Plan Review Stops For Permit 19070355 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-10-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-10-17 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-10-17 |
Time |
13:12 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-07-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-07-22 |
Time |
13:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-07-22 |
Time |
13:31 |
Sent To |
|
|
Notes |
2019-07-22 13:34:23 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE | | HANDWRITTEN SIGNATURE OF THE ENGINEER PER FS 471 AND | | FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS. | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | USED. | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | | 2019-07-13 04:42:30 | LOGGED IN BY MISTAKE |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-10-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-10-16 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-10-16 |
Time |
15:21 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-07-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-07-23 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-07-23 |
Time |
14:20 |
Sent To |
|
|
Notes |
2019-07-23 14:22:25 | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | SUBMIT A SIGNED CONTRACT FOR WORK INVOLVED | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2019-07-13 |
|
|
Cont ID |
|
Sent By |
abelisle |
Date |
2019-07-13 |
Time |
07:05 |
Rev Time |
0.00 |
Received By |
abelisle |
Date |
2019-07-13 |
Time |
03:32 |
Sent To |
|
|
Notes |
2019-07-13 03:39:22 | 7/13/19 DENIED | | | | THE PLANS INDICATE AN EXISTING GAS METER. THE BTU LOAD | | OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL | | BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS | | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST | | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A | | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF | | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE | | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4, | | 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES. | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE | | APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED | | CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING | | PERMITS VALUATIONS. | | | | ATELYO BELISLE | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6695 | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
abelisle |
Date |
2019-10-28 |
Time |
07:17 |
Rev Time |
0.00 |
Received By |
abelisle |
Date |
2019-10-28 |
Time |
07:17 |
Sent To |
I |
|
Notes |
2019-10-28 07:19:34 | 10/28/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING/GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | A. BELISLE | | PLUMBING PLAN EXAMINER | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-10-28 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-10-10 |
Time |
14:26 |
Sent To |
|
|
Notes |
2019-10-10 14:26:13 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-07-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-07-23 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-07-23 |
Time |
14:22 |
Sent To |
|
|
Notes |
2019-07-10 15:12:59 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2019-10-11 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2019-10-11 |
Time |
13:23 |
Sent To |
E |
|
Notes |
2019-10-11 13:26:01 | 10/11/19 PASSED. | | | | *** ZONING PROVISO*** | | | | GENERATOR MUST NOT ENCROACH MORE THAN FOUR FEET INTO | | THE REAR SETBACK. | | | | RACHEL FALCONE | | ASSOCIATE PLANNER | | (561) 822-1442 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-07-17 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2019-07-17 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2019-07-17 |
Time |
16:25 |
Sent To |
|
|
Notes |
2019-07-17 16:32:37 | 7/17/19- FAILED. THE GENERATOR CAN BE LOCATED AT | | MAXIMUM OF 4 FEET INTO ANY REQUIRED SETBACK. THE | | REQUIRED SETBACK ALONG RIYLN DRVE IS 25 FEET. | | THEREFORE, THE GENERATOR CAN BE NO CLOSER THAN 21 FEET | | FOR THE PROPERTY LINE ALONG RIYLN DRIVE. | | | | ANGELLA VANN, AICP | | 561-822-1441 | | [email protected] |
|
|