Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-12 Cont ID  
Sent By dbattles Date 2019-09-12 Time 13:15 Rev Time 0.00
Received By dbattles Date 2019-09-12 Time 13:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By dbattles Date 2019-07-18 Time 07:58 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 07:57 Sent To  
Notes
2019-07-18 08:00:36BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070089
 REVIEWED: JULY 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 481.229?EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
 THIS CHANGE OF OCCUPANCY WILL REQUIRE A CERTIFICATE OF
 OCCUPANCY AND THE PLANS NEED TO BE PREPARED BY A
 LICENSED DESIGN PROFESSIONAL.
 FLORIDA STATUTE 481.229 HAS SOME EXEMPTIONS FROM
 LICENSURE, BUT NOT FOR PUBLIC BUILDING CONTAINING
 EDUCATIONAL OCCUPANCY.
  
 THE PLAN DOES CONTAIN THE NAME OF AN ENGINEER, BUT THEY
 ARE NOT SIGNED AND SEALED. THE DRAWING PROVIDED WOULD
 APPEAR TO BE LIFE SAFETY AND THIS TYPE OF WORK SHOULD
 BE PERFORMED BY A LICENSED ARCHITECT. PLEASE REVIEW
 481.229 WHERE IT STATES THAT ENGINEERS CAN PROVIDE
 ARCHITECTURAL DRAWINGS INCIDENTAL TO THEIR ENGINEERING
 SERVICES.
  
 PLEASE PROVIDE PROJECT DATA THAT CAN BE REVIEWED FOR
 COMPLIANCE WITH THE FLORIDA BUILDING CODE 2017 6TH
 EDITION.
 SOME DATA I?M LOOKING FOR:
 THE USE OF SPACE (DAY CARE? SCHOOL? LEARNING CENTER?
 AGE RANGE?), OCCUPANT LOAD, AREA OF SPACE, ANY WORK
 BEING PERFORMED, EXIT COMMON PATH OF TRAVEL, TYPE OF
 CONSTRUCTION (MAIN STRUCTURE), COMPLIANCE WITH FLORIDA
 BUILDING CODE 2017 6TH EDITION 468 AND 453.
  
 NOTES:
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-11 Cont ID  
Sent By jpearson Date 2019-09-11 Time 12:05 Rev Time 0.00
Received By jpearson Date 2019-09-11 Time 12:05 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-25 Cont ID  
Sent By jpearson Date 2019-07-25 Time 09:35 Rev Time 0.00
Received By jpearson Date 2019-07-25 Time 09:31 Sent To  
Notes
2019-07-25 09:35:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By pleduc Date 2019-09-16 Time   Rev Time 0.00
Received By pleduc Date 2019-09-16 Time 11:13 Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By pleduc Date 2019-07-08 Time   Rev Time 0.00
Received By pleduc Date 2019-07-08 Time 14:44 Sent To  
Notes
2019-07-08 15:27:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO
 DETERMINE COMPLAINCE WITH THE FLORIDA FIRE PREVETNION
 CODE.
  
 PLEASE PROVIDE A DETAILED REVIEW OF WHAT THIS
 EDUCATIONAL OCCUPONACY IS, DIMENSION OF ALL
 ROOMS/SPACES, TOTAL SQUARE FOOTAGE.HOURS OF OPERATION,
 NUMBER OF STUDENTS, AGE OF STUDENTS, ETC.
  
  
  
  
 2) THERE IS NO INDICATION OF COMPLINACE WITH ANY FIRE
 CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101,
 INCLUDING CHAPTE 14, NEW EDUCATIONAL OCCUPANCIES
  
 PLEASE REVIEW AND ENSURE COMPLIANCE
  
  
  
 3) THERE IS NO INDICATION OF A LIFE SAFETY PLAN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN
  
  
  
  
 4) THERE APPEARS TO ONE FIRE ALARM DEVICE.
  
 PER NFPA 101, CH. 14, NEW EDUCATIONAL OCCUPANCIES.
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6.
  
 PLEASE PROVIDE FOR THE APPLICABLE FIRE ALARM SYSTEM AND
 A NOTE OF INTENT TO PROVIDE THE FIRE ALARM SYSTEM PER
 THE APPLICABLE CODE.
  
 ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 5) THERE IS NO INDICATIONS OF A FIRE SPRINKLER SYSTEM.
  
 PER NFPA 101, CH. 14, NEW EDUCATIONAL OCCUPANCIES.
  
 14.3.5 EXTINGUISHMENT REQUIREMENTS.
 14.3.5.1* EDUCATIONAL OCCUPANCY BUILDINGS EXCEEDING
 12,000 FT2
 (1120 M2) SHALL BE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION
 9.7.
  
 PLEASE PROVIDE APPLICABLE INFORMATION TO DETERMINE IF A
 FIRE SPRINKLER SYSTEM IS REQUIRED.
  
  
  
 6) THERE ARE NO INDICATIONS OF DOOR HARDWARE.
  
 PLEASE REVIEW NFPA 101 CH 14 AND PROVIDE APPLICABLE
 DOOR INFORMATION, HARDWARE AND LOCKING DEVICES PER THE
 CODE.
  
 14.2.2.2 DOORS.
 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7.
  
  
  
  
 7) THERE IS AN INDICATION OF A "SPACE OWNED BY OTHERS"
 THAT HAS A DOOR TO THIS PROPOSED OCCUPANCY.
  
 WHAT IS THE PURPOSE/OCCUPANCY TYPE OF THAT SPACE?
  
 THE OCCUPANCY IS REQUIRED TO BE SEPARATED BY A FIRE
 RATING PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF
 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED
 OCCUPANCY.
  
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE PROVIDE DETAILS AND THE REQUIRED SEPARATION.
  
  
  
  
 8) THERE IS NO INDICATION OF THE ROOM/SPACES FLOOR,
 WALL AND CEILING FINISHES
  
 14.3.3 INTERIOR FINISH.
 14.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 14.3.3.2* INTERIOR WALL AND CEILING FINISH. INTERIOR
 WALL AND
 CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE
 PERMITTED AS FOLLOWS:
 (1) EXITS ? CLASS A
 (2) OTHER THAN EXITS ? CLASS A OR CLASS B
 (3) LOW-HEIGHT PARTITIONS NOT EXCEEDING 60 IN. (1525
 MM) AND
 USED IN LOCATIONS OTHER THAN EXITS ? CLASS A, CLASS B,
 OR
 CLASS C
 14.3.3.3 INTERIOR FLOOR FINISH.
 14.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 14.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS
 CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS
 COMPLYING
 WITH 14.3.6 SHALL BE NOT LESS THAN CLASS II.
 14.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE.
  
 PLEASE PROIVDE DETAILS INDICATING COMPLIANCE
  
  
  
  
 9) THERE ARE EXIT SIGNS INDICATED BY THEY DO NOT
 INDICATE TYPE.
  
 PER NFPA 101, CH 14
  
 14.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
 14.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9.
 14.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PLEASE PROVIDE DETAILS INDICATING COMPLIANCE WITH THE
 ABOVE.
  
  
 11) THERE IS STORAGE INDICATED IN A CENTER/MAIN AREA.
  
 EXITS CAN NOT PASS THROUGH A HIGHER HAZARD AREA.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 12) THERE DOES NOT APPEAR TO BE CODE COMPLIANT EXITS.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 14.2.4 NUMBER OF MEANS OF EGRESS.
 14.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4.
 14.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN
 ACCORDANCE
 WITH THE FOLLOWING CRITERIA:
 (1) THEY SHALL BE PROVIDED ON EVERY STORY.
 (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY
 STORY AND
 MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL BE
 PERMITTED TO
 BE COMMON FOR THE DISTANCE PERMITTED AS COMMON PATH OF
 TRAVEL BY 14.2.5.3.
 14.2.5 ARRANGEMENT OF MEANS OF EGRESS. SEE ALSO SECTION
 7.5.
 14.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
 14.2.5.4 EVERY ROOM OR SPACE LARGER THAN 1000 FT2 (93
 M2) OR WITH
 AN OCCUPANT LOAD OF MORE THAN 50 PERSONS SHALL COMPLY
 WITH THE
 FOLLOWING:
 (1) THE ROOM OR SPACE SHALL HAVE A MINIMUM OF TWO EXIT
 ACCESS
 DOORS.
 (2) THE DOORS REQUIRED BY 14.2.5.4(1) SHALL PROVIDE
 ACCESS TO
 SEPARATE EXITS.
 (3) THE DOORS REQUIRED BY 14.2.5.4(1) SHALL BE
 PERMITTED TO OPEN
 ONTO A COMMON CORRIDOR, PROVIDED THAT SUCH CORRIDOR
 LEADS TO
 SEPARATE EXITS LOCATED IN OPPOSITE DIRECTIONS.
  
  
  
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By rfalcone Date 2019-09-17 Time 11:38 Rev Time 0.00
Received By shill Date 2019-09-11 Time 11:48 Sent To  
Notes
2019-09-16 07:03:459/16 TO FIRE
  
2019-09-12 07:33:569/12 TO DB DESK
2019-09-11 15:08:29TO CM DESK
2019-09-11 11:49:03TO JP DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-07 Cont ID  
Sent By cmontell Date 2019-08-07 Time 13:14 Rev Time 0.00
Received By cmontell Date 2019-08-07 Time 13:14 Sent To  
Notes
2019-08-05 08:01:50TO CM DESK
  
2019-07-03 11:17:27C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By dbattles Date 2019-10-02 Time 16:11 Rev Time 0.00
Received By dbattles Date 2019-10-02 Time 16:10 Sent To  
Notes
2019-10-02 16:12:07OK-PLANS STAMPED
 NO FEE DUE AND MU NUMBER FROM COUNTY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By dbattles Date 2019-07-18 Time 07:58 Rev Time 0.00
Received By dbattles Date 2019-07-17 Time 14:17 Sent To  
Notes
2019-07-18 07:59:09109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-12 Cont ID  
Sent By cmontell Date 2019-09-12 Time 06:02 Rev Time 0.00
Received By cmontell Date 2019-09-12 Time 06:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-07 Cont ID  
Sent By cmontell Date 2019-08-07 Time 13:14 Rev Time 0.00
Received By cmontell Date 2019-08-07 Time 13:12 Sent To I
Notes
2019-08-07 13:14:27MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN PER WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, 6TH EDITION (2017),
 CHAPTER 1, ADMINISTRATION, SEC 107.2 CONSTRUCTION
 DOCUMENTS.
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-09-13 Cont ID  
Sent By gjohnson Date 2019-09-13 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2019-09-13 Time 09:43 Sent To  
Notes
2019-09-13 09:48:591)NO PLUMBING WORK IS APPROVED UNDER THIS PERMIT ANY
 PLUMBING WORK WILL REQUIRE A SEPARATE PLANS AND PERMIT.
  
 2) ANY WORK SHALL COMPLY WITH FBC ACC 202.4.1 AND
 202.4.2
  
 3) TH BATHROOMS DO NOT COMPLY WITH CURRENT
 ACCESSIBILITY CODE FLORIDA BUILDING CODE ACCESSIBILITY
 2017 6TH EDITION
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By gjohnson Date 2019-07-19 Time 09:31 Rev Time 0.00
Received By gjohnson Date 2019-07-19 Time 08:32 Sent To  
Notes
2019-07-19 09:31:201ST REVIEW: 19070089
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SEE BUILDINGS COMMENTS
  
 2. PROVIDE EXISTING OR DEMO PLAN. PER WPB AMEND TO FBC
 107.2
  
 3. SHOW LEVEL OF ACCESSIBILITY IN BATHROOMS AND WATER
 FOUNTAIN INCLUDE DIMENSIONS . PER FBC ACC CH 6- 602,
 603, 604, 606, 609
  
 4. SHOW ALL PLUMBING FIXTURES INCLUDE DIMENSIONS IN THE
 BATHROOMS.PER WPB AMEND TO FBC 107.2
  
 5. ALL FIXTURE IN KITCHEN AREA SHALL DISCHARGE THROUGH
 GREASE INTERCEPTOR. PER FBC PL 1003.3.1
  
 6. INDICATE UNIT NUMBER IN THE ADDRESS ON THE PLAN AND
 PERMIT APPLICATION. PER WPB AMEND TO FBC 107.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By rfalcone Date 2019-09-17 Time 09:26 Rev Time 0.00
Received By rfalcone Date 2019-09-17 Time 11:38 Sent To I
Notes
2019-09-17 09:29:249/17/2019 PASSED.
  
 ADDITIONAL INFORMATION IS REQUIRED FOR DAY CARE
 FACILITIES LOCATED IN NEIGHBORHOOD COMMERICAL ZONING
 DISTRICTS.
  
 PURSUANT ZLDR SEC. 94-272(18), DAY CARE FACILITIES,
 CHILDREN, AS PRINCIPAL USE (PXR: SEE ITEM 32, TABLE
 IX-1):
 A. ADDITIONAL APPLICATION REQUIREMENTS. A STATEMENT
 THAT THE PROPOSED DAY CARE CENTER WILL COMPLY WITH ALL
 APPLICABLE COUNTY AND STATE REGULATIONS.
 B. ADDITIONAL STANDARDS. APPLICATIONS TO ESTABLISH
 CHILD DAY CARE CENTER SHALL COMPLY WITH THE
 REQUIREMENTS OF LAWS OF FLA. CH. 59 (1968), AS AMENDED.
  
 UPON BUSINESSTAX APPLICATION SUBMITTAL, PLEASE PROVIDE
 THE REQUIRED DOCUMENTATION LISTED ABOVE FOR ZONING
 APPROVAL.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By llouie Date 2019-07-24 Time   Rev Time  
Received By llouie Date 2019-07-24 Time   Sent To  
Notes
2019-07-24 14:07:59** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) WHAT IS THE EXISTING AND PROPOSED USE FOR THE
 SPACE? IT IS NOT CLEAR WHAT THE PROPOSED USE FOR THE
 SPACE IS. PLEASE PROVIDE ADDITIONAL INFORMATION.
  
 2.) PLANS SHOWING THE EXISTING SPACE/INTERIOR DEMO
 SHALL BE PROVIDED TO DETERMINE THE EXTENT OF THE
 MODIFICATION TO THE SPACE.
  
 3.) PLANS SHALL BE SIGNED, DATED AND SEALED BY A
 FLORIDA LICENSED ENGINEER OR ARCHITECT.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: NC
  