Plan Review Stops For Permit 19061225 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-07-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-07-15 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-07-15 |
Time |
11:06 |
Sent To |
|
|
Notes |
2019-07-15 11:11:29 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PERMIT SAYS SERVICE CHANGE? | | | | PLANS SHOW TEMPORARY PANEL? | | | | VALUE SHOWS $1,000???????? | | | | WHERE IS SERVICE LOCATED? | | SHOW ALL OTHER SERVICES IN/ON BUILDING AND LOCATION. | | PANEL SHOWS NO LOADS? | | SUBMIT A LOAD CALCULATION FOR SERVICE. | | GROUNDING ELECTRODE SYSTEMS ARE TO BE COMMON. |
|
|