Plan Review Details - Permit 19061134
Plan Review Stops For Permit 19061134
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By shill Date 2019-07-18 Time 16:40 Rev Time 0.00
Received By shill Date 2019-07-18 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-05 Cont ID  
Sent By shill Date 2019-07-05 Time 08:32 Rev Time 0.00
Received By shill Date 2019-07-05 Time 08:32 Sent To  
Notes
2019-07-05 08:38:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE THE INSTALLATION SCHEDULE TO STATE WHICH
 SHUTTER MOUNTING CONNECTION TYPE IS PROPOSED. C1, C4,
 C6, C8 ARE CIRCLED IN THE DETAILS, C8 REQUIRES 8"
 ANCHOR SPACING, BUT 9" IS PROPOSED FOR ALL OPENINGS.
  
 2. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By shill Date 2019-06-25 Time 06:39 Rev Time 0.00
Received By shill Date 2019-06-25 Time 06:39 Sent To  
Notes
2019-06-25 06:41:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, FBC B 1609 COMPLETE THE "SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES" OR PROVIDE
 ALL INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS
 EXCEL SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 A SCHEDULE WAS PROVIDED BUT DOES NOT INCLUDE ALL
 INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 2. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.
  
 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL". THE RESUBMITTAL FORM CAN BE
 FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-18 Cont ID  
Sent By shill Date 2019-07-18 Time 16:40 Rev Time 0.00
Received By shill Date 2019-07-09 Time 15:26 Sent To  
Notes
2019-07-10 15:26:22RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-05 Cont ID  
Sent By shill Date 2019-07-05 Time 08:39 Rev Time 0.00
Received By shill Date 2019-07-02 Time 13:49 Sent To  
Notes
2019-07-03 13:49:20RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By shill Date 2019-06-25 Time 06:42 Rev Time 0.00
Received By shill Date 2019-06-24 Time 11:49 Sent To  
Notes
***NONE***