Plan Review Details - Permit 19061314
Plan Review Stops For Permit 19061314
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-07-02 Cont ID  
Sent By skennedy Date 2019-07-02 Time 09:48 Rev Time 0.00
Received By skennedy Date 2019-07-02 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-02 Cont ID  
Sent By pleduc Date 2019-07-02 Time   Rev Time 0.00
Received By pleduc Date 2019-07-02 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-27 Cont ID  
Sent By pleduc Date 2019-06-27 Time   Rev Time 0.00
Received By pleduc Date 2019-06-27 Time 10:34 Sent To  
Notes
2019-06-27 10:59:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAILS PROVIDED TO DETERMINE
 COMPIANCE WITH THE LIFE SAFETY CODE.
  
  
  
 2) THIS IS A PARKING GARAGE CLASSIFIED AS A STORAGE
 OCCUPANCY. THE PROPOSED EVENT IS AN ASSEMBLY EVENT.
  
 2A) WHAT IS THE PROPOSED ATTENDANCE?
  
 2B) HOW WILL THE ATTENDANCE BE MONITORED/MAINTAINED?
 (TO PREVENT OVERCROWDING OF THE ROOF TOP)
  
 2C) PROVIDE THE DIMENSIONS OF THE OPEN SPACES AS THIS
 AREA IS THE ASSEMBLY AREA AND THE OCCUPANCY LOAD CAN
 NOT BE EXCEED.
  
  
  
 3) ARE TENTS BEING USED, PLEASE PROVIDE THOSE
 LOCATIONS.
  
  
  
 4) BBQ IS INDICATED. WHAT IS THE AREA OF BBQ, HOW MANY,
 WHAT TYPE?
  
 SHALL BE A MINIMUM OF 10' AWAY FROM ALL COMBUSTILES AND
 VENT TO THE OPEN AIR (UNDER NO CEILING AREA OR LOWER
 LEVELS)
  
 4A) A MIINIMUM 2A,10BC FIRE EXTINGUISHER SHALL BE
 LOCATED WITH EACH SEPARATE BBQ.
  
  
  
 5) A STAGE IS INDICATED, IS IS ROLL OUT TYPE OR IS IT
 BUILT ON SITE?
  
 5A) WHAT IS STAGE CONSTRUCTION TYPE?
  
  
 6) HOW WILL POWER BE SUPPLIED TO THIS EVENT,
 GENERATOR/EXTENSION CORDS?
  
 6A) PROVIDE GENERATOR LOCATIONS, IF APPLICABLE.
  
 6B) EXTENSION CORDS SHALL BE PROTECTED FROM TRIP HAZARD
 AND ACCIDENTAL DAMAGE.
  
 PROVIDE DETAILS.
  
  
  
 7) THERE SHALL BE NO PYROTECHINCS OR FIREWORKS FROM
 THIS STAGE OR ROOF TOP EVENT.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-02 Cont ID  
Sent By sholder Date 2019-07-02 Time 15:31 Rev Time 0.00
Received By sholder Date 2019-06-26 Time 16:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-02 Cont ID  
Sent By ajones Date 2019-07-02 Time 11:50 Rev Time 0.00
Received By ajones Date 2019-07-02 Time 11:50 Sent To  
Notes
***NONE***