Plan Review Details - Permit 19070209
Plan Review Stops For Permit 19070209
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-01 Cont ID  
Sent By pvalenti Date 2019-08-01 Time 14:42 Rev Time 0.00
Received By pvalenti Date 2019-07-23 Time 14:14 Sent To  
Notes
2019-07-24 14:14:34RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-03 Time 15:21 Sent To  
Notes
2019-07-03 15:21:23REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-01 Cont ID  
Sent By ccole Date 2019-08-01 Time 14:41 Rev Time 0.00
Received By pvalenti Date 2019-08-01 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-09 Cont ID  
Sent By ccole Date 2019-07-09 Time 17:34 Rev Time 0.00
Received By ccole Date 2019-07-09 Time 17:27 Sent To I
Notes
2019-07-09 17:39:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070209
 7/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DUCT WORK WAS NOT INCLUDED IN THE ORIGINAL PLANS
 APPROVED UNDER PERMIT #19040945. PLEASE INDICATE THE
 INCREASE IN VALUE FOR THE PROPOSED WORK ON THE REVISION
 APPLICATION, AND LABEL THE AIR HANDLER AS EITHER NEW
 (REPLACED) OR EXISTING.
  
 2) THE APPROVED PLANS UNDER PERMIT #19040945 SHOWS THE
 MASTER SUITE TO BE THE BEDROOM THAT HAS THE WALK-IN
 CLOSET. PLEASE NOTE THAT ALL AIR FROM A MASTER SUITE
 SHALL BE RETURNED. PLEASE INCREASE THE SIZE OF THE
 RETURN GRILL R1 IN COMPLIANCE WITH SECTION 601.6 ITEM
 3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719