2019-07-14 06:38:22 | 7/14/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1) THERE IS NO VALUE LISTED ON THE PLUMBING |
| SUB-APPLICATION AND THE OVERALL VALUE IS LOW. WPB |
| AMENDMENTS TO THE FBC 109.3 BUILDING PERMITS |
| VALUATIONS. IF IN THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE |
| WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING |
| OF THE DOWELS ON THE CENTER. THE REPAIR SHALL ALSO |
| INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE |
| CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION. |
| |
| 3) THE SCOPE OF THE PLUMBING TO BE DONE IS UNCLEAR |
| PLEASE PROVIDE PLUMBING PLAN INCLUDING A SANITARY AND |
| WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 4) PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER |
| FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE. |
| |
| 5) PLEASE PROVIDE ELEVATION DETAILS FOR ALL PLUMBING |
| LOCATIONS. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |