Plan Review Details - Permit 19060579
Plan Review Stops For Permit 19060579
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2019-08-28 Cont ID  
Sent By jleahy Date 2019-08-28 Time 15:32 Rev Time 0.00
Received By jleahy Date 2019-08-28 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-12 Cont ID  
Sent By pvalenti Date 2019-08-12 Time 17:41 Rev Time 0.00
Received By pvalenti Date 2019-08-12 Time 17:41 Sent To  
Notes
2019-08-12 17:44:54***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW DENIED:
  
 FBC B 109.3 THE VALUATION IS TOO LOW, SEE ELECTRIC
 REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By pvalenti Date 2019-07-18 Time 06:39 Rev Time 0.00
Received By pvalenti Date 2019-07-18 Time 06:39 Sent To  
Notes
2019-07-18 06:40:27***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW PASSED WITH NOTES:
  
 STILL NEED TO PASS ELECTRIC AND ZONING REVIEWS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-06-27 Cont ID  
Sent By pvalenti Date 2019-06-27 Time 16:57 Rev Time 0.00
Received By pvalenti Date 2019-06-27 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-08-28 Cont ID  
Sent By jleahy Date 2019-08-28 Time 15:32 Rev Time 0.00
Received By jleahy Date 2019-08-28 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-08-12 Cont ID  
Sent By hmtribou Date 2019-08-08 Time 15:18 Rev Time 0.00
Received By jleahy Date 2019-08-12 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By jleahy Date 2019-07-17 Time 15:38 Rev Time 0.00
Received By jleahy Date 2019-07-17 Time 15:37 Sent To  
Notes
2019-07-17 15:39:25COMMENTS FROM FIRST REVIEW NOT ADDRESSED
  
 ELECTRICAL NEEDS TO BE ON THIS PLAN
  
 VALUE NOT ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-28 Cont ID  
Sent By jleahy Date 2019-06-28 Time 15:36 Rev Time 0.00
Received By jleahy Date 2019-06-28 Time 15:36 Sent To Z
Notes
2019-06-28 15:44:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE IS LOW
  
 PLEASE SUBMIT A SIGNED CONTRACT WITH THE OWNER FOR
 REVIEW.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SHOW WHERE BRANCH CIRCUIT IS FROM (PANEL) AND WHAT
 CIRCUIT NUMBER OR NUMBERS.
  
 3) WHAT IS THE VOLTAGE DROP ON CIRCUIT. SHOW THE
 DISTANCE FROM PANEL TO LOAD.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-28 Cont ID  
Sent By jleahy Date 2019-08-28 Time 15:32 Rev Time 0.00
Received By jleahy Date 2019-08-26 Time 15:38 Sent To  
Notes
2019-08-26 15:38:39RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-12 Cont ID  
Sent By pvalenti Date 2019-08-12 Time 17:45 Rev Time 0.00
Received By pvalenti Date 2019-08-06 Time 14:15 Sent To  
Notes
2019-08-07 14:15:44RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-18 Cont ID  
Sent By pvalenti Date 2019-07-18 Time 06:40 Rev Time 0.00
Received By pvalenti Date 2019-07-11 Time 14:33 Sent To  
Notes
2019-07-12 14:34:00RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-02 Cont ID  
Sent By cpuell Date 2019-07-02 Time 13:27 Rev Time 0.00
Received By cpuell Date 2019-06-12 Time 13:51 Sent To  
Notes
2019-06-13 13:52:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 4 Status P Date 2019-08-28 Cont ID  
Sent By hmtribou Date 2019-08-28 Time 09:27 Rev Time 0.00
Received By hmtribou Date 2019-08-28 Time 09:26 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2019-08-08 Cont ID  
Sent By hmtribou Date 2019-08-08 Time 15:18 Rev Time 0.00
Received By hmtribou Date 2019-08-08 Time 15:18 Sent To E
Notes
2019-08-08 14:27:04LOCATION OF SIGN DOES NOT MEET CODE. PLEASE TALK TO
 SEAN HICKMAN AT INTERPLAN REGARDING AN EMAIL WITH
 HEATHER DANFFORTH AT THE CITY OF WEST PALM BEACH WITH
 APPROVED LOCATION WHICH IS 11.55' FEET FROM THE
 SOUTHEST PROPERTY LINE SO THAT THE EXISITNG TREE IS NOT
 IMPACTED AND 5 FEET FROM PROPERTY LINE. DIMENSIONS MUST
 BE PROVIDED ON THE PLAN. QUESTIONS CALL HEATHER
 DANFORTH AT 561-822-1562
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By hmtribou Date 2019-07-17 Time 09:31 Rev Time 0.00
Received By hmtribou Date 2019-07-17 Time 09:31 Sent To E
Notes
2019-07-17 09:33:54PROPOSED SIGN LOCATION DOES NOT MATCH APPROVED PLANS
 PROPOSED SIGN LOCATION WILL IMPACT REQUIRED TREE
 LOCATED IN REQUIRED TREE ISLAND FOR PARKING LOT OF
 ENTIRE PLAZA.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By hmtribou Date 2019-07-02 Time 09:03 Rev Time 0.00
Received By hmtribou Date 2019-07-02 Time 09:03 Sent To I
Notes
2019-07-02 09:02:45FOR QUESTIONS PLEASE CALL HEATHER DANFORTH 561-822-1562
 1. LOCATION OF SIGN DOES NOT MATCH THE APPROVED SITE
 PLAN. A MINOR AMENDMENT WILL BE REQUIRED TO BE
 SUBMITTED.
 2. SIGN MUST BE LOCATED FIVE FEET FROM THE PUBLIC
 RIGHT-OF-WAY LINE PER SEC. 94-408(2)E.2.
 3. LABEL THE LINEAR DISTANCE OF THE STREET FRONTAGE ON
 THE SITE PLAN FOR COMPLIANCE WITH MAXIMUM SUM OF TOTAL
 AREA PER 94-408(2)B.
  
2019-06-13 16:41:21SEND TO ZONING LAST