2019-08-13 17:17:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19070067 |
| 8/13/2019 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| 1) SHEET M2.17: PROVIDE SYSTEM SIZING CALCULATIONS FOR |
| THE AHU-CH- SECTION 312.1 FBC M. |
| 2) M2.17: NORMAL AND EMERGENCY VENTILATION SHALL BE |
| PROVIDED FOR THE CHILLER ROOM- SEE SECTIONS 1105.6 & |
| 1105.6.3 FBC M. PLEASE INDICATE HOW THE VENTILATION |
| SYSTEM DESIGN AS SHOWN ON THE PLAN WILL MEET COMPLIANCE |
| FOR BOTH NORMAL AND EMERGENCY VENTILATION. PROVIDE |
| CALCULATIONS AND THE SEQUENCES OF OPERATION ON THE |
| PLAN. |
| 3) M2.17: SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE REFRIGERANT DETECTOR |
| WITH APPROVAL STAMP BY THE ENGINEER OF RECORD. PLEASE |
| NOTE THIS MAY BE A DEFERRED SUBMITTAL AS NOTED BELOW. |
| 4) M22.17: DEFERRED SUBMITTALS: THE MIAMI-DADE NOA?S |
| FOR THE AC STAND, LOUVERS, AND THE SPECS FOR THE |
| REFRIGERANT DETECTOR MAY BE SUBMITTED WITH THE PLANS |
| BEARING APPROVAL STAMPS BY THE EOR, OR MAY BE DEFERRED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |