Plan Review Details - Permit 19061323
Plan Review Stops For Permit 19061323
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-21 Cont ID  
Sent By tklarge Date 2020-07-21 Time 09:17 Rev Time 0.00
Received By tklarge Date 2020-07-21 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-01 Cont ID  
Sent By abelisle Date 2020-03-05 Time 07:17 Rev Time 0.00
Received By thunt Date 2019-06-27 Time 10:27 Sent To  
Notes
2019-06-28 10:27:47PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-21 Cont ID  
Sent By tklarge Date 2020-07-21 Time 09:17 Rev Time 0.00
Received By tklarge Date 2020-07-21 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-05 Cont ID  
Sent By abelisle Date 2020-03-31 Time 07:16 Rev Time 0.00
Received By abelisle Date 2020-03-31 Time 13:18 Sent To I
Notes
2020-03-05 07:17:113/31/2020 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 A BATHROOM, KITCHEN AND WASHING MACHINE AT THIS ADDRESS
 IN THE BACK APARTMENT AREA.SINCE THERE IS NO RECORD OF
 A PERMIT FOR THE PLUMBING, THE EXISTING PLUMBINGIN
 THESE LOCATIONS SHALL BE CONSIDERED AS NEW. WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-01 Cont ID  
Sent By thunt Date 2019-07-01 Time 08:21 Rev Time 0.00
Received By thunt Date 2019-07-01 Time 08:20 Sent To  
Notes
2019-07-01 08:23:55PLUMBING 1ST REVIEW**DENIED**'
  
  
 1) PROVIDE SCOPE OF WORK. APPLICATION DESCRIPTION (
 EXISTING PLUMBING) AND PLAN DOES NOT SHOW THE INTENTED
 WORK TO BE PERFORMED. FBC 107.3.5
  
 2) VALUE $200.00 SEEMS TO BE LOW UNLESS THE SCOPE OF
 WORK IT ONLY RECONNECTING ALL EXISTING FIXTURE NOT
 REPLACING THEM. WPB AMEND 109.3
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  