Plan Review Details - Permit 19070244
Plan Review Stops For Permit 19070244
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-01-31 Cont ID  
Sent By dbattles Date 2020-01-31 Time 14:19 Rev Time 0.00
Received By dbattles Date 2020-01-31 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-27 Cont ID  
Sent By dbattles Date 2019-12-27 Time 11:01 Rev Time 0.00
Received By dbattles Date 2019-12-27 Time 11:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By dbattles Date 2019-09-18 Time 12:49 Rev Time 0.00
Received By dbattles Date 2019-09-18 Time 12:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-01 Cont ID  
Sent By shill Date 2019-08-01 Time 11:16 Rev Time 0.00
Received By dbattles Date 2019-08-01 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-01-28 Cont ID  
Sent By jleahy Date 2020-01-28 Time 07:09 Rev Time 0.00
Received By jleahy Date 2020-01-28 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-01-07 Cont ID  
Sent By jleahy Date 2020-01-07 Time 08:24 Rev Time 0.00
Received By jleahy Date 2020-01-07 Time 08:24 Sent To  
Notes
2020-01-07 08:38:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 REVISION NARRATIVE COMMENTS FOR ELECTRIC.
  
 1) #27,28 NO WORK SHOWN NO CHANGES
  
 2) #29 ROOM #108 IS STORAGE ROOM
  
 3) #30 ROOM 109 IS A LAB
  
 4) #32 ROOM 112 IS THE BREAKROOM
  
 5) #33 PAN IS ROOM 114
  
 6) #34 ROOM 103 IS A CLOSET
  
 7) #35 ROOM 102 IS A CLOSET
  
 8) #36 ROOM 111 IS POLISH
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 11:35 Rev Time 0.00
Received By jleahy Date 2019-09-16 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-23 Cont ID  
Sent By jleahy Date 2019-07-23 Time 07:10 Rev Time 0.00
Received By jleahy Date 2019-07-23 Time 07:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-01-24 Cont ID  
Sent By pleduc Date 2020-01-24 Time   Rev Time 0.00
Received By pleduc Date 2020-01-24 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-12-30 Cont ID  
Sent By pleduc Date 2019-12-30 Time   Rev Time 0.00
Received By pleduc Date 2019-12-30 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By pleduc Date 2019-09-09 Time   Rev Time 0.00
Received By pleduc Date 2019-09-09 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-11 Cont ID  
Sent By scaldero Date 2019-07-11 Time   Rev Time 0.00
Received By pleduc Date 2019-07-11 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-04-10 Cont ID  
Sent By lcrespo Date 2020-04-10 Time 11:36 Rev Time 0.00
Received By lcrespo Date 2020-04-10 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-03-16 Cont ID  
Sent By lmarchan Date 2020-03-16 Time 07:50 Rev Time 0.00
Received By lmarchan Date 2020-02-13 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-10 Cont ID  
Sent By gjohnson Date 2020-02-10 Time 18:24 Rev Time 0.00
Received By gjohnson Date 2020-01-23 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-09 Cont ID  
Sent By gjohnson Date 2020-01-09 Time 19:28 Rev Time 0.00
Received By gjohnson Date 2019-12-19 Time 12:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-06 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-02 Cont ID  
Sent By shill Date 2019-08-02 Time 07:51 Rev Time 0.00
Received By shill Date 2019-07-03 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-02-10 Cont ID  
Sent By ccole Date 2020-02-10 Time 10:09 Rev Time 0.00
Received By ccole Date 2020-02-10 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-01-06 Cont ID  
Sent By ccole Date 2020-01-06 Time 17:27 Rev Time 0.00
Received By ccole Date 2020-01-06 Time 17:12 Sent To  
Notes
2020-01-06 17:30:433RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19070244
 1/6/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE MECHANICAL PLANS WERE APPROVED ON 8/14/19 WITH THE
 PROVISOS LISED BELOW. THE REVISED PLAN DATED 9/6/19 TO
 ADDRESS THOSE PROVISOS IS NOT IN COMPLIANCE. SEE
 PROVISOS LISTED BELOW
  
  
 MECHANICAL PROVISOS:
  
 THE MECHANICAL PLAN IS APPROVED WITH EXCEPTION- A
 REVISION IS REQUIRED TO ADDRESS THESE ISSUES:
  
 1) PROVIDE AN INDEPENDENT EXHAUST VENTILATION SYSTEM
 FOR THE LAB IF CHEMICAL PROCESSING OR TESTING IS
 PERFORMED IN THE ROOM.
  
 2) THE POLISH ROOM AND TOILET ROOM EXHAUST DUCTS MUST
 BE RUN INDEPENDENTLY FROM INLET TO OUTLET.
  
 3) THE TRANSFER DUCT (JUMPER) RETURNING AND
 RECIRCULATING AIR FROM THE LAB TO THE CORRIDOR IS NOT
 ALLOWED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-09-23 Cont ID  
Sent By pvalenti Date 2019-09-23 Time 10:58 Rev Time 0.00
Received By ccole Date 2019-09-23 Time 10:58 Sent To  
Notes
2019-09-23 11:04:332ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19070244
 9/23/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE MECHANICAL PLANS WERE APPROVED ON 8/14/19 WITH THE
 PROVISOS LISED BELOW. THE REVISED PLAN SUBMITTED ON
 9/6/19 TO ADDRESS THOSE PROVISOS IS NOT IN COMPLIANCE.
 SEE PROVISOS LISTED BELOW
  
  
 MECHANICAL PROVISOS:
  
 THE MECHANICAL PLAN IS APPROVED WITH EXCEPTION- A
 REVISION IS REQUIRED TO ADDRESS THESE ISSUES:
  
 1) PROVIDE AN INDEPENDENT EXHAUST VENTILATION SYSTEM
 FOR THE LAB IF CHEMICAL PROCESSING OR TESTING IS
 PERFORMED IN THE ROOM.
  
 2) THE POLISH ROOM AND TOILET ROOM EXHAUST DUCTS MUST
 BE RUN INDEPENDENTLY FROM INLET TO OUTLET.
  
 3) THE TRANSFER DUCT (JUMPER) RETURNING AND
 RECIRCULATING AIR FROM THE LAB TO THE CORRIDOR IS NOT
 ALLOWED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By pvalenti Date 2019-08-14 Time 16:27 Rev Time 0.00
Received By ccole Date 2019-08-14 Time 16:27 Sent To  
Notes
2019-08-14 16:29:002ND MECHANICAL REVIEW
  
 APPROVED PER CHRIS COLE (REMOTELY) WITH PROVISO:
  
 PROVIDE LAB EXHAUST SYSTEM PRIOR TO C.O.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-02 Cont ID  
Sent By ccole Date 2019-08-02 Time 07:51 Rev Time 0.00
Received By shill Date 2019-08-02 Time 07:51 Sent To  
Notes
2019-08-02 07:51:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070244
 8/1/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE RETURN AIR TRANSFERS FROM THE ROOMS
 INTO THE CORRIDORS (LABELED HALLS ON THE PLAN) ARE
 PROHIBITED PER SECTION 601.2 FBC M.
  
 2) M1: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER
 SF. IS REQUIRED FOR THE LAB AND RECIRCULATION OF AIR
 FROM THE ROOM IS PROHIBITED EXCEPT WHERE THE AIRSTREAM
 CONSISTS OF NOT MORE THAN 10% OF THE AIR SUPPLIED TO
 THE ROOM- TABLE 403.3.1.1 FOOTNOTE G.
  
 3) REFER TO SECTIONS 510.1 & 510.2 FBC M AND CLARIFY
 THE PROCESSES THAT OCCUR IN THE LAB AND WHAT MATERIALS
 ARE STORED AND USED FOR PROCESSING IN THE ROOM.
 PLEASE PROVIDE A LIST OF MATERIALS AND THEIR
 QUANTITIES- SECTION 414.1.3 FBC B.
  
 510.2 WHERE REQUIRED.
  
 A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER
 OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF
 HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST
 SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE
 POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS:
 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT
 IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER
 FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED
 ROOM TEMPERATURE.
 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 4 IS PRESENT IN ANY CONCENTRATION.
 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS
 EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION
 OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY.
  
 EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1,
 EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE
 EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A
 HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN
 CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL
 CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION
 TOXICITY.
  
 4) M1: PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES, AND AIR BALANCE CALCULATIONS- TABLE
 403.3.1.1 AND SECTION 501.4 FBC M.
  
 5) M1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 POLISH ROOM, AND INDICATE WHAT TYPE OF FUMES, MISTS, OR
 VAPORS ETC. ARE BEING EXHAUSTED FROM THE ROOM. ARE
 THEIR ANY FUME OR CAPTURE HOODS IN THE ROOM OR IN THE
 LAB?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  
  

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2020-04-10 Cont ID  
Sent By lcrespo Date 2020-04-10 Time 11:36 Rev Time 0.00
Received By lcrespo Date 2020-04-10 Time 11:36 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2020-03-06 Cont ID  
Sent By lcrespo Date 2020-03-06 Time 16:40 Rev Time 0.00
Received By lcrespo Date 2020-03-03 Time 17:35 Sent To  
Notes
2020-03-06 16:41:3703/05/20 2ND MEDICAL GAS REVISION REVIEW **DENIED**
 WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
 REFERENCE: NFPA 99 2012 EDITION
  
 1. EQUIPMENT SPECIFICATIONS DO PROVIDE GENERIC DETAILS
 FOR CONNECTIONS, BUT DO NOT ADDRESS THE DISTRIBUTION
 AND CONFIGURATIONS OF THIS EQUIPMENT LAY OUT THAT IS
 NEEDED TO GUIDE THE CONTRACTOR AND INSTALLERS AS WELL
 AS ALLOWING THE INSPECTOR TO INSPECT FOR NFPA 99
 COMPLIANCE AND TO CONFIRM THAT THE INSTALLATION
 CONFORMS TO THE DESIGNER?S INTENT, PROVIDE DETAILS ON
 THE PLAN THAT CLEARLY INDICATE THE MANIFOLDS AND PIPING
 DISTRIBUTION AND CONFIGURATIONS REQUIRED FOR A COMPLETE
 INSTALLATION. THIS INCLUDES A RISER DIAGRAMS FOR ALL
 THE MEDICAL GAS PIPING TO BE INSTALLED. PROVIDE
 ISOMETRIC DRAWING FOR MED GAS INCLUDING VACUUM EXHAUST
 PER THE WPB AMENDMENTS TO FBC 107.3.5.1.3(13).
  
 2. ALL WATER TUBES MEDICAL GAS SHALL BE IN ACCORDANCE
 WITH NFPA 99 2012 SECTION 5.3.7.2.1. WITH ASTM B 819,
 STANDARD SPECIFICATION FOR SEAMLESS COPPER.
  
 3. THERE ARE 2 P-3 SHEETS WHICH ON HAS A REVISION DATE
 SO PLEASE DELETE THE ONE NOT NEEDED PER THE WPB AMEND
 TO FBC 107.2.1.
  
 4. PLEASE PROVIDE SPECIFICATION FOR VACUUM PUMP AND FOR
 AIR COMPRESSOR SHOWING COMPLIANCE PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 5. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING THE DENTAL
 CHAIRS, TANKS AND VALVES PER THE WPB AMEND TO FBC
 107.2.1.
  
 6. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR
 COMPRESSOR SHALL BE VENTILATED PER NFPA 99 SECS.
 5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1.
  
 7. PIPING SYSTEMS FOR CATEGORY 3 GASES SHALL NOT BE
 USED AS GROUNDING ELECTRODES PER THE NFPA 99 2012 SEC.
 5.3.13.2.2.
  
 8. ALL DOCUMENTATION PERTAINING TO INSPECTIONS AND
 TESTING SHALL BE MAINTAINED ON-SITE PER THE NFPA 99
 2012 SEC. 5.3.9.1.5.
  
 9. PROVIDE A DETAIL FOR RESTRAINTS ON THE OXYGEN TANK
 INCLUDING WALL ANCHORAGE PER THE WPB AMEND TO FBC
 107.2.1.
  
 10. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE
 2017 WPB A TO FBC 107.5.
  
 11. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM
 EXHAUST AND RELIEF PIPING ON THE ROOF PLAN, IT SHALL BE
 DISCHARGED ABOVE ROOF IN A SEPARATE VENT PER THE NFPA
 99 2012 SEC. 5.3.8.3.11. (1).
  
 12. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS
 SYSTEM IS DESIGNED TO BE PER THE NFPA 99 CHAPTER 4,
 CATEGORY 3.
  
 13. PROVIDE COMPLETED INSTALLATION MANUALS FOR ALL NEW
 MED GAS EQUIPMENT IN DETAIL PER THE 2017 WPB A TO
 SECTION FBC 107.3.5.
  
 14. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER
 THE WPB AMEND TO FBC 107.2.1.
  
 15. PLEASE PROVIDE A LEGEND FOR ALL GAS VALVES PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 16. PLEASE PROVIDE DETAIL HOW PIPING IS GOING TO BE
 SUPPORTED IN ACCORDANCE WITH NFPA 2012 5.3.7.3.3 PIPE
 SUPPORT. PIPE SUPPORT SHALL BE IN ACCORDANCE.
  
 17. FILTER MUST COMPLY WITH NSF 42 PLEASE SUBMIT
 MANUFACTURES SPECIFICATION FOR COMPLIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 18. PLEASE PROVIDE HOW WARNING SYSTEM WILL ABIDE PER
 THE 5.3.6.22.1 WARNING SYSTEMS FOR MEDICAL GAS SYSTEMS.
  
 19. PLEASE PROVIDE HOW PIPE IS GOING TO BE LABELED PER
 THE 2012 NFPA 5.3.11.1.4 (1) AT INTERVALS OF NOT MORE
 THAN 6.1 M (20 FT).
  
 20. PROVIDE PIPING DETAIL OF CONTROL VALVES AND TANK
 MANIFOLD ALSO DETAIL OF HOW TANK IS SECURED PER WPB
 AMEND TO FBC 107.2.1 AND NFPA 99.
  
 21. PLEASE SHOW WHERE EMERGENCY VALVE IS LOCATED AND
 LABELED PER THE 2012 NFPA 5.3.6.19.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2020-02-10 Cont ID  
Sent By gjohnson Date 2020-02-10 Time 18:24 Rev Time 0.00
Received By gjohnson Date 2020-02-10 Time 18:24 Sent To  
Notes
2020-02-10 18:24:323RD REVIEW:.19070244
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
  
 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE
 INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED.
 INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON
 JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031
  
 2. PROVIDE NOTE ON PLAN MED GAS SHALL COMPLY WITH NFPA
 99
  
 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHT. P3 KEY NOTE A REFERENCES SHT P6 BUT P6 HAS NOT
 BEEN UPLOADED PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 5. WHAT TYPE OF PIPING IS BEING USED FOR THE COMPRESSED
 AIR LINES. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT P3 UNDER PLUMBING KEYNOTES ( DENTAL) REFERENCES
 DENTAL DRAWINGS THEY HAVE NOT BEEN DOWNLOADED PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2020-04-10 Cont ID  
Sent By lcrespo Date 2020-04-10 Time 11:35 Rev Time 0.00
Received By lcrespo Date 2020-04-10 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status N Date 2020-03-12 Cont ID  
Sent By jesmith Date 2020-03-12 Time 15:26 Rev Time 0.00
Received By jesmith Date 2020-03-12 Time 15:27 Sent To  
Notes
2020-03-12 15:25:55PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 19070244 4100 S DIXIE HWY

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-02-10 Cont ID  
Sent By gjohnson Date 2020-02-10 Time 18:23 Rev Time 0.00
Received By gjohnson Date 2020-02-10 Time 15:17 Sent To  
Notes
2020-02-10 18:23:573RD REVIEW:.19070244
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
  
 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE
 INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED.
 INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON
 JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031
  
 2. PROVIDE NOTE ON PLAN MED GAS SHALL COMPLY WITH NFPA
 99
  
 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHT. P3 KEY NOTE A REFERENCES SHT P6 BUT P6 HAS NOT
 BEEN UPLOADED PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 5. WHAT TYPE OF PIPING IS BEING USED FOR THE COMPRESSED
 AIR LINES. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT P3 UNDER PLUMBING KEYNOTES ( DENTAL) REFERENCES
 DENTAL DRAWINGS THEY HAVE NOT BEEN DOWNLOADED PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-01-09 Cont ID  
Sent By gjohnson Date 2020-01-09 Time 19:28 Rev Time 0.00
Received By gjohnson Date 2020-01-09 Time 19:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-21 Cont ID  
Sent By gjohnson Date 2019-09-21 Time 14:02 Rev Time 0.00
Received By gjohnson Date 2019-09-21 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-07-24 Cont ID  
Sent By thunt Date 2019-07-24 Time 17:05 Rev Time 0.00
Received By gjohnson Date 2019-07-24 Time 17:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status N Date 2020-04-10 Cont ID  
Sent By lcrespo Date 2020-04-10 Time 11:36 Rev Time 0.00
Received By lcrespo Date 2020-04-10 Time 11:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-03-03 Cont ID  
Sent By shill Date 2020-03-03 Time 11:35 Rev Time 0.00
Received By shill Date 2020-03-03 Time 11:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-01-31 Cont ID  
Sent By dbattles Date 2020-01-31 Time 14:19 Rev Time 0.00
Received By dbattles Date 2020-01-31 Time 14:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-12-27 Cont ID  
Sent By dbattles Date 2019-12-27 Time 11:01 Rev Time 0.00
Received By dbattles Date 2019-12-27 Time 11:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By dbattles Date 2019-09-18 Time 12:50 Rev Time 0.00
Received By dbattles Date 2019-09-18 Time 12:50 Sent To  
Notes
2019-09-18 12:51:36ALL SHEETS OK FOR SECOND REVIEW.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-01 Cont ID  
Sent By dbattles Date 2019-08-01 Time 10:30 Rev Time 0.00
Received By dbattles Date 2019-08-01 Time 10:30 Sent To  
Notes
2019-08-01 10:32:29DRAWING SHEETS ARE NOT DIGITALLY SIGNED.
 PLEASE PROVIDE SHEETS THAT ARE DIGITALLY SIGNED, OR
 DROP OF HARD COPY UPON APPROVAL FOR SIGNATURE
 VERIFICATION.
  
 DYLAN BATTLES
 [email protected]
 561-805-6718