Plan Review Stops For Permit 19070244 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2020-01-31 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2020-01-31 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-12-27 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-12-27 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-12-27 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-09-18 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-09-18 |
Time |
12:49 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-09-18 |
Time |
12:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2019-08-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-08-01 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-01 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-01-28 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-01-28 |
Time |
07:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2020-01-07 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-01-07 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-01-07 |
Time |
08:24 |
Sent To |
|
|
Notes |
2020-01-07 08:38:37 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | REVISION NARRATIVE COMMENTS FOR ELECTRIC. | | | | 1) #27,28 NO WORK SHOWN NO CHANGES | | | | 2) #29 ROOM #108 IS STORAGE ROOM | | | | 3) #30 ROOM 109 IS A LAB | | | | 4) #32 ROOM 112 IS THE BREAKROOM | | | | 5) #33 PAN IS ROOM 114 | | | | 6) #34 ROOM 103 IS A CLOSET | | | | 7) #35 ROOM 102 IS A CLOSET | | | | 8) #36 ROOM 111 IS POLISH | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-09-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-09-16 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-09-16 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2019-07-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-07-23 |
Time |
07:10 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-07-23 |
Time |
07:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2020-01-24 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-01-24 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-01-24 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2019-12-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-12-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-12-30 |
Time |
16:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2019-09-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-09-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-09-09 |
Time |
10:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2019-07-11 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2019-07-11 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-07-11 |
Time |
10:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-04-10 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-04-10 |
Time |
11:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-03-16 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-02-13 |
Time |
13:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2020-02-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-02-10 |
Time |
18:24 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-01-23 |
Time |
11:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-01-09 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-01-09 |
Time |
19:28 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-12-19 |
Time |
12:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-09-23 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-09-06 |
Time |
10:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-08-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-08-02 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-07-03 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2020-02-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-02-10 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-02-10 |
Time |
08:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2020-01-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-01-06 |
Time |
17:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-01-06 |
Time |
17:12 |
Sent To |
|
|
Notes |
2020-01-06 17:30:43 | 3RD REVIEW FBC-2017 MECHANICAL | | PERMIT #19070244 | | 1/6/20 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | THE MECHANICAL PLANS WERE APPROVED ON 8/14/19 WITH THE | | PROVISOS LISED BELOW. THE REVISED PLAN DATED 9/6/19 TO | | ADDRESS THOSE PROVISOS IS NOT IN COMPLIANCE. SEE | | PROVISOS LISTED BELOW | | | | | | MECHANICAL PROVISOS: | | | | THE MECHANICAL PLAN IS APPROVED WITH EXCEPTION- A | | REVISION IS REQUIRED TO ADDRESS THESE ISSUES: | | | | 1) PROVIDE AN INDEPENDENT EXHAUST VENTILATION SYSTEM | | FOR THE LAB IF CHEMICAL PROCESSING OR TESTING IS | | PERFORMED IN THE ROOM. | | | | 2) THE POLISH ROOM AND TOILET ROOM EXHAUST DUCTS MUST | | BE RUN INDEPENDENTLY FROM INLET TO OUTLET. | | | | 3) THE TRANSFER DUCT (JUMPER) RETURNING AND | | RECIRCULATING AIR FROM THE LAB TO THE CORRIDOR IS NOT | | ALLOWED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2019-09-23 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-09-23 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-09-23 |
Time |
10:58 |
Sent To |
|
|
Notes |
2019-09-23 11:04:33 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #19070244 | | 9/23/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | THE MECHANICAL PLANS WERE APPROVED ON 8/14/19 WITH THE | | PROVISOS LISED BELOW. THE REVISED PLAN SUBMITTED ON | | 9/6/19 TO ADDRESS THOSE PROVISOS IS NOT IN COMPLIANCE. | | SEE PROVISOS LISTED BELOW | | | | | | MECHANICAL PROVISOS: | | | | THE MECHANICAL PLAN IS APPROVED WITH EXCEPTION- A | | REVISION IS REQUIRED TO ADDRESS THESE ISSUES: | | | | 1) PROVIDE AN INDEPENDENT EXHAUST VENTILATION SYSTEM | | FOR THE LAB IF CHEMICAL PROCESSING OR TESTING IS | | PERFORMED IN THE ROOM. | | | | 2) THE POLISH ROOM AND TOILET ROOM EXHAUST DUCTS MUST | | BE RUN INDEPENDENTLY FROM INLET TO OUTLET. | | | | 3) THE TRANSFER DUCT (JUMPER) RETURNING AND | | RECIRCULATING AIR FROM THE LAB TO THE CORRIDOR IS NOT | | ALLOWED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2019-08-14 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-08-14 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-08-14 |
Time |
16:27 |
Sent To |
|
|
Notes |
2019-08-14 16:29:00 | 2ND MECHANICAL REVIEW | | | | APPROVED PER CHRIS COLE (REMOTELY) WITH PROVISO: | | | | PROVIDE LAB EXHAUST SYSTEM PRIOR TO C.O. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2019-08-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-08-02 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-08-02 |
Time |
07:51 |
Sent To |
|
|
Notes |
2019-08-02 07:51:23 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19070244 | | 8/1/2019 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M1: THE RETURN AIR TRANSFERS FROM THE ROOMS | | INTO THE CORRIDORS (LABELED HALLS ON THE PLAN) ARE | | PROHIBITED PER SECTION 601.2 FBC M. | | | | 2) M1: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER | | SF. IS REQUIRED FOR THE LAB AND RECIRCULATION OF AIR | | FROM THE ROOM IS PROHIBITED EXCEPT WHERE THE AIRSTREAM | | CONSISTS OF NOT MORE THAN 10% OF THE AIR SUPPLIED TO | | THE ROOM- TABLE 403.3.1.1 FOOTNOTE G. | | | | 3) REFER TO SECTIONS 510.1 & 510.2 FBC M AND CLARIFY | | THE PROCESSES THAT OCCUR IN THE LAB AND WHAT MATERIALS | | ARE STORED AND USED FOR PROCESSING IN THE ROOM. | | PLEASE PROVIDE A LIST OF MATERIALS AND THEIR | | QUANTITIES- SECTION 414.1.3 FBC B. | | | | 510.2 WHERE REQUIRED. | | | | A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER | | OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF | | HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST | | SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE | | POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: | | 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT | | IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER | | FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED | | ROOM TEMPERATURE. | | 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD | | RATING OF 4 IS PRESENT IN ANY CONCENTRATION. | | 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD | | RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS | | EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION | | OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. | | | | EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, | | EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE | | EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A | | HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN | | CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL | | CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION | | TOXICITY. | | | | 4) M1: PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES, AND AIR BALANCE CALCULATIONS- TABLE | | 403.3.1.1 AND SECTION 501.4 FBC M. | | | | 5) M1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE | | POLISH ROOM, AND INDICATE WHAT TYPE OF FUMES, MISTS, OR | | VAPORS ETC. ARE BEING EXHAUSTED FROM THE ROOM. ARE | | THEIR ANY FUME OR CAPTURE HOODS IN THE ROOM OR IN THE | | LAB? | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | BUILDING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | | | |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
3 |
Status |
P |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-04-10 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-04-10 |
Time |
11:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
2 |
Status |
F |
Date |
2020-03-06 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-03-06 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-03-03 |
Time |
17:35 |
Sent To |
|
|
Notes |
2020-03-06 16:41:37 | 03/05/20 2ND MEDICAL GAS REVISION REVIEW **DENIED** | | WITH COMMENTS | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS | | | | REFERENCE: NFPA 99 2012 EDITION | | | | 1. EQUIPMENT SPECIFICATIONS DO PROVIDE GENERIC DETAILS | | FOR CONNECTIONS, BUT DO NOT ADDRESS THE DISTRIBUTION | | AND CONFIGURATIONS OF THIS EQUIPMENT LAY OUT THAT IS | | NEEDED TO GUIDE THE CONTRACTOR AND INSTALLERS AS WELL | | AS ALLOWING THE INSPECTOR TO INSPECT FOR NFPA 99 | | COMPLIANCE AND TO CONFIRM THAT THE INSTALLATION | | CONFORMS TO THE DESIGNER?S INTENT, PROVIDE DETAILS ON | | THE PLAN THAT CLEARLY INDICATE THE MANIFOLDS AND PIPING | | DISTRIBUTION AND CONFIGURATIONS REQUIRED FOR A COMPLETE | | INSTALLATION. THIS INCLUDES A RISER DIAGRAMS FOR ALL | | THE MEDICAL GAS PIPING TO BE INSTALLED. PROVIDE | | ISOMETRIC DRAWING FOR MED GAS INCLUDING VACUUM EXHAUST | | PER THE WPB AMENDMENTS TO FBC 107.3.5.1.3(13). | | | | 2. ALL WATER TUBES MEDICAL GAS SHALL BE IN ACCORDANCE | | WITH NFPA 99 2012 SECTION 5.3.7.2.1. WITH ASTM B 819, | | STANDARD SPECIFICATION FOR SEAMLESS COPPER. | | | | 3. THERE ARE 2 P-3 SHEETS WHICH ON HAS A REVISION DATE | | SO PLEASE DELETE THE ONE NOT NEEDED PER THE WPB AMEND | | TO FBC 107.2.1. | | | | 4. PLEASE PROVIDE SPECIFICATION FOR VACUUM PUMP AND FOR | | AIR COMPRESSOR SHOWING COMPLIANCE PER THE WPB | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | 5. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION | | GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING THE DENTAL | | CHAIRS, TANKS AND VALVES PER THE WPB AMEND TO FBC | | 107.2.1. | | | | 6. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR | | COMPRESSOR SHALL BE VENTILATED PER NFPA 99 SECS. | | 5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1. | | | | 7. PIPING SYSTEMS FOR CATEGORY 3 GASES SHALL NOT BE | | USED AS GROUNDING ELECTRODES PER THE NFPA 99 2012 SEC. | | 5.3.13.2.2. | | | | 8. ALL DOCUMENTATION PERTAINING TO INSPECTIONS AND | | TESTING SHALL BE MAINTAINED ON-SITE PER THE NFPA 99 | | 2012 SEC. 5.3.9.1.5. | | | | 9. PROVIDE A DETAIL FOR RESTRAINTS ON THE OXYGEN TANK | | INCLUDING WALL ANCHORAGE PER THE WPB AMEND TO FBC | | 107.2.1. | | | | 10. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE | | 2017 WPB A TO FBC 107.5. | | | | 11. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM | | EXHAUST AND RELIEF PIPING ON THE ROOF PLAN, IT SHALL BE | | DISCHARGED ABOVE ROOF IN A SEPARATE VENT PER THE NFPA | | 99 2012 SEC. 5.3.8.3.11. (1). | | | | 12. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS | | SYSTEM IS DESIGNED TO BE PER THE NFPA 99 CHAPTER 4, | | CATEGORY 3. | | | | 13. PROVIDE COMPLETED INSTALLATION MANUALS FOR ALL NEW | | MED GAS EQUIPMENT IN DETAIL PER THE 2017 WPB A TO | | SECTION FBC 107.3.5. | | | | 14. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER | | THE WPB AMEND TO FBC 107.2.1. | | | | 15. PLEASE PROVIDE A LEGEND FOR ALL GAS VALVES PER THE | | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | 16. PLEASE PROVIDE DETAIL HOW PIPING IS GOING TO BE | | SUPPORTED IN ACCORDANCE WITH NFPA 2012 5.3.7.3.3 PIPE | | SUPPORT. PIPE SUPPORT SHALL BE IN ACCORDANCE. | | | | 17. FILTER MUST COMPLY WITH NSF 42 PLEASE SUBMIT | | MANUFACTURES SPECIFICATION FOR COMPLIANCE PER THE WPB | | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | 18. PLEASE PROVIDE HOW WARNING SYSTEM WILL ABIDE PER | | THE 5.3.6.22.1 WARNING SYSTEMS FOR MEDICAL GAS SYSTEMS. | | | | 19. PLEASE PROVIDE HOW PIPE IS GOING TO BE LABELED PER | | THE 2012 NFPA 5.3.11.1.4 (1) AT INTERVALS OF NOT MORE | | THAN 6.1 M (20 FT). | | | | 20. PROVIDE PIPING DETAIL OF CONTROL VALVES AND TANK | | MANIFOLD ALSO DETAIL OF HOW TANK IS SECURED PER WPB | | AMEND TO FBC 107.2.1 AND NFPA 99. | | | | 21. PLEASE SHOW WHERE EMERGENCY VALVE IS LOCATED AND | | LABELED PER THE 2012 NFPA 5.3.6.19.3. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | [email protected] | | 561-701-6437 | | |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
1 |
Status |
F |
Date |
2020-02-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-02-10 |
Time |
18:24 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-02-10 |
Time |
18:24 |
Sent To |
|
|
Notes |
2020-02-10 18:24:32 | 3RD REVIEW:.19070244 | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | MED GAS COMMENTS: | | | | 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE | | INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED. | | INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON | | JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031 | | | | 2. PROVIDE NOTE ON PLAN MED GAS SHALL COMPLY WITH NFPA | | 99 | | | | 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION | | GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR. PER | | WPB AMEND TO FBC 107.2.1 | | | | 4. SHT. P3 KEY NOTE A REFERENCES SHT P6 BUT P6 HAS NOT | | BEEN UPLOADED PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 5. WHAT TYPE OF PIPING IS BEING USED FOR THE COMPRESSED | | AIR LINES. PER WPB AMEND TO FBC 107.2.1 | | | | 6. SHT P3 UNDER PLUMBING KEYNOTES ( DENTAL) REFERENCES | | DENTAL DRAWINGS THEY HAVE NOT BEEN DOWNLOADED PLEASE | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | END OF COMMENTS | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-04-10 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-04-10 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
N |
Date |
2020-03-12 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-03-12 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-03-12 |
Time |
15:27 |
Sent To |
|
|
Notes |
2020-03-12 15:25:55 | PLUMBING COMMENTS: APPROVED | | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | INSPECTOR'S APPROVAL | | | | 19070244 4100 S DIXIE HWY |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2020-02-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-02-10 |
Time |
18:23 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-02-10 |
Time |
15:17 |
Sent To |
|
|
Notes |
2020-02-10 18:23:57 | 3RD REVIEW:.19070244 | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | MED GAS COMMENTS: | | | | 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE | | INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED. | | INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON | | JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031 | | | | 2. PROVIDE NOTE ON PLAN MED GAS SHALL COMPLY WITH NFPA | | 99 | | | | 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION | | GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR. PER | | WPB AMEND TO FBC 107.2.1 | | | | 4. SHT. P3 KEY NOTE A REFERENCES SHT P6 BUT P6 HAS NOT | | BEEN UPLOADED PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 5. WHAT TYPE OF PIPING IS BEING USED FOR THE COMPRESSED | | AIR LINES. PER WPB AMEND TO FBC 107.2.1 | | | | 6. SHT P3 UNDER PLUMBING KEYNOTES ( DENTAL) REFERENCES | | DENTAL DRAWINGS THEY HAVE NOT BEEN DOWNLOADED PLEASE | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | END OF COMMENTS | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2020-01-09 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-01-09 |
Time |
19:28 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-01-09 |
Time |
19:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-09-21 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-09-21 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-09-21 |
Time |
13:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2019-07-24 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-07-24 |
Time |
17:05 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-07-24 |
Time |
17:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
6 |
Status |
N |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-04-10 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-04-10 |
Time |
11:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2020-03-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-03-03 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-03-03 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2020-01-31 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2020-01-31 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2019-12-27 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-12-27 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-12-27 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-09-18 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-09-18 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-09-18 |
Time |
12:50 |
Sent To |
|
|
Notes |
2019-09-18 12:51:36 | ALL SHEETS OK FOR SECOND REVIEW. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-08-01 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-08-01 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-01 |
Time |
10:30 |
Sent To |
|
|
Notes |
2019-08-01 10:32:29 | DRAWING SHEETS ARE NOT DIGITALLY SIGNED. | | PLEASE PROVIDE SHEETS THAT ARE DIGITALLY SIGNED, OR | | DROP OF HARD COPY UPON APPROVAL FOR SIGNATURE | | VERIFICATION. | | | | DYLAN BATTLES | | [email protected] | | 561-805-6718 |
|
|