Plan Review Details - Permit 19060342
Plan Review Stops For Permit 19060342
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-07-13 Cont ID  
Sent By tklarge Date 2019-07-13 Time 03:40 Rev Time 0.00
Received By tklarge Date 2019-07-13 Time 02:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 17:06 Rev Time 0.00
Received By thunt Date 2019-06-10 Time 17:06 Sent To  
Notes
2019-06-10 17:11:29GAS 1ST REVISION REVIEW**DENIED**
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER R 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2.
  
 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-RES.
 SEC. G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 4) THE MOUNTING MIN DISTANCE PERMITTED FOR THE TANKLESS
 WATER HEATER FROM A DOOR OR WINDOW IS 4'. PLEASE REFER
 TO PAGE 8 THE THE INSTALLATION MANUAL. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-13 Cont ID  
Sent By tklarge Date 2019-07-13 Time 03:41 Rev Time 0.00
Received By tklarge Date 2019-07-10 Time 14:29 Sent To  
Notes
2019-07-11 14:29:29RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 17:11 Rev Time 0.00
Received By thunt Date 2019-06-07 Time 11:00 Sent To  
Notes
2019-06-10 11:00:29REVISION ROUTED TO THUNT

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-13 Cont ID  
Sent By tklarge Date 2019-07-13 Time 03:40 Rev Time 0.00
Received By tklarge Date 2019-07-13 Time 03:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 17:05 Rev Time 0.00
Received By thunt Date 2019-06-10 Time 17:05 Sent To  
Notes
2019-06-10 17:05:54PLUMBING 1ST REVIEW**DENIED**
  
 SEE GAS REVIEW COMMENTS.
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  