Plan Review Details - Permit 19061265
Plan Review Stops For Permit 19061265
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-31 Cont ID  
Sent By rmcdouga Date 2019-07-31 Time 09:53 Rev Time 0.00
Received By rmcdouga Date 2019-07-31 Time 09:53 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-19 Cont ID  
Sent By rmcdouga Date 2019-07-19 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2019-07-19 Time 18:42 Sent To I
Notes
2019-07-19 19:00:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) PARTIALLY COMPLIED. THE INFORMATION PROVIDED IS
 INCOMPLETE. THE INSTALLATION SCHEDULE SPECIFIES THAT
 THE SUBSTRATE IS WOOD FOR BOTH THE FIRST AND SECOND
 FLOORS. THE PROPERTY APPRAISER'S WEBSITE INDICATES THAT
 THE FIRST FLOOR IS CBS AND THE SECOND FLOOR IS WOOD
 FRAME STUCCO. THE ACCORDION SHUTTERS ARE ALWAYS
 INSTALLED VERTICALLY NOT HORIZONTALLY AS SPECIFIED ON
 THE SCHEDULE. THE TYPE OF ANCHOR IS LISTED AS ALL POINT
 SOLID SET IN ONE PLACE AND TAPCON 2 1/4" IS LISED IN
 THE SCHEDULE. THE SHUTTER MOUNTING IS SPECIFIED AS #14
 AND I WAS UNABLE TO DETERMINE WHICH MOUNTING YOU WILL
 USE. PLEASE CIRCLE THE MOUNTINGS AND ANCHOR SPACINGS
 YOU WILL USE IN THE PRODUCT APPROVAL DETAILS AND ANCHOR
 SCHEDULES. FBC 107.2.1 FBC - R 301.2.1.2 SUBMIT TWO
 COPIES OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE
 STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND
 PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE
 DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE
 FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER
 FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK
 TO THE CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS
 MANY OF THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By rmcdouga Date 2019-07-08 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2019-07-08 Time 08:40 Sent To I
Notes
2019-07-08 08:45:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY C. THE
 COMPONENT AND CLADDING PRESSURES AND THE EXPOSURE
 CATEGORY LISTED ON THE FORM THAT WAS SUBMITTED IS
 EXPOSURE CATEGORY B. IN ORDER TO USE EXPOSURE B, YOU
 WILL NEED TO PROVIDE A SITE SPECIFIC ANALYSIS SHOWING
 THAT THIS PROPERTY IS ACTUALLY EXPOSURE CATEGORY B. THE
 ANALYSIS IS REQUIRED TO BE PRODUCED BY AND SIGNED AND
 SEALED BY A FLORIDA LICENSED PROFESSIONAL ENGINEER. FBC
 107.2.1 & FS 471
  
 2) THE MEAN ROOF HEIGHT FOR THIS BUILDING IS 25 FEET
 PER THE INFORMATION THAT YOU PROVIDED. YOU NEED TO USE
 THE MEAN ROOF HEIGHT OF THE BUILDING FOR DETERMINING
 THE COMPONENT AND CLADDING PRESSURES FOR THE SHUTTERS.
 FBC R301.2.1
  
 FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN INSTALLATION
 SCHEDULE AND KEY PLAN FOR THE STORM PANELS. SPECIFY THE
 OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR,
 ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL
 SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE
 APPLICABLE SECTION NUMBER FROM THE INSTALLATION
 DRAWINGS. I HAVE INCLUDED A LINK TO THE CONSTRUCTION
 SERVICES DEPARTMENT SITE THAT HAS MANY OF THE RELATED
 FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-31 Cont ID  
Sent By rmcdouga Date 2019-07-31 Time 09:53 Rev Time 0.00
Received By rmcdouga Date 2019-07-26 Time 14:21 Sent To  
Notes
2019-07-30 14:21:34RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-19 Cont ID  
Sent By rmcdouga Date 2019-07-19 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2019-07-17 Time 15:13 Sent To  
Notes
2019-07-18 15:13:36RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-08 Cont ID  
Sent By rmcdouga Date 2019-07-08 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2019-06-26 Time 10:01 Sent To  
Notes
***NONE***