Plan Review Details - Permit 19070355
Plan Review Stops For Permit 19070355
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-17 Cont ID  
Sent By rmcdouga Date 2019-10-17 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2019-10-17 Time 13:12 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-22 Cont ID  
Sent By rmcdouga Date 2019-07-22 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2019-07-22 Time 13:31 Sent To  
Notes
2019-07-22 13:34:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 HANDWRITTEN SIGNATURE OF THE ENGINEER PER FS 471 AND
 FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  
  
2019-07-13 04:42:30LOGGED IN BY MISTAKE

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-16 Cont ID  
Sent By jleahy Date 2019-10-16 Time 15:21 Rev Time 0.00
Received By jleahy Date 2019-10-16 Time 15:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jleahy Date 2019-07-23 Time 14:20 Rev Time 0.00
Received By jleahy Date 2019-07-23 Time 14:20 Sent To  
Notes
2019-07-23 14:22:25 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SUBMIT A SIGNED CONTRACT FOR WORK INVOLVED
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-07-13 Cont ID  
Sent By abelisle Date 2019-07-13 Time 07:05 Rev Time 0.00
Received By abelisle Date 2019-07-13 Time 03:32 Sent To  
Notes
2019-07-13 03:39:227/13/19 DENIED
  
 THE PLANS INDICATE AN EXISTING GAS METER. THE BTU LOAD
 OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES.
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING
 PERMITS VALUATIONS.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-10-28 Cont ID  
Sent By abelisle Date 2019-10-28 Time 07:17 Rev Time 0.00
Received By abelisle Date 2019-10-28 Time 07:17 Sent To I
Notes
2019-10-28 07:19:3410/28/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING/GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 A. BELISLE
 PLUMBING PLAN EXAMINER
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-28 Cont ID  
Sent By cpuell Date 2019-10-28 Time 09:17 Rev Time 0.00
Received By cpuell Date 2019-10-10 Time 14:26 Sent To  
Notes
2019-10-10 14:26:13RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-23 Cont ID  
Sent By jleahy Date 2019-07-23 Time 14:23 Rev Time 0.00
Received By jleahy Date 2019-07-23 Time 14:22 Sent To  
Notes
2019-07-10 15:12:59ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By rfalcone Date 2019-10-11 Time 13:23 Rev Time 0.00
Received By rfalcone Date 2019-10-11 Time 13:23 Sent To E
Notes
2019-10-11 13:26:0110/11/19 PASSED.
  
 *** ZONING PROVISO***
  
 GENERATOR MUST NOT ENCROACH MORE THAN FOUR FEET INTO
 THE REAR SETBACK.
  
 RACHEL FALCONE
 ASSOCIATE PLANNER
 (561) 822-1442
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By ajones Date 2019-07-17 Time 16:25 Rev Time 0.00
Received By ajones Date 2019-07-17 Time 16:25 Sent To  
Notes
2019-07-17 16:32:377/17/19- FAILED. THE GENERATOR CAN BE LOCATED AT
 MAXIMUM OF 4 FEET INTO ANY REQUIRED SETBACK. THE
 REQUIRED SETBACK ALONG RIYLN DRVE IS 25 FEET.
 THEREFORE, THE GENERATOR CAN BE NO CLOSER THAN 21 FEET
 FOR THE PROPERTY LINE ALONG RIYLN DRIVE.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]