Plan Review Details - Permit 19071003
Plan Review Stops For Permit 19071003
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By dbattles Date 2019-09-20 Time 08:46 Rev Time 0.00
Received By dbattles Date 2019-09-20 Time 08:46 Sent To  
Notes
2019-09-20 08:50:34PROVISO:
 SKYLIGHT PRODUCT APPROVAL TO BE DEFERRED.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-26 Cont ID  
Sent By dbattles Date 2019-07-26 Time 12:59 Rev Time 0.00
Received By dbattles Date 2019-07-26 Time 12:59 Sent To  
Notes
2019-07-26 13:17:44BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 1901
 REVIEWED: JULY 26, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 SKY LIGHT.
  
 2) 401.2 FBC[RE] PLEASE PROVIDE UPDATED ENERGY
 CALCULATIONS TO INCLUDE THE SKYLIGHT.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 15:32 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-23 Cont ID  
Sent By jpearson Date 2019-09-23 Time 08:20 Rev Time 0.00
Received By jpearson Date 2019-09-23 Time 08:20 Sent To  
Notes
2019-09-23 08:20:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CORRECTED.
 2. CORRECTED.
  
 NEW COMMENTS:
  
 3. PANEL B AND PANEL P ARE NOW SHOWN BEING FED FROM A
 100 AMP BREAKER. THE RISER SHOWS THE FEEDER SIZE AS #6
 WIRE, WHICH IS NOT RATED FOR 100 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE E3705.1
 4. RISER SHOWS THE EQUIPMENT GROUNDING CONDUCTOR TO
 PANEL B AND PANEL B SIZED AT #10. THIS IS NOT THE
 CORRECT SIZE FOR A 100 AMP CIRCUIT. PROVIDE CORRECTION.
 NEC 250.122; FBC RE E3704.6, 3607.3.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-09 Cont ID  
Sent By jpearson Date 2019-08-09 Time 15:54 Rev Time 0.00
Received By jpearson Date 2019-08-09 Time 13:32 Sent To  
Notes
2019-08-09 15:14:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION FOR PANEL B SHOWS DEMAND FACTORS
 THAT ARE NOT PERMITTED. BECAUSE THIS IS ONLY A 60 AMP
 FEED, DEMAND FACTORS CANNOT BE USED. DEMAND FACTORS ARE
 ONLY PERMITTED WHEN THE FEEDERS ARE RATED 100 AMPS OR
 MORE. THERFORE, THE CIRCUIT BREAKER FOR THIS WOULD
 LIKELY BE OVERLOADED. PROVIDE CORRECTION. NEC 220.82;
 FBC RE E3602.2.1
 2. ORIGINAL RISER DIAGRAM SHOWS A PANEL BEING INSTALLED
 FOR THE POOL EQUIPMENT. THIS HAS BEEN REMOVED FROM THIS
 DRAWING. WITH THE POOL EQUIPMENT NOW BEING FED FROM
 PANEL B, HOW WILL THIS EQUIPMENT HAVE THE REQUIRED
 DISCONNECT WITHIN SIGHT OF THE EQUIPMENT? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-24 Cont ID  
Sent By hmoser Date 2019-09-24 Time 14:27 Rev Time 0.00
Received By hmoser Date 2019-09-16 Time 09:42 Sent To  
Notes
2019-09-24 10:58:47TO HM DESK
  
2019-09-18 09:42:55R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-21 Cont ID  
Sent By cmontell Date 2019-08-21 Time 13:03 Rev Time 0.00
Received By cmontell Date 2019-08-21 Time 13:03 Sent To  
Notes
2019-07-22 13:21:02R19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By cmontell Date 2019-09-24 Time 14:26 Rev Time 0.00
Received By hmoser Date 2019-09-24 Time 13:26 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-08-21 Cont ID  
Sent By skennedy Date 2019-08-21 Time 13:02 Rev Time 0.00
Received By cmontell Date 2019-08-21 Time 12:43 Sent To I
Notes
2019-08-21 12:43:46PROVISOS
 NEEDS TO COMPLY WITH 2017 FLORIDA BUILDING CODE - FUEL
 GAS, SIXTH EDITION
 304.5.3.1COMBINING SPACES ON THE SAME STORY.
 EACH OPENING SHALL HAVE A MINIMUM FREE AREA OF 1 SQUARE
 INCH PER 1,000 BTU/H (2,200 MM2/KW) OF THE TOTAL INPUT
 RATING OF ALL APPLIANCES IN THE SPACE, BUT NOT LESS
 THAN 100 SQUARE INCHES (0.06 M2). ONE OPENING SHALL
 COMMENCE WITHIN 12 INCHES (305 MM) OF THE TOP AND ONE
 OPENING SHALL COMMENCE WITHIN 12 INCHES (305 MM) OF THE
 BOTTOM OF THE ENCLOSURE. THE MINIMUM DIMENSION OF AIR
 OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM).
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 11:53 Rev Time 0.00
Received By tklarge Date 2019-08-14 Time 13:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-19 Cont ID  
Sent By awooten Date 2019-08-19 Time   Rev Time  
Received By awooten Date 2019-08-19 Time   Sent To  
Notes
***NONE***