Plan Review Details - Permit 19070669
Plan Review Stops For Permit 19070669
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-06 Cont ID  
Sent By jleahy Date 2019-08-06 Time 11:41 Rev Time 0.00
Received By jleahy Date 2019-08-06 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By jleahy Date 2019-07-24 Time 15:33 Rev Time 0.00
Received By jleahy Date 2019-07-24 Time 15:33 Sent To  
Notes
2019-07-24 15:42:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 MAIN TO DOCK TO MEET 555.3 GFCI PROTECTION
 REQUIREMENTS.
  
 FAULT CURRENT CALCULATION REQUIRED FOR THE SERVICE.
 110.9, 10
  
 MAIN FEEDING DOCK IS 150A WITH #6 WIRE???
  
 PVC ON UNDERSIDE OF DOCK WILL HAVE TO MEET 352.44
 EXPANSION FITTING REQUIREMENTS.
  
 CONNECTIONS ON DOCK SHALL MEET 555.9
  
 TRANSFORMER AND SERVICE TO MEET 555.5 , AND 555.7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-06 Cont ID  
Sent By jleahy Date 2019-08-06 Time 11:41 Rev Time 0.00
Received By jleahy Date 2019-08-01 Time 15:02 Sent To  
Notes
2019-08-02 15:02:29RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-24 Cont ID  
Sent By jleahy Date 2019-07-24 Time 15:42 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 14:06 Sent To  
Notes
2019-07-16 14:06:25ROUTED TO ELECTRICAL INBOX