Plan Review Details - Permit 19060596
Plan Review Stops For Permit 19060596
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-07-08 Cont ID  
Sent By shill Date 2019-07-08 Time 07:26 Rev Time 0.00
Received By shill Date 2019-07-08 Time 07:26 Sent To  
Notes
2019-06-27 13:55:14SENT TO MISC2 BIN JL

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 12:15 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 12:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 09:41 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 09:41 Sent To  
Notes
2019-07-15 09:58:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 INVERTER 32A X 125% = 40A + 150 = 190A 150A X 120% =
 180A
  
  
 705.12(D)(3)(B) WHERE TWO SOURCES, ONE A UTILITY AND
 THE OTHER AN
 INVERTER, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT
 CONTAINS
 LOADS, THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT
 CIRCUIT
 CURRENT AND THE RATING OF THE OVERCURRENT DEVICE
 PROTECTING THE
 BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF
 THE
 BUSBAR. THE BUSBAR SHALL BE SIZED FOR THE LOADS
 CONNECTED IN
 ACCORDANCE WITH ARTICLE 220. A PERMANENT WARNING LABEL
 SHALL
 BE APPLIED TO THE DISTRIBUTION EQUIPMENT ADJACENT TO
 THE BACKFED
 BREAKER FROM THE INVERTER THAT DISPLAYS THE FOLLOWING
 OR
 EQUIVALENT WORDING:

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-27 Cont ID  
Sent By jroach Date 2019-07-12 Time 14:35 Rev Time 0.00
Received By jleahy Date 2019-06-27 Time 13:51 Sent To B
Notes
2019-06-27 13:54:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BACKFED BREAKER IN PANEL NEEDS TO BEW LOCATED AT THE
 OPPOSITE END OF THE BUS FROM THE MAIN. PLEASE NOTE ON
 PLAN.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL
  
 SUBMIT A COPY OF THE SIGNED CONTRACT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-12 Cont ID  
Sent By cpuell Date 2019-07-12 Time 14:48 Rev Time 0.00
Received By cpuell Date 2019-06-12 Time 14:31 Sent To  
Notes
2019-07-08 07:26:467/8 TO ZONING
  
2019-06-13 14:31:14ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-12 Cont ID  
Sent By jroach Date 2019-07-12 Time 14:35 Rev Time 0.00
Received By jroach Date 2019-07-12 Time 14:35 Sent To E
Notes
2019-06-13 16:39:29SEND TO ZONING LAST