Plan Review Stops For Permit 19070831 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-11-21 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-21 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-21 |
Time |
15:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-10-16 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-10-02 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-10-02 |
Time |
07:39 |
Sent To |
|
|
Notes |
2019-10-02 08:22:27 | 3202.2 FBC[B]ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET | | IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY | | ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL | | BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS | | 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT | | OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. | | | | THE NEW DOORS THAT ARE BEING INSTALLED ON SOUTH SIDE | | WHERE GLASS BLOCK REMOVED (SF-06 SHEET A-403.0) APPEAR | | TO BE SWINGING INTO THE RIGHT OF WAY. | | PLEASE ADJUST STOREFRONT SYSTEM SO THAT THIS DOES NOT | | OCCUR. | | | | | | PROVISO: | | AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR | | TO C.O. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-08-12 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-08-12 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-05 |
Time |
10:59 |
Sent To |
|
|
Notes |
2019-08-12 12:52:44 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 19070831 | | REVIEWED: AUGUST 8, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[B] = FBC BUILDING | | FBC[EXISTING] = FBC EXISTING BUILDING | | FBC[A] = FBC ACCESSIBILITY | | FBC[E] = FBC ENERGY CONSERVATION | | | | 1) ADJUST STATEMENT ON STRUCTURAL PLANS TO SAY | | ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT | | REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | ARCHITECT OR ENGINEER OF RECORD CONTAIN THIS STATEMENT: | | | | TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, | | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE SAFETY | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | ACCORDANCE WITH THIS CHAPTER 553 AND CHAPTER 633. | | | | 2) 107.5.3 FBC[AMENDED]SHEET A-600. ADJUST CODE | | REFERENCE FROM 2014 TO FBC 2017 6TH EDITION AT DOOR | | TYPES. | | | | 3) 107.2.3 FBC[AMENDED]PLEASE ADD LIFE SAFETY DATA THAT | | IS APPLICABLE TO ANY CHANGES IN CONFIGURATION CAUSED BY | | THE EXTERIOR DOORS. FOR EXAMPLE THE THERE WILL BE LESS | | EGRESS WIDTH PROVIDED AT SOUTH ENTRY DOORS. WHILE I | | UNDERSTAND THAT THE INTERIOR WORK WOULD PROVIDE MUCH | | MORE DETAIL ON LIFE SAFETY, SOME COORDINATION IS NEEDED | | FOR PERIMETER EGRESS DOORS THAT WILL BE INSTALLED PRIOR | | TO INTERIOR WORK. | | | | 4) PLEASE CLARIFY ON PLANS THE SCOPE OF EXTERIOR WOK | | ONLY. NO INTERIOR BUILD OUT ON THIS PERMIT AND ONLY | | LIFE SAFETY TO THE EXTENT OF HOW IT AFFECTS CHANGES IN | | PERIMETER EGRESS. FOR EXAMPLE THE PLANS STATE COURTYARD | | BY SEPARATE PERMIT. SOMETHING ALONG THOSE LINES FOR | | INTERIOR WORK WOULD HELP CLARIFY THE SCOPE OF EXTERIOR | | WORK. | | | | NOTES: | | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2019-10-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-10-16 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-10-16 |
Time |
08:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2019-12-11 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2019-12-11 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2019-12-11 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2019-10-15 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2019-10-15 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2019-10-15 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2019-08-19 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2019-08-19 |
Time |
|
Sent To |
|
|
Notes |
2019-08-19 11:34:22 | PLEASE ADDRESS BUILDING COMMENTS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-12-12 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-12-12 |
Time |
07:45 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-19 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-10-17 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-10-17 |
Time |
09:44 |
Rev Time |
|
Received By |
gjohnson |
Date |
2019-09-18 |
Time |
07:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-08-20 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-08-20 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-07-17 |
Time |
11:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-12-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-12-09 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-12-09 |
Time |
10:30 |
Sent To |
|
|
Notes |
2019-12-20 08:37:43 | PLUMBING NOTES: | | APPROVED FOR STORM DRAIN ON VERSA WALL ONLY. | | ALL IRRIGATION SYSTEMS SHALL HAVE A BACK FLOW DEVISE | | WITH SEPARATE PERMIT | | SEE MAIN PERMIT 19090882 | | | 2019-12-12 17:20:46 | REVIEWED REMOTELY BY GEORGE JOHNSON | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-10-17 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-10-17 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-10-17 |
Time |
09:11 |
Sent To |
|
|
Notes |
2019-10-17 09:44:05 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE PROVIDE A DETAILED SCOPE OF PROPOSED PLUMBING | | WORK IT IS NOT CLEAR ON THE PLAN. PER WPB AMEND TO FBC | | 107.2.1 | | | | 2. PROVIDE CIVIL PLAN NOTED ON SHT. FP101 PER WPB AMEND | | TO FBC 107.2.1 | | | | 3. IT IS UNCLEAR WHAT THE NOTE IS FOR 4" STM FOR VERSA | | WALL IS THIS A STORM DRAIN IF SO PROVIDE CALCULATIONS | | FOR SIZING. PER WPB AMEND TO FBC 107.2.1 AND PER WPB | | AMEND TO FBC 107.2.1 | | | | 4. WHAT IS THE VERSA WALL. PER WPB AMEND TO FBC 107.2.1 | | | | 5. PLEASE PROVIDE DETAIL FOR STM DRAIN PIPING. PER WPB | | AMEND TO FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2019-11-21 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-21 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-21 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-10-02 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-10-02 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-10-02 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-08-12 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-08-12 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-12 |
Time |
12:55 |
Sent To |
|
|
Notes |
2019-08-12 12:55:20 | FIRST REVIEW SHEETS OK. | | | | ANY ADDITIONAL SHEETS FOR RE-SUBMITTAL TO BE DIGITALLY | | SIGNED. |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
P |
Date |
2019-10-10 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-10-02 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-10-02 |
Time |
08:27 |
Sent To |
|
|
Notes |
2019-10-02 08:29:51 | PLEASE CONTACT ME TO DISCUSS THRESHOLD INSPECTOR | | AGREEMENT (SEE PREVIOUS REVIEW COMMENTS) | | | | | | DYLAN BATTLES | | 561-805-6718 | | [email protected] | | | | THE CITY OF WEST PALM BEACH | | BUILDING PLANS EXAMINER PX4191 | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2019-08-12 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-08-12 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-12 |
Time |
12:53 |
Sent To |
|
|
Notes |
2019-08-12 13:00:09 | I SEE THAT A THRESHOLD AGREEMENT WAS SUBMITTED AND | | APPROVED FOR THE DEMO PERMIT. | | IF THEY WILL CONTINUE TO BE THE THRESHOLD FOR THE | | EXTERIOR STRUCTURAL MODIFICATION PLEASE SEND UPDATED | | AGREEMENT TO INCLUDE THE PERMIT NUMBER OF THE EXTERIOR | | WORK. (19070831) | | THIS CAN BE DIGITALLY SIGNED AND UPLOADED TO THE | | SUPPORTING DOCUMENTS, OR 3 ORIGINALS BROUGHT INTO | | DEVELOPMENT SERVICES AS SUBMITTAL. | | IF CHANGING THE THRESHOLD INSPECTOR THAN SEND ME E-MAIL | | DRAFT OF NEW COMPANY FOR APPROVAL. | | | | DYLAN BATTLES | | 561-805-6718 | | [email protected] | | | | THE CITY OF WEST PALM BEACH | | BUILDING PLANS EXAMINER PX4191 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2019-12-11 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2019-12-11 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2019-12-11 |
Time |
15:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-10-15 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2019-10-15 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2019-10-15 |
Time |
11:32 |
Sent To |
|
|
Notes |
2019-10-15 11:35:25 | PROVISO: NEW ENTRY DOORS ALONG DATURA STREET SHALL BE | | RECESSED SO THEY DO NOT ENCROACH INTO THE ROW MORE THAN | | ONE FOOT WHEN OPEN. | | FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-08-20 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2019-08-20 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2019-08-20 |
Time |
08:57 |
Sent To |
|
|
Notes |
2019-08-20 09:00:29 | 1. PLEASE INCLUDE THE CANOPY PROJECTION IN THE SITE | | PLAN AND THE FLOOR PLANS. INCLUDE DIMENSION. | | 2. PLEASE INCLUDE DIMENSION ON THE VERTICAL CLEARANCE | | FOR THE CANOPY. | | 3. ARTIFICIAL TURF IS NOT ALLOWED IN ANY AREA THAT IS | | VISIBLE FROM THE PUBLIC. PLEASE CLARIFY THE LOCATION OF | | THE ARTIFICIAL TURF. | | 4. PLEASE NOTE THAT IF THE TOTAL COST OF THE PROJECT | | EXCEED MORE THAN 50% OF THE BUILDING ASSESSED VALUE | | ACCORDING TO PAPA, STREETSCAPE IMPROVEMENT WOULD BE | | REQUIRED. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|