Plan Review Details - Permit 19070169
Plan Review Stops For Permit 19070169
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-30 Cont ID  
Sent By dbattles Date 2019-07-30 Time 09:31 Rev Time 0.00
Received By dbattles Date 2019-07-30 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By dbattles Date 2019-07-16 Time 15:35 Rev Time 0.00
Received By dbattles Date 2019-07-16 Time 15:35 Sent To  
Notes
2019-07-16 15:38:05BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070169
 REVIEWED: JULY 16, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 1004.1 FBC[B]DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
  -PLEASE PROVIDE AREA, OCCUPANCY AND OCCUPANT LOAD FOR
 THE EXISTING SPACE LABELED MID FLORIDA ARMORED SPACE.
 STORAGE AREA CAN USE STORAGE OCCUPANY FOR OCCUPANT
 LOAD.
  -IF THE OCCUPACY EXCEEDS 49 THAN 2 EXITS ARE REQUIRED
 (SEE COMMENT 2)
  
 2) 1006.1 FBC[B]GENERAL. THE NUMBER OF EXITS OR EXIT
 ACCESS DOORWAYS REQUIRED WITHIN THE MEANS OF EGRESS
 SYSTEM SHALL COMPLY WITH THE PROVISIONS OF SECTION
 1006.2
  -THE LIFE SAFETY PLANS SHOWS ADDITIONAL EXIT THROUGH
 THE OTHER TENANT SPACE. IT APPEARS THAT BATHROOMS ARE
 SHARED, BUT THE OTHER SPACE THAT IS HATCHED IS OPEN AND
 WOULDN?T APPEAR TO BE A MEANS OF EGRESS.
  -IS THE BUILDING SPRINKLED?
 PLEASE ADD TO DATA TABLE SO THE MAXIMUM COMMON PATH OF
 TRAVEL CAN BE ESTABLISHED.
 ACCORDING TO A-2 BUILDING ANALYSIS COMMON PATH OF
 TRAVEL IS 75 FEET AND MAX DEAD END CORRIDOR IS 20 FEET.
 THE DRAWING SHOWS 100 FEET FROM OFFICE 6 AND DEAD
 COORIDOR IS OVER 20 FEET.
  
 NOTES:
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-31 Cont ID  
Sent By jpearson Date 2019-07-31 Time 08:59 Rev Time 0.00
Received By jpearson Date 2019-07-31 Time 08:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 13:16 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 13:16 Sent To  
Notes
2019-07-14 13:16:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By pleduc Date 2019-08-02 Time   Rev Time 0.00
Received By pleduc Date 2019-08-02 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-10 Cont ID  
Sent By pleduc Date 2019-07-10 Time   Rev Time 0.00
Received By pleduc Date 2019-07-10 Time 14:42 Sent To  
Notes
2019-07-10 14:44:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) LIFE SAFETY SHEET - THERE IS AN INCORRECT REFERENCE
 TO THE CURRENT FLORIDA FIRE PREVENTION CODE.
  
 PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 6TH
 EDITION OF FLORIDA FIRE PREVENTION CODE WHICH INCLUDES
 THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-07 Cont ID  
Sent By rmcdouga Date 2019-08-07 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2019-07-23 Time 13:57 Sent To  
Notes
2019-08-07 07:45:18TO RM DESK
  
2019-07-24 13:57:48B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-16 Cont ID  
Sent By dbattles Date 2019-07-16 Time 15:36 Rev Time 0.00
Received By dbattles Date 2019-07-02 Time 13:36 Sent To  
Notes
2019-07-03 13:36:13B10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-16 Cont ID  
Sent By ccole Date 2019-07-16 Time 12:46 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 12:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-08-07 Cont ID  
Sent By rmcdouga Date 2019-08-07 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2019-08-07 Time 08:16 Sent To I
Notes
2019-08-07 08:17:36NO PLUMBING WORK IS SPECIFIED ON THE PLANS. THE
 EXISTING BATHROOMS ARE ADA COMPLIANT. VERIFY IN THE
 FIELD.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-14 Cont ID  
Sent By abelisle Date 2019-07-14 Time 05:19 Rev Time  
Received By abelisle Date 2019-07-14 Time   Sent To  
Notes
2019-07-14 06:38:227/14/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) THERE IS NO VALUE LISTED ON THE PLUMBING
 SUB-APPLICATION AND THE OVERALL VALUE IS LOW. WPB
 AMENDMENTS TO THE FBC 109.3 BUILDING PERMITS
 VALUATIONS. IF IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS ON THE CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 3) THE SCOPE OF THE PLUMBING TO BE DONE IS UNCLEAR
 PLEASE PROVIDE PLUMBING PLAN INCLUDING A SANITARY AND
 WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 4) PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 5) PLEASE PROVIDE ELEVATION DETAILS FOR ALL PLUMBING
 LOCATIONS.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  