Plan Review Details - Permit 19061225
Plan Review Stops For Permit 19061225
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 11:06 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 11:06 Sent To  
Notes
2019-07-15 11:11:29FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT SAYS SERVICE CHANGE?
  
 PLANS SHOW TEMPORARY PANEL?
  
 VALUE SHOWS $1,000????????
  
 WHERE IS SERVICE LOCATED?
 SHOW ALL OTHER SERVICES IN/ON BUILDING AND LOCATION.
 PANEL SHOWS NO LOADS?
 SUBMIT A LOAD CALCULATION FOR SERVICE.
 GROUNDING ELECTRODE SYSTEMS ARE TO BE COMMON.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 11:11 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 11:11 Sent To  
Notes
***NONE***