Plan Review Details - Permit 19060810
Plan Review Stops For Permit 19060810
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-16 Cont ID  
Sent By pvalenti Date 2019-07-16 Time 08:19 Rev Time 0.00
Received By pvalenti Date 2019-07-16 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-20 Cont ID  
Sent By shill Date 2019-06-20 Time 17:44 Rev Time 0.00
Received By shill Date 2019-06-20 Time 17:44 Sent To  
Notes
2019-06-20 17:48:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, THE INSTALLATION SCHEDULE DOES NOT
 SPECIFY WHICH TAPCON IS PROPOSED, PLEASE REVISE. PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 3. FBC 107, THE PLAN SHOWS THE FRONT DOOR COVERED, AND
 ANOTHER OPENING AS EGRESS. REVISE PLAN TO NOTE ROOM
 DESIGNATION; THIS CANNOT BE A ROOM THAT IS NOT WITHIN
 THE CONTROL OF THE OCCUPANT.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-16 Cont ID  
Sent By pvalenti Date 2019-07-16 Time 08:20 Rev Time 0.00
Received By pvalenti Date 2019-07-11 Time 14:32 Sent To  
Notes
2019-07-12 14:33:07ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-20 Cont ID  
Sent By shill Date 2019-06-20 Time 17:49 Rev Time 0.00
Received By shill Date 2019-06-18 Time 10:33 Sent To  
Notes
***NONE***