2019-06-19 16:12:16 | GAS 1ST REVIEW**DENIED** |
| |
| 1- PROVIDE PAGE #9 OF THE INSTALLATION MANUAL SHOWING |
| REQUIRED DISTANCE FROM ANY DOOR OR WINDOW. SUBMIT TWO |
| COPIES OF A HOUSE PLAN SHOWING THE LOCATION OF THE |
| TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE OF |
| ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| |
| 2- VALUE APPEARS LOW. PROVIDE A SIGNED BONA FIDE |
| CONTRACT. VALUE SHALL INCLUDE ALL COST INCLUDING TANK |
| LESS WATER HEATER. WPB AMEND 109.3 |
| |
| 3- CITY RECORDS # 14060789 SHOWS EXISTING SYSTEM .LIST |
| THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| G2413.4 (1 ) THROUGH G2413.4 (21). |
| |
| 4- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| |
| 5- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| G2421.1. |
| |
| 6- SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| PROPER PIPE SIZE AND BTU LOAD. |
| |
| 7- PLAN CALLS OUT FOR 55? OF NEW PIPING BUT THE SIZING |
| CHART PROVIDED CALLS OUT 125?. PLEASE CLARIFY FBC |
| 107.2.1 |
| |
| 8- PLAN CALLS OUT FOR ?? P.E PIPING FOR SIZING CHART |
| PROVIDED IS CALLING OUT 1?. PLEASE CLARIFY. FBC 107.2.1 |
| |
| 9) PROVIDE ENERGY U.E.F RATING OF THIS TANKLESS SHOWING |
| IT MEETS FEDERAL MIN STANDARDS. FBC 107.3.5 |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| BUILDING DIVISION |