Plan Review Details - Permit 19060806
Plan Review Stops For Permit 19060806
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-28 Cont ID  
Sent By dbattles Date 2019-08-28 Time 08:27 Rev Time 0.00
Received By dbattles Date 2019-08-28 Time 08:27 Sent To  
Notes
2019-08-28 08:28:31PROVISO:
 PROVIDE PRODUCT APPROVAL AND IMPACT PROTECTION IF NEW
 WINDOW IS BEING INSTALLED ARE REPAIR AREA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By dbattles Date 2019-07-12 Time 16:20 Rev Time 0.00
Received By dbattles Date 2019-07-12 Time 15:38 Sent To  
Notes
2019-07-12 16:21:49BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19060806
 REVIEWED: JULY 12, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH
 CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN
 ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL
 COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY
 ADJUSTED PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL.
 - ALSO, PROVIDE PROJECT DESCRIPTION IF IT IS NOT
 INCLUDED ON THE PROPOSAL.
  
 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE).
  
 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED IF WORK AREA COMPLIANCE METHOD IS
 BEING USED.
  
 107.5.3 FBC[AMENDED] PLEASE PROVIDE DRAWING THAT DEPICT
 EXISTING CONDITIONS, DEMOLITION (IF APPLICABLE) AND
 PROPOSED CHANGES. DESIGN CRITERIA, PRODUCT APPROVALS,
 SCHEDULES AND DETAILS FOR NEW WORK.
 NEW WORK WILL NEED TO COMPLY WITH ENERGY CODE.
 ALSO, THE FLOOR PLAN LABELED AS-BUILT SOUNDS LIKE WORK
 HAS BEEN PERFORMED. IS THIS WORK ALREADY COMPLETE?
  
 REVIEW HAS NOT BEEN PERFORMED DUE TO LACK OF
 INFORMATION ON THE PLANS. PLEASE PROVIDE TWO SETS OF
 PLANS THAT DEPICT THE WORK TO BE PERFORMED SO THAT A
 REVIEW CAN BE COMPLETED ON THE SECOND REVIEW.
  
 NOTES:
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By ppetty Date 2019-08-27 Time 14:05 Rev Time 0.00
Received By ppetty Date 2019-08-27 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By jpearson Date 2019-07-12 Time 08:31 Rev Time 0.00
Received By jpearson Date 2019-07-12 Time 08:28 Sent To  
Notes
2019-07-12 08:31:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. WPB FBC 107.2.1,
 107.3.5; FS 471, 481
 3. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS
 FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-08-28 Cont ID  
Sent By fmittner Date 2019-08-28 Time 10:27 Rev Time 0.00
Received By fmittner Date 2019-08-28 Time 10:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By fmittner Date 2019-07-05 Time 13:56 Rev Time 0.00
Received By fmittner Date 2019-07-05 Time 13:56 Sent To  
Notes
2019-07-05 13:57:27SCOPE OF WORK IS NOT CLEAR. NO NOA'S. PLEASE CLEARLY
 EXPLAIN PROJECT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-29 Cont ID  
Sent By tklarge Date 2019-08-29 Time 14:15 Rev Time 0.00
Received By tklarge Date 2019-08-20 Time 15:29 Sent To  
Notes
2019-08-20 15:29:58R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-12 Cont ID  
Sent By dbattles Date 2019-07-12 Time 16:20 Rev Time 0.00
Received By dbattles Date 2019-06-18 Time 14:20 Sent To  
Notes
2019-06-19 14:20:18R32

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-08-27 Cont ID  
Sent By cmontell Date 2019-08-27 Time 14:26 Rev Time 0.00
Received By cmontell Date 2019-08-27 Time 14:26 Sent To  
Notes
2019-08-27 14:27:22PER PLANS NO MECHANICAL WORK TO BE DONE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By cmontell Date 2019-07-10 Time 13:54 Rev Time 0.00
Received By cmontell Date 2019-07-10 Time 13:54 Sent To  
Notes
2019-07-10 13:54:08MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLANS AND SCOPE OF WORK PER 2017
 FLORIDA BUILDING CODE - BUILDING, SIXTH EDITION SEC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-08-29 Cont ID  
Sent By tklarge Date 2019-08-29 Time 14:15 Rev Time 0.00
Received By tklarge Date 2019-08-29 Time 14:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By thunt Date 2019-07-08 Time 09:34 Rev Time 0.00
Received By thunt Date 2019-07-08 Time 09:08 Sent To  
Notes
2019-07-08 09:34:03PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) PLANS SHALL BE SIGNED BY PERSON TAKING
 RESPONSIBILITY AND LICENSED BY F.S 471, 481, 489. VANN
 BUCKLE PER DBPR AND PBC GOV IS NOT LICENSED UNDER ANY
 THE F.S LISTED.
  
 2) PROVIDE A NARRATIVE OF THE SCOPE OF WORK. YOUR PLAN
 SUBMITTED IS NOT CLEAR WHAT IS BEING DONE. FBC 107.3.5
  
 3) PROVIDE SIGNED BONA FIDE CONTRACT. WPB AMEND 109.3
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-08-28 Cont ID  
Sent By fmittner Date 2019-08-28 Time 10:27 Rev Time 0.00
Received By fmittner Date 2019-08-28 Time 10:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-05 Cont ID  
Sent By fmittner Date 2019-07-05 Time 13:57 Rev Time 0.00
Received By fmittner Date 2019-07-05 Time 13:57 Sent To  
Notes
***NONE***