Cont ID  
Sent By abelisle Date 2021-12-22 Time 13:07 Rev Time 0.00
Received By abelisle Date 2021-12-22 Time 13:07 Sent To  
Notes
2021-12-22 13:08:34A GAS REVIEW HAS NOT BEEN PERFORMED UNDER THIS PERMIT,
 A SEPERATE REVIEW AND GAS PERMIT IS REQUIRED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-12-05 Cont ID  
Sent By tklarge Date 2019-12-05 Time 11:41 Rev Time 0.00
Received By tklarge Date 2019-12-05 Time 11:02 Sent To  
Notes
2021-12-22 10:10:05ARMAND PATEL CALLED AND REQUESTED TO HAVE THE GAS
 PORTION REMOVED FROM THE PLANS AND A SEPERATE GAS
 PERMIT AND GAS REVIEW WILL BE SUBMITTED
2019-12-05 11:38:35GAS REVIEW
  
 1) SUBMIT AN EXPANDED GAS RISER FOR THE AREA OF
 REGULATOR "B". IT IS DIFFICULT TO SEE WHERE THE GAS
 LINES CONTINUE/CONNECT AND TO CHECK IF THE LINES ARE
 PROPERLY SIZED. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE GAS RISER SHOWS A 3/4" SUPPLYING A 352 BTUH
 FUTURE GENERATOR. THIS LINE IS UNDERSIZED PER THE
 REFERENCED GAS TABLE. ALSO, INDICATE THE TYPE ON THE
 GAS RISER FOR THE GENERATOR.
 3) SHOW THE SIZE OF THE PIPE ABOVEGROUND TO THE POOL
 HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE GAS RISER SHOWS A 3/4 INCH PE LINE AT .5 PSI TO
 A FUTURE 400 BTUH POOL HEATER. THIS LINE IS UNDERSIZED
 PER THE REFERENCED GAS TABLE.
 5) UNIONS ARE REQUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF ALL REGULATORS. 2017 FBC-GAS SEC.410.2
 (7). INDICATE ON THE RISER.
 6) THE GAS RISER HAS A TABLE FOR REGULATOR "A" &
 REGULATOR "B" BUT THE RISER SHOWS REGULATORS "B" & "C".
 CLARIFY.
 7) CHECK THE BTU LOAD FOR REGULATOR "B". I CALCULATE
 947 BTUH ACCORDING TO THE RISER.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-05 Cont ID  
Sent By tklarge Date 2019-12-05 Time 11:41 Rev Time 0.00
Received By tklarge Date 2019-11-14 Time 15:29 Sent To  
Notes
2019-11-15 15:29:42RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By hmoser Date 2019-08-19 Time 13:51 Rev Time 0.00
Received By hmoser Date 2019-07-19 Time 13:25 Sent To  
Notes
2019-07-22 13:25:08R24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-08-19 Cont ID  
Sent By hmoser Date 2019-08-19 Time 13:51 Rev Time 0.00
Received By hmoser Date 2019-08-19 Time 13:22 Sent To I
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2019-08-18 Cont ID  
Sent By pvalenti Date 2019-08-18 Time 12:34 Rev Time 0.00
Received By pvalenti Date 2019-08-18 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-12-22 Cont ID  
Sent By abelisle Date 2021-12-22 Time 14:18 Rev Time 0.00
Received By abelisle Date 2021-12-22 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-12-05 Cont ID  
Sent By tklarge Date 2019-12-05 Time 11:02 Rev Time 0.00
Received By tklarge Date 2019-12-05 Time 09:34 Sent To  
Notes
2019-12-05 11:01:591) THE SINK IN THE LAUNDRY ROOM IS NOT SHOWN ON THE
 SANITARY RISER. SHOW THE SINK ON THE SANITARY RISER.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-15 Cont ID  
Sent By cthroop Date 2019-08-15 Time 06:32 Rev Time 0.00
Received By tklarge Date 2019-08-15 Time 05:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-30 Cont ID  
Sent By llouie Date 2019-07-30 Time   Rev Time  
Received By llouie Date 2019-07-30 Time   Sent To  
Notes
2019-07-30 10:37:58NOTES:
  
 * SEPARATE PERMIT FOR LANDSCAPING REQUIRED PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.). A HOLD
 ON THE C.O. HAS BEEN PLACED IN THE SYSTEM.
  
 * ADDITIONAL SEPARATE PERMITS REQUIRED FOR: SWIMMING
 POOL, GENERATOR.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  