Plan Review Details - Permit 19070664
Plan Review Stops For Permit 19070664
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-01 Cont ID  
Sent By pvalenti Date 2019-10-01 Time 11:27 Rev Time 0.00
Received By pvalenti Date 2019-10-01 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 13:23 Rev Time 0.00
Received By shill Date 2019-09-24 Time 13:23 Sent To  
Notes
2019-09-24 13:23:12***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 THIS REVIEW CAN NOT PASS UNTIL PERMIT NUMBER 19060008
 (RAMP) IS APPROVED. THE RAMP PERMIT STILL HAS PENDING
 COMMENTS FROM PRIOR REVIEW THAT HAVE NOT BEEN
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-16 Cont ID  
Sent By pvalenti Date 2019-08-16 Time 07:34 Rev Time 0.00
Received By pvalenti Date 2019-08-16 Time 07:34 Sent To  
Notes
2019-08-16 07:39:55***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 THIS REVIEW CAN NOT PASS UNTIL PERMIT NUMBER 19060008
 (RAMP) IS APPROVED. THE RAMP PERMIT STILL HAS PENDING
 COMMENTS FROM PRIOR REVIEW THAT HAVE NOT BEEN
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 14:45 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 14:44 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By jpearson Date 2019-08-12 Time 13:55 Rev Time 0.00
Received By jpearson Date 2019-08-12 Time 10:59 Sent To  
Notes
2019-08-12 13:10:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO REVISIONS ARE INDICATED ON PLAN SHEET. THE ONLY
 CHANGE I CAN SEE IS THAT THE METER CAN IS SHOWN INSIDE
 THE HALLWAY, WHICH IS OBVIOUSLY NOT CORRECT. PROVIDE
 NARRATIVE OF CHANGES AND CLOUD CHANGES ON PLAN. CORRECT
 THE LOCATION OF METER CAN ON PLAN. WPB FBC 107.2.1
 2. AS A PROVISO ON THE ORIGINAL PLAN, IT WAS NOTED THAT
 THE OUTSIDE DISCONNECT MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT, WHICH IN A LETTER FROM FPL WAS STATED AS
 21110 AIC. THE DISCONNECT ON THIS PLAN STILL SHOWS A
 RATING OF 10,000 AIC. PROVIDE CORRECTION. NEC 110.9,
 110.10; FBC RE E3606.3
 3. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 4. LOAD CALCULATION STATES THIS IS A 125 AMP SERVICE.
 RISER DIAGRAM INDICATES THIS IS A 100 AMP SERVICE.
 CORRECT DISCREPANCY. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-01 Cont ID  
Sent By pvalenti Date 2019-10-01 Time 11:27 Rev Time 0.00
Received By pvalenti Date 2019-09-26 Time 17:10 Sent To  
Notes
2019-09-26 17:10:35TO PV DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-10 Time 15:05 Sent To  
Notes
2019-09-11 15:05:40B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-16 Cont ID  
Sent By pvalenti Date 2019-08-16 Time 07:41 Rev Time 0.00
Received By pvalenti Date 2019-07-15 Time 15:05 Sent To  
Notes
2019-08-15 12:00:58PETER VALENTI'S DESK
2019-07-16 15:05:34B03

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-23 Cont ID  
Sent By gjohnson Date 2019-09-23 Time 11:54 Rev Time 0.00
Received By gjohnson Date 2019-09-23 Time 11:54 Sent To  
Notes
2019-09-23 11:55:37PLANS APPROVED AND STAMPED BY JERALD SMITH ON 8/15/19

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-15 Cont ID  
Sent By jesmith Date 2019-08-15 Time 11:51 Rev Time 0.00
Received By jesmith Date 2019-08-15 Time 11:49 Sent To  
Notes
2019-08-15 11:51:01PLUMBING COMMEMTS: APPROVED
 MASTER PERMIT #18101088
 19070874 2450 PRESIDENTIAL WAY 1706
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-09-19 Cont ID  
Sent By llouie Date 2019-09-19 Time   Rev Time 0.00
Received By llouie Date 2019-09-19 Time   Sent To  
Notes
***NONE***