Plan Review Details - Permit 19070191
Plan Review Stops For Permit 19070191
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By jleahy Date 2019-07-19 Time 07:30 Rev Time 0.00
Received By jleahy Date 2019-07-19 Time 07:30 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By fgiaquin Date 2019-07-08 Time 06:20 Rev Time 0.00
Received By fgiaquin Date 2019-07-08 Time 06:03 Sent To I
Notes
2019-07-08 06:18:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SATISFY ALL REQUIREMENTS FROM ZONING DEPT.
  
 2. PROVIDE SPEC SHEETS SHOWING UL OR OTHER NRTL LISTING
 FOR ALL LIGHTING AND LEGRAND CHARGING STATIONS. FBC
 107.2.1 NEC 90.7, 110.2, 110.3B
  
 3. PROVIDE STRUCTURAL DETAIL FOR POLE/BASE FOR POLE
 MOUNTED LIGHT, INCLUDE WIND LOADS. FBC 107.2.1 FBC 1609
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-24 Cont ID  
Sent By cpuell Date 2019-07-24 Time 09:00 Rev Time 0.00
Received By cpuell Date 2019-07-18 Time 15:58 Sent To  
Notes
2019-07-18 15:58:15RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-08 Cont ID  
Sent By fgiaquin Date 2019-07-08 Time 06:21 Rev Time 0.00
Received By fgiaquin Date 2019-07-03 Time 14:58 Sent To  
Notes
2019-07-03 14:58:12ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By eschneid Date 2019-07-23 Time 12:30 Rev Time 0.25
Received By eschneid Date 2019-07-23 Time 11:08 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By eschneid Date 2019-07-05 Time 13:13 Rev Time 0.25
Received By eschneid Date 2019-07-05 Time 13:13 Sent To E
Notes
2019-07-05 13:20:06FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) CITYPLACE RETAIL MANAGEMENT STAMP NOT INCLUDED ON
 THE PLANS.
  
 2) LIGHT LX-01 IS LISTED AS POLE MOUNTED. THE
 SPECIFICATION SHEET FOR THE LIGHT FIXTURE AND THE POLE
 MUST BE PROVIDED.
  
 3) LIGHT LX-06 IS LISTED AS SUSPENDED FROM TREE
 BRANCHES. THE CITY DOES NOT PERMIT PERMANENT LIGHTS TO
 BE SUSPENDED OR ATTACHED TO TREES.
  
 4) PROVIDE PHOTOMETRIC PLANS SHOWING COMPLIANCE WITH
 CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]