2019-07-15 11:32:39 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS. |
| FBC 6TH EDITION (2017). |
| |
| 1- DOOR PRODUCT APPROVAL SUBMITTED IS FOR NON-IMPACT |
| GLAZED DOORS. NEED TO PROVIDE IMPACT PROTECTION AS |
| REQUIRED BY SEC. 707.4 FBC-EXISTING BUILDING. |
| |
| 2- PROVIDE FLOOR PLAN OR SKETCH IDENTIFYING THE ROOMS |
| WHERE WINDOWS ARE GOING TO BE REPLACED. FOR EXAMPLE: |
| BEDROOM, LIVING AREA, ETC. ALSO, SPECIFY THE SIZE AND |
| TYPE OF EXISTING WINDOW AND SIZE AND TYPE OF PROPOSED |
| WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS |
| REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING. |
| |
| 3-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| 109.3 CITY AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY |
| OF SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |