Plan Review Details - Permit 19070831
Plan Review Stops For Permit 19070831
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-21 Cont ID  
Sent By dbattles Date 2019-11-21 Time 15:14 Rev Time 0.00
Received By dbattles Date 2019-11-21 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-16 Cont ID  
Sent By dbattles Date 2019-10-02 Time 08:27 Rev Time 0.00
Received By dbattles Date 2019-10-02 Time 07:39 Sent To  
Notes
2019-10-02 08:22:273202.2 FBC[B]ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET
 IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS
 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 THE NEW DOORS THAT ARE BEING INSTALLED ON SOUTH SIDE
 WHERE GLASS BLOCK REMOVED (SF-06 SHEET A-403.0) APPEAR
 TO BE SWINGING INTO THE RIGHT OF WAY.
 PLEASE ADJUST STOREFRONT SYSTEM SO THAT THIS DOES NOT
 OCCUR.
  
  
 PROVISO:
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By dbattles Date 2019-08-12 Time 12:51 Rev Time 0.00
Received By dbattles Date 2019-08-05 Time 10:59 Sent To  
Notes
2019-08-12 12:52:44BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070831
 REVIEWED: AUGUST 8, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) ADJUST STATEMENT ON STRUCTURAL PLANS TO SAY
 ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN THIS STATEMENT:
  
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER 553 AND CHAPTER 633.
  
 2) 107.5.3 FBC[AMENDED]SHEET A-600. ADJUST CODE
 REFERENCE FROM 2014 TO FBC 2017 6TH EDITION AT DOOR
 TYPES.
  
 3) 107.2.3 FBC[AMENDED]PLEASE ADD LIFE SAFETY DATA THAT
 IS APPLICABLE TO ANY CHANGES IN CONFIGURATION CAUSED BY
 THE EXTERIOR DOORS. FOR EXAMPLE THE THERE WILL BE LESS
 EGRESS WIDTH PROVIDED AT SOUTH ENTRY DOORS. WHILE I
 UNDERSTAND THAT THE INTERIOR WORK WOULD PROVIDE MUCH
 MORE DETAIL ON LIFE SAFETY, SOME COORDINATION IS NEEDED
 FOR PERIMETER EGRESS DOORS THAT WILL BE INSTALLED PRIOR
 TO INTERIOR WORK.
  
 4) PLEASE CLARIFY ON PLANS THE SCOPE OF EXTERIOR WOK
 ONLY. NO INTERIOR BUILD OUT ON THIS PERMIT AND ONLY
 LIFE SAFETY TO THE EXTENT OF HOW IT AFFECTS CHANGES IN
 PERIMETER EGRESS. FOR EXAMPLE THE PLANS STATE COURTYARD
 BY SEPARATE PERMIT. SOMETHING ALONG THOSE LINES FOR
 INTERIOR WORK WOULD HELP CLARIFY THE SCOPE OF EXTERIOR
 WORK.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-10-16 Cont ID  
Sent By jpearson Date 2019-10-16 Time 08:44 Rev Time 0.00
Received By jpearson Date 2019-10-16 Time 08:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-12-11 Cont ID  
Sent By rrossano Date 2019-12-11 Time   Rev Time 0.00
Received By rrossano Date 2019-12-11 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-10-15 Cont ID  
Sent By rrossano Date 2019-10-15 Time   Rev Time 0.00
Received By rrossano Date 2019-10-15 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By rrossano Date 2019-08-19 Time   Rev Time 0.00
Received By rrossano Date 2019-08-19 Time   Sent To  
Notes
2019-08-19 11:34:22PLEASE ADDRESS BUILDING COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-12 Cont ID  
Sent By dbattles Date 2019-12-12 Time 07:45 Rev Time 0.00
Received By dbattles Date 2019-11-19 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-17 Cont ID  
Sent By cpuell Date 2019-10-17 Time 09:44 Rev Time  
Received By gjohnson Date 2019-09-18 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By lmarchan Date 2019-08-20 Time 09:35 Rev Time 0.00
Received By lmarchan Date 2019-07-17 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-09 Cont ID  
Sent By shill Date 2019-12-09 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2019-12-09 Time 10:30 Sent To  
Notes
2019-12-20 08:37:43PLUMBING NOTES:
 APPROVED FOR STORM DRAIN ON VERSA WALL ONLY.
 ALL IRRIGATION SYSTEMS SHALL HAVE A BACK FLOW DEVISE
 WITH SEPARATE PERMIT
 SEE MAIN PERMIT 19090882
  
2019-12-12 17:20:46REVIEWED REMOTELY BY GEORGE JOHNSON
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By gjohnson Date 2019-10-17 Time 09:44 Rev Time 0.00
Received By gjohnson Date 2019-10-17 Time 09:11 Sent To  
Notes
2019-10-17 09:44:051ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A DETAILED SCOPE OF PROPOSED PLUMBING
 WORK IT IS NOT CLEAR ON THE PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 2. PROVIDE CIVIL PLAN NOTED ON SHT. FP101 PER WPB AMEND
 TO FBC 107.2.1
  
 3. IT IS UNCLEAR WHAT THE NOTE IS FOR 4" STM FOR VERSA
 WALL IS THIS A STORM DRAIN IF SO PROVIDE CALCULATIONS
 FOR SIZING. PER WPB AMEND TO FBC 107.2.1 AND PER WPB
 AMEND TO FBC 107.2.1
  
 4. WHAT IS THE VERSA WALL. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE PROVIDE DETAIL FOR STM DRAIN PIPING. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-11-21 Cont ID  
Sent By dbattles Date 2019-11-21 Time 15:15 Rev Time 0.00
Received By dbattles Date 2019-11-21 Time 15:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By dbattles Date 2019-10-02 Time 08:31 Rev Time 0.00
Received By dbattles Date 2019-10-02 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By dbattles Date 2019-08-12 Time 12:55 Rev Time 0.00
Received By dbattles Date 2019-08-12 Time 12:55 Sent To  
Notes
2019-08-12 12:55:20FIRST REVIEW SHEETS OK.
  
 ANY ADDITIONAL SHEETS FOR RE-SUBMITTAL TO BE DIGITALLY
 SIGNED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-10-10 Cont ID  
Sent By dbattles Date 2019-10-02 Time 08:27 Rev Time 0.00
Received By dbattles Date 2019-10-02 Time 08:27 Sent To  
Notes
2019-10-02 08:29:51PLEASE CONTACT ME TO DISCUSS THRESHOLD INSPECTOR
 AGREEMENT (SEE PREVIOUS REVIEW COMMENTS)
  
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By dbattles Date 2019-08-12 Time 12:53 Rev Time 0.00
Received By dbattles Date 2019-08-12 Time 12:53 Sent To  
Notes
2019-08-12 13:00:09I SEE THAT A THRESHOLD AGREEMENT WAS SUBMITTED AND
 APPROVED FOR THE DEMO PERMIT.
 IF THEY WILL CONTINUE TO BE THE THRESHOLD FOR THE
 EXTERIOR STRUCTURAL MODIFICATION PLEASE SEND UPDATED
 AGREEMENT TO INCLUDE THE PERMIT NUMBER OF THE EXTERIOR
 WORK. (19070831)
 THIS CAN BE DIGITALLY SIGNED AND UPLOADED TO THE
 SUPPORTING DOCUMENTS, OR 3 ORIGINALS BROUGHT INTO
 DEVELOPMENT SERVICES AS SUBMITTAL.
 IF CHANGING THE THRESHOLD INSPECTOR THAN SEND ME E-MAIL
 DRAFT OF NEW COMPANY FOR APPROVAL.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-12-11 Cont ID  
Sent By aaponte Date 2019-12-11 Time 15:55 Rev Time 0.00
Received By aaponte Date 2019-12-11 Time 15:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-15 Cont ID  
Sent By aaponte Date 2019-10-15 Time 11:32 Rev Time 0.00
Received By aaponte Date 2019-10-15 Time 11:32 Sent To  
Notes
2019-10-15 11:35:25PROVISO: NEW ENTRY DOORS ALONG DATURA STREET SHALL BE
 RECESSED SO THEY DO NOT ENCROACH INTO THE ROW MORE THAN
 ONE FOOT WHEN OPEN.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By aaponte Date 2019-08-20 Time 08:57 Rev Time 0.00
Received By aaponte Date 2019-08-20 Time 08:57 Sent To  
Notes
2019-08-20 09:00:291. PLEASE INCLUDE THE CANOPY PROJECTION IN THE SITE
 PLAN AND THE FLOOR PLANS. INCLUDE DIMENSION.
 2. PLEASE INCLUDE DIMENSION ON THE VERTICAL CLEARANCE
 FOR THE CANOPY.
 3. ARTIFICIAL TURF IS NOT ALLOWED IN ANY AREA THAT IS
 VISIBLE FROM THE PUBLIC. PLEASE CLARIFY THE LOCATION OF
 THE ARTIFICIAL TURF.
 4. PLEASE NOTE THAT IF THE TOTAL COST OF THE PROJECT
 EXCEED MORE THAN 50% OF THE BUILDING ASSESSED VALUE
 ACCORDING TO PAPA, STREETSCAPE IMPROVEMENT WOULD BE
 REQUIRED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.