2019-08-26 11:57:10 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19071002 |
| ADD: 1675 PALM BEACH LAKES BLVD. |
| CONT: TBD. TO BE DETERMINED |
| TEL: ??????????? |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. AUGUST 26, 2019 |
| ACTION: DENIED |
| |
| 1) SHEET 001-GN-1 INDICATES THE CANOPY CONSTRUCTION |
| TYPE IS A TYPE V CONSTRUCTION. SHEET 007-A-113 HAS A |
| NOTE THAT STAINED WOOD T & G ON 5/8 INCH EXTERIOR GRADE |
| PLYWOOD SHEATHING. |
| |
| PLEASE NOTE UNDER THE 2017 FBC-B SECTION 3104.3 |
| CONSTRUCTION. THE PEDESTRIAN WALKWAY SHALL BE OF |
| NON-COMBUSTIBLE CONSTRUCTION. PLEASE REVIEW EXCEPTION # |
| 2. |
| EXCEPTION 2. FIRE-RETARDANT-TREATED WOOD, IN ACCORDANCE |
| WITH SECTION 603.1, ITEM 1.3, SHALL BE PERMITTED FOR |
| THE ROOF CONSTRUCTION OF THE PEDESTRIAN WALKWAY WHERE |
| CONNECTED BUILDINGS ARE A MINIMUM OF TYPE I OR II |
| CONSTRUCTION. |
| |
| 2) SHEET S-2.01 INDICATES THE USE OF WELDED AND BOLTED |
| CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| AMERICAN WELDING SOCIETY. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU |
| |
| 3) SHEET 007-A-113 DETAIL # 2 INDICATES THE |
| INSTALLATION OF SINGLE PLY 60 MIL TPO ROOF MEMBRANE |
| OVER TAPERED FOAM INSULATION. PLEASE PROVIDE THE |
| PRODUCT APPROVAL FOR THE ROOFING AND TAPERED FOAM |
| INSULATION. |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF |
| INSULATION. |
| |
| 4) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS, INSULATION AND THEIR |
| ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL |
| BE INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 5) WHEN SUBMITTING THE ROOFING AND INSULATION PRODUCT |
| APPROVAL PLEASE VERIFY BEFORE THE PRODUCT APPROVAL IS |
| SUBMITTED TO THE BUILDING DEPARTMENT THAT THE DECK |
| GAUGE, JOIST SPAN AND ATTACHMENT ARE IN CONFORMANCE |
| WITH THE SELECTED ROOFING PRODUCT APPROVAL. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7) SHEET S-1.01 UNDER THE HEADING OF SHALLOW |
| FOUNDATIONS INDICATES ALL FOOTINGS SHALL BEAR ON SOIL |
| OR ROCK PREPARED B PER THE PENDING GEOTECHNICAL REPORT |
| THAT WILL BE AVAILABLE. |
| 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |