Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-28 Cont ID  
Sent By sathomas Date 2019-06-28 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-06-28 Time 00:00 Sent To I
Notes
2019-06-28 15:22:251. UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS, AS WELL AS THE 2013 EDITION OF NFPA 13, 24,
 & 20.
  
 2. TOTAL SPRINKLER HEAD COUNT DOES NOT MATCH NUMBER
 DEPICTED ON DRAWINGS.
  
 3. THIS IS A NEW PLAN SUBMITTAL, WHAT IS THE PURPOSE
 FOR THE CLOUDED AREA CONTAINING 6 HEADS?
  
 S. THOMAS
 561-804-4728
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-01 Cont ID  
Sent By cpuell Date 2019-07-01 Time 11:31 Rev Time 0.00
Received By cpuell Date 2019-06-24 Time 14:31 Sent To  
Notes
2019-06-25 14:32:04ROUTED TO FIRE INBOX