Plan Review Details - Permit 19070530
Plan Review Stops For Permit 19070530
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2019-08-16 Cont ID  
Sent By shill Date 2019-08-16 Time 12:26 Rev Time 0.00
Received By shill Date 2019-08-16 Time 12:26 Sent To  
Notes
2019-08-16 12:26:53ADDRESS ASSIGNED BY M.ORIO
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 10:40 Rev Time 0.00
Received By shill Date 2019-09-24 Time 10:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-16 Cont ID  
Sent By jgomez Date 2019-08-16 Time 17:40 Rev Time 0.00
Received By jgomez Date 2019-08-16 Time 10:53 Sent To  
Notes
2019-08-16 17:44:20TEMPORARY BUILDING USED EXCLUSIVELY FOR CONSTRUCTION
 PURPOSES IS EXEMPT FROM FBC. (SEE LETTER FROM
 CONTRACTOR). LOCATION OF BUILDING IS OUTSIDE OF THE
 FLOOD ZONE. NO REVIEW WAS DONE ON THE TRAILER ITSELF.
 JG.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-01 Cont ID  
Sent By jleahy Date 2019-10-01 Time 15:54 Rev Time 0.00
Received By jleahy Date 2019-10-01 Time 15:54 Sent To  
Notes
2019-10-01 15:55:25PUT IN RESULTS FOR JPEARSON JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-23 Cont ID  
Sent By jpearson Date 2019-09-23 Time 11:19 Rev Time 0.00
Received By jpearson Date 2019-09-23 Time 08:31 Sent To  
Notes
2019-09-23 11:19:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MODULAR DESIGN PLANS PROVIDED STATE THAT THERE ARE 2
 ELECTRICAL PANELS. THE LOAD CALCULATION SHOWN ON THESE
 PLANS IS 97 AMPS FOR PANEL A, AND 65 AMPS FOR PANEL B.
 THE LOAD CALCULATION PROVIDED ON THE RISER DIAGRAM DOES
 NOT MATCH THIS. PROVIDE CLARIFICATIONS AND CORRECTIONS.
 NEC 220.
 2. BASED ON LOAD CALCULATIONS, THE PROPOSED 100 AMP
 SERVICE IS NOT ADEQUATE TO SUPPLY THE LOAD. PROVIDE
 CORRECTION. NEC 215.2, 220
 3. A MAIN BREAKER IS REQUIRED AT THE SERVICE LOCATION.
 RISER PROVIDED SHOWS A 100 AMP METER CAN FEEDING #6
 WIRES WITH NO OVER CURRENT PROTECTION. THIS WIRE IS NOT
 RATED FOR 100 AMPS. THE SERVICE DOES NOT SHOW THE
 REQUIRED MAIN BREAKER. PROVIDE CORRECTION. NEC 230.70,
 310.15(B)(16)
 4. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-02 Cont ID  
Sent By fgiaquin Date 2019-08-02 Time 14:44 Rev Time 0.00
Received By fgiaquin Date 2019-08-02 Time 13:30 Sent To  
Notes
2019-08-02 14:44:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW LOCATION OF TEMP SERVICE ON PLANS THAT WILL
 FEED JOBSITE TRAILER. PROVIDE LOAD CALCULATION AND ALL
 PERTINENT INFORMATION FOR TEMP SERVICE. FBC 107.2.1 NEC
 220
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By pleduc Date 2019-09-09 Time   Rev Time 0.00
Received By pleduc Date 2019-09-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By pleduc Date 2019-07-15 Time   Rev Time 0.00
Received By pleduc Date 2019-07-15 Time 13:57 Sent To  
Notes
2019-07-15 14:02:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO ADDRESS INDICATED ON THE DITE PLAN NOR
 APPLICATION.
  
 PLEASE PROVIDE AN ADDRESS.
  
  
 2) THERE IS NO INDICATION OF DIMESNIONS FROM EXISTING
 OR PROPOSED BUILDINGS.
  
 SEPARATION DISTANCES SHALL MEET NFPA 241,
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES
  
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 PLEASE PROVIDE DISTANCE SEPARATION IN COMPLIANCE WITH
 THE ABOVE OR PROVIDE FIRE SPRINKLER PROTECTION FOR A
 75% DISTANCE REDUCTION.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-01 Cont ID  
Sent By jleahy Date 2019-10-01 Time 15:54 Rev Time 0.00
Received By jleahy Date 2019-09-27 Time 13:38 Sent To  
Notes
2019-10-01 13:38:54RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 10:40 Rev Time 0.00
Received By shill Date 2019-09-05 Time 11:30 Sent To  
Notes
2019-09-06 11:31:02B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By lmarchan Date 2019-08-20 Time 16:13 Rev Time 0.00
Received By lmarchan Date 2019-07-11 Time 14:22 Sent To  
Notes
2019-07-12 14:22:39B18

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By jesmith Date 2019-09-17 Time 14:59 Rev Time 0.00
Received By jesmith Date 2019-09-17 Time 14:59 Sent To  
Notes
2019-09-17 14:59:38PLUMBING COMMENTS: APPROVED
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-06 Cont ID  
Sent By jesmith Date 2019-08-06 Time 14:15 Rev Time 0.00
Received By jesmith Date 2019-08-06 Time 14:15 Sent To  
Notes
2019-08-06 14:15:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS:
  
 A. PER FBC 107.2.1, PROVIDE THE FOLLOWING:
  
 1. PROVIDE PLAN WITH STATE OF FLORIDA (DBPR)
 CERTIFICATION FOR MODULAR STRUCTURES.
 2. ON SITE PLAN, SHOW WATER SERVICE FROM METER TO
 STRUCTURE?S POINT OF CONNECTION AND PROVIDE BFP
 (BACKFLOW PREVENTER) TO COMPLY WITH WPB CROSS
 CONNECTION CONTROL. A SEPARATE PERMIT IS REQUIRED FOR
 THE BFP.
 3. ON SITE PLAN, SHOW LOCATION OF 250 GALLON HOLDING
 TANK AND SANITARY BUILDING DRAIN FROM SANITARY OUTLETS
 TO THE TANK.
  
 B. PER WPB FBC 107.1, PLAN SHOWING WATER AND SEWER SITE
 SERVICES SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL PER ES 471 AND 61G15 FAC OR FS 481 AND
 61G1 FAC AND BEAR THE SEAL AND SIGNATURE OF SAID DESIGN
 PROFESSIONAL.
  
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
  
  
 19070530 401 CLEMATIS ST
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By jroach Date 2019-09-13 Time 10:41 Rev Time 0.00
Received By jroach Date 2019-09-13 Time 10:29 Sent To  
Notes
2019-09-13 10:41:46ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09.13.2019
 PERMIT NO.: 19070530
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL TRAILERS SHALL BE REMOVED WITHIN 7 DAYS OF THE
 FINAL CONSTRUCTION INSPECTION BY THE CITY AND PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR THE
 PROJECT AT 1500 CENTREPARK BOULEVARD. THE TRAILER SHALL
 BE REMOVED AND THE SITE SHALL BE TILLED AND PLANTED
 WITH GROUND COVER TO INCLUDE SODDING OR SEEDING WHICH
 SHALL HAVE IRRIGATION AND SHALL BE MAINTAINED IN
 ACCORDANCE WITH SECTIONS 74-2 AND 94-446 OF THE CITY?S
 CODE OF ORDINANCES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By elevesqu Date 2019-08-20 Time 13:27 Rev Time 0.00
Received By jroach Date 2019-08-20 Time 13:23 Sent To  
Notes
2019-08-20 14:57:23ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.20.2019
 PERMIT NO.: 19070530
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE CLARIFY THE PURPOSE OF THIS CONSTRUCTION
 TRAILER; IS THIS ASSOCIATED WITH THE RESIDENTIAL
 DEVELOPMENT PROPOSED AT 1500 CENTREPARK BOULEVARD?
  
 THE FOLLOWING ARE PROVIDED FOR INFORMATIONAL PURPOSES
 ONLY:
  
 A. ALL TRAILERS SHALL BE REMOVED WITHIN 7 DAYS OF THE
 FINAL CONSTRUCTION INSPECTION BY THE CITY AND PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY. THE TRAILER
 SHALL BE REMOVED AND THE SITE SHALL BE TILLED AND
 PLANTED WITH GROUND COVER TO INCLUDE SODDING OR SEEDING
 WHICH SHALL HAVE IRRIGATION AND SHALL BE MAINTAINED IN
 ACCORDANCE WITH SECTIONS 74-2 AND 94-446 OF THE CITY?S
 CODE OF ORDINANCES.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH