Plan Review Details - Permit 19061348
Plan Review Stops For Permit 19061348
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-09-05 Cont ID  
Sent By gjohnson Date 2019-09-05 Time 10:17 Rev Time 0.00
Received By gjohnson Date 2019-09-05 Time 10:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-01 Cont ID  
Sent By gjohnson Date 2019-07-01 Time 11:16 Rev Time 0.00
Received By gjohnson Date 2019-07-01 Time 11:16 Sent To  
Notes
2019-07-01 11:16:581ST REVIEW: 19061348
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. THE REVISIONS TO THE MASTER OR UNDER THE APPROVED
 MASTER PERMIT SHALL BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL OF RECORD DAVID LAWRENCE. PER WPB AMEND TO
 FBC 107.2.1 /61G15-23.001, F.A.C
  
 2. THE FLOOR PLAN DOES NOT MATCH APPROVED PLAN AFTER
 CHECKING INSPECTION NOTES IT APPEARS THAT A FULL
 REVISION IS GOING TO BE REQUIRED, THE GAS REVISION
 FLOOR PLAN SHALL MATCH APPROVED PLAN . PER WPB AMEND TO
 FBC 107.2.1
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS SEC.
 402.2
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2017 FUEL GAS CODE SEC. 304.
  
 5. THE FIRST TABLE LISTED 402.4(5) IS LABELED
 CORRUGATED STAINLESS STEEL TUBING (CSST)THIS DOESN'T
 MATCH THE CODE IT SHALL BE SCH 40 METALLIC PLEASE LIST
 CORRECT TABLE FOR PIPE BEING INSTALLED.PER WPB AMEND TO
 FBC 107.2.1
  
 6. ON REGULATOR A YOU LIST 937,000 BTU WHEN I ADDED THE
 BTU LOADS ON THE RISER IT ADDS UP TO 947,000 BTU PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. THE SECTION OF PIPE BETWEEN THE GENERATOR IS
 UNDERSIZED IT SHOULD BE 11/2 PER TABLE 402.4(2) AT 50FT
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-05 Cont ID  
Sent By gjohnson Date 2019-09-05 Time 10:17 Rev Time 0.00
Received By gjohnson Date 2019-07-19 Time 13:18 Sent To  
Notes
2019-08-22 05:29:05ROUTED TO GJOHNSON
2019-08-01 14:40:21TO TL DESK
  
2019-07-22 13:18:14REVISION ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-01 Cont ID  
Sent By gjohnson Date 2019-07-01 Time 11:17 Rev Time 0.00
Received By gjohnson Date 2019-06-27 Time 14:08 Sent To  
Notes
2019-06-28 14:08:47REVISION ROUTED TO GJOHNSON


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved