Plan Review Stops For Permit 19070954 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-11-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-09 |
Time |
06:30 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-11-08 |
Time |
08:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-10-21 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-10-21 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-10-09 |
Time |
09:20 |
Sent To |
|
|
Notes |
2019-10-21 15:32:29 | PLAN REVIEW - BUILDING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | ADVISORY - HISTORIC PRODUCT APPROVALS | | | | PROPERTY IS LOCATED IN AN ESTABLISHED HISTORIC | | DISTRICT. ALL PRODUCT APPROVALS SHALL BE SUBMITTED AND | | APPROVED PRIOR TO PERMIT. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-26 |
Time |
17:06 |
Sent To |
|
|
Notes |
2019-08-31 11:13:00 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. OWNER/AGENT SHALL SIGN ENERGY SUBMITTAL. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 2. BUILDER SHALL SIGN EPL CARD. | | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | (MANDATORY). | | | | 3. DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS. | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | SUBMITTALS. | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | OFFICIAL. | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | OFFICIAL. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-10-22 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-10-22 |
Time |
06:32 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-10-10 |
Time |
06:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-08-24 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-08-24 |
Time |
22:05 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-08-23 |
Time |
07:14 |
Sent To |
|
|
Notes |
2019-08-24 21:53:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | GUEST HOUSE: | | | | 1. PROVIDE ACCURATE PANEL SCHEDULES SHOWING OCP, WIRE | | SIZE, AND AFCI/GFCI PROTECTION WHERE APPLICABLE. FBC | | 107.2.1 NEC 210.8, 210.12 | | | | 2. SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS | | REQUIRED. FBC RE 314&315 | | | | 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | FBC EC R404.1 | | | | 4. GARAGE RECEPTACLES MUST BE GFCI PROTECTED NEC 210.8 | | | | 5. PROVIDE NOTE ON PLAN THAT STATES LOW VOLTAGE AND | | GENERATOR REQUIRES SEPARATE ELECTRICAL PERMITS. FBC | | 107.2.1 | | | | 6. SERVICE RECEPTACLES REQUIRED FOR AHU'S AND A/C | | CONDENSORS NEC 210.63 | | | | MAIN HOUSE: | | | | 1. PROVIDE ACCURATE PANEL SCHEDULES SHOWING OCP, WIRE | | SIZE, AND AFCI/GFCI PROTECTION WHERE APPLICABLE. FBC | | 107.2.1 NEC 210.8, 210.12 | | | | 2. PROVIDE LOCATIONS ON PLANS OF ALL PANELS SHOWN ON | | ONE-LINE/RISER DIAGRAM. PROVIDE LOCATIONS FOR ALL THREE | | ATS'S, ALL SUB-PANELS, AND POOL PANEL. ALL LOCATIONS | | NOW SHOWN ON PLAN. FBC 107.2.1 | | | | 3. SMOKE DETECTORS/ CARBON MONOXIDE DETECTORS REQUIRED | | PER FBC RE 314&315. PROVIDE CORRECTION. | | | | 4. PROVIDE NOTE ON PLAN THAT STATES LOW VOLTAGE AND | | GENERATOR REQUIRES SEPARATE ELECTRICAL PERMITS. FBC | | 107.2.1 | | | | 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | FBC EC R404.1 | | | | 6. LIGHTING PLAN AND POWER PLAN DO NOT HAVE SAME | | STRUCTURAL LAYOUT. POWER PLAN SHOWS A ROOM ADJACENT TO | | BEDROOM#2 AND BATHROOM #2 BUT IS NOT SHOWN ON LIGHTING | | PLAN?? PROVIDE ACCURATE DRAWINGS SHOWING ALL DOOR AND | | ROOM LOCATIONS THAT MATCH ON BOTH ELEC AND LIGHTING | | PLANS FBC 107.2.1 | | | | 7. NO ELECTRIC SHOWN FOR A/C CONDENSORS OUTSIDE? FBC | | 107.2.1 | | | | 8. NO LOCATIONS SHOWN FOR AHU'S OR ELECTRIC. FBC | | 107.2.1 | | | | 9. NO ATTIC ACCESS SHOWN? MUST SHOW ATTIC ACCESS WITH | | PROPER ELECTRICAL REQUIRED. FBC 107.2.1 | | | | 10. MUST HAVE BONDING BRIDGE AT SERVICE. NEC 250.94 | | | | 11. SERVICE RECEPTACLES REQUIRED FOR AHU'S AND A/C | | CONDENSORS NEC 210.63 | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
3 |
Status |
P |
Date |
2019-10-30 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2019-10-30 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-10-30 |
Time |
13:41 |
Sent To |
|
|
Notes |
2019-10-30 13:42:13 | ALL ARCHITECTURAL DETAILS TO MATCH THOSE APPROVED BY | | HPB. HISTORIC DESIGN DETAILS FROM BOARD SET SUPERSEDES | | THOSE IN PERMIT SET. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
F |
Date |
2019-10-11 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2019-10-11 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-10-11 |
Time |
13:23 |
Sent To |
|
|
Notes |
2019-10-11 13:32:05 | DETAILS IN ELEVATIONS STILL DO NOT MATCH HPB APPROVAL | | OR HISTORIC PHOTO, SUCH AS: | | - SCALLOP OF ENTRY PORCH MISSING | | - BRITTANY STYLE DOORS NOT ORIGINAL PATTERN | | - EAST PORCH ROOF LINE MISSING RAFTER TAILS | | - PANEL BELOW PORCH WINDOWS MISSING INSET PANEL | | | | ETC. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2019-08-27 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2019-08-27 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-08-27 |
Time |
11:38 |
Sent To |
|
|
Notes |
2019-08-27 11:44:51 | SYNTHETIC ROOFING MATERIAL NOT PERMITTED. | | | | ALL ELEVATIONS/PRODUCTS TO MATCH WHAT WAS APPROVED BY | | THE HISTORIC PRESERVATION BOARD. | | | | QUESTIONS CONTACT FRIEDERIKE MITTNER AT (561) 822-1457 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-11-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-09 |
Time |
06:29 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-10-29 |
Time |
15:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-10-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-10-22 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-10-08 |
Time |
11:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-06 |
Time |
16:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2019-10-24 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-10-24 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-10-22 |
Time |
07:37 |
Sent To |
|
|
Notes |
2019-10-23 15:42:42 | RECEIPT 2019-1023-221 - $22.46 - PAID | 2019-10-22 07:37:57 | 10/22/19 SENT EMAIL TO IMPACT FEE OFFICE. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-26 |
Time |
17:06 |
Sent To |
|
|
Notes |
2019-08-31 11:18:49 | PALM BEACH COUNTY IMPACT FEES | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. APPLICANT SHALL SUBMIT IMPACT FEES QUESTIONAIRE. | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] . |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-26 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2019-09-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-09-05 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-09-05 |
Time |
08:39 |
Sent To |
|
|
Notes |
2019-09-05 08:41:35 | PROPERTY IS LOCATED IN A SFHA. ZONE AE 6.0 W DFE OF 8.0 | | FT. NAVD. 2019 IMPROVEMENT VALUE IS $176,111 AND VALUE | | OF THIS PERMIT PLUS A FIVE YEAR TAIL IS $780,000. | | PROJECT IS CLASSIFIED AS A S/I PER FEMA 50% RULE. | | | | | | CONTRIBUTING HOUSE LOCATED IN A HISTORIC DISTRICT. | | EXEMPT FROM SUBSTANTIAL IMPROVEMENT PER FBC EXISTING | | BUILDING CHPT. 12 SECTION 1201.3. | | | | CBAA WAIVER REQUIRED PER CITY ORDINANCE NO. 4729-17 AND | | FBC CHPT 12 HISTORIC BUILDINGS. CT |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-26 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
P |
Date |
2019-11-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-09 |
Time |
06:29 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-11-08 |
Time |
08:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2019-10-21 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-10-21 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-10-09 |
Time |
09:20 |
Sent To |
|
|
Notes |
2019-10-21 15:33:20 | PLAN REVIEW - ROOFING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | ADVISORY - HISTORIC PRODUCT APPROVALS | | | | PROPERTY IS LOCATED IN AN ESTABLISHED HISTORIC | | DISTRICT. ALL PRODUCT APPROVALS SHALL BE SUBMITTED AND | | APPROVED PRIOR TO PERMIT. | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-26 |
Time |
17:06 |
Sent To |
|
|
Notes |
2019-08-31 11:15:24 | BUILDING PLAN REVIEW - ROOFING | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS. | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2019-11-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-09 |
Time |
06:29 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-11-08 |
Time |
08:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-10-21 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-10-21 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-10-09 |
Time |
09:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2019-08-31 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-31 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-26 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-10-30 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2019-10-30 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-10-30 |
Time |
13:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-08-27 |
|
|
Cont ID |
|
Sent By |
pgreilic |
Date |
2019-08-27 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-08-27 |
Time |
11:39 |
Sent To |
|
|
Notes |
2019-08-27 11:46:00 | REQURIES SUBMITTAL OF SEPERATE LANDSCAPE PLAN. | | | | QUESTIONS, CONTACT RAY CARANCI |
|
|