Plan Review Details - Permit 19061116
Plan Review Stops For Permit 19061116 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-08-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-08-26 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-08-26 |
Time |
08:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-06-27 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-06-27 |
Time |
07:09 |
Sent To |
P |
|
Notes |
2019-06-27 07:14:20 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF A FLOOR PLAN SHOWING THE SCOPE OF | | WORK AND LOCATION OF THE SHOWER WITH SHOWER PAN | | DETAILS. FBC 107.2.1 | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-08-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-26 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-23 |
Time |
15:55 |
Sent To |
|
|
Notes |
2019-08-23 15:56:10 | RESUB ROUTED TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-06-28 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-06-28 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-06-24 |
Time |
14:58 |
Sent To |
|
|
Notes |
2019-06-25 14:58:43 | BLDG MISC 2 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-08-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-26 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-26 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-08-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-06-28 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-06-28 |
Time |
10:47 |
Sent To |
|
|
Notes |
2019-06-28 11:04:57 | | | 1) SUBMIT TWO SETS OF A FLOOR PLAN SHOWING THE SCOPE OF | | WORK AND LOCATION OF THE SHOWER WITH SHOWER PAN | | DETAILS. FBC 107.2.1 | | | | 2) THE PLUMBING WORK TO BE DONE MUST BE DONE BY A | | LICENSED PLUMBING CONTRACTOR PER FL. STATUTE 489. | | SUBMIT A PERMIT APPLICATION FROM A CURRENTLY LICENSED | | PLUMBING CONTRACTOR. A CGC CANNOT INSTALL THE SHOWER | | PAN OR ANY PLUMBING ITEMS. WPB AMEND. TO FBC SEC. | | 105.1. | | | | 3) INDICATE ON THE REQUESTED PLANS IF A NEW SHOWER | | VALVE WILL BE INSTALLED. THE VALVE SHALL BE | | THERMOSTATIC OR PRESSURE-BALANCED.WPB AMEND. TO FBC | | SEC. 107.2.1. | | | | 4) MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND | | SHOWER AREAS AND WALL AND CEILING PANELS IN SHOWER | | AREAS SHALL BE OF MATERIALS LISTED IN 2017 FBC TABLE | | 2509.2. INDICATE TYPE OF MATERIAL ON REQUESTED PLANS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
|