Plan Review Details - Permit 19060311
Plan Review Stops For Permit 19060311
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-30 Cont ID  
Sent By dbattles Date 2019-08-30 Time 08:27 Rev Time 0.00
Received By dbattles Date 2019-08-30 Time 08:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-16 Cont ID  
Sent By dbattles Date 2019-08-16 Time 08:05 Rev Time 0.00
Received By dbattles Date 2019-08-16 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By dbattles Date 2019-07-17 Time 11:00 Rev Time 0.00
Received By dbattles Date 2019-07-16 Time 12:40 Sent To  
Notes
2019-07-17 11:01:15BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19060311
 REVIEWED: JULY 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 716.1 FBC[B]GENERAL. OPENING PROTECTIVES REQUIRED BY
 OTHER SECTIONS OF THIS CODE SHALL COMPLY WITH THE
 PROVISIONS OF THIS SECTION.
  -PLEASE ADD THE DOOR ACROSS FROM ACCESSIBLE BATHROOM
 TO THE DOOR SCHEDULE. INCLUDE FIRE RATING OF EXISTING,
 OR FOR NEW IF APPLICABLE.
  -DOES THIS DOOR LEAD TO ANOTHER SECTION OF CASPER AND
 IS IT EGRESS FOR THAT SECTION?
  
 NOTES:
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-08-29 Cont ID  
Sent By jpearson Date 2019-08-29 Time 13:13 Rev Time 0.00
Received By jpearson Date 2019-08-29 Time 13:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-26 Cont ID  
Sent By jpearson Date 2019-08-26 Time 07:11 Rev Time 0.00
Received By jpearson Date 2019-08-26 Time 07:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-08 Cont ID  
Sent By jpearson Date 2019-08-08 Time 11:13 Rev Time 0.00
Received By jpearson Date 2019-08-08 Time 11:13 Sent To  
Notes
2019-08-08 11:13:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE MUST
 INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481 (NO DIGITAL SIGNATURE ON PLANS SUBMITTED.)
  
 NEW COMMENT:
  
 2. THE PLANS UPLOADED APPEAR TO BE A SCAN AND ARE
 ILLEGIBLE. PROVIDE LEGIBLE PLANS. WPB FBC 107.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 12:57 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 12:57 Sent To  
Notes
2019-07-14 12:57:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE MUST
 INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By pleduc Date 2019-08-29 Time   Rev Time 0.00
Received By pleduc Date 2019-08-29 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-07 Cont ID  
Sent By pleduc Date 2019-08-07 Time   Rev Time 0.00
Received By pleduc Date 2019-08-07 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-03 Cont ID  
Sent By pleduc Date 2019-07-03 Time   Rev Time 0.00
Received By pleduc Date 2019-07-03 Time 11:24 Sent To  
Notes
2019-07-03 11:50:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) DOOR 104 IS AN EXIT DOOR AND THE HARDWARE WITHIN THE
 DOOR SCHEDULE INDICATES IT WILL HAVE KEYED ENTRY.
  
 THE HARDWARE SHALL COMPLY WITH NFPA 101 CH 7, MEANS OF
 EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
  
 PLEASE ENSURE COMPLIANCE FOR FIRE INSPECTIONS.
  
  
  
 2) ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-30 Cont ID  
Sent By skennedy Date 2019-08-30 Time 10:06 Rev Time 0.00
Received By skennedy Date 2019-08-29 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-29 Cont ID  
Sent By jesmith Date 2019-08-29 Time 08:06 Rev Time 0.00
Received By jesmith Date 2019-08-29 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-20 Cont ID  
Sent By rmcdouga Date 2019-08-20 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2019-07-31 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 14:49 Rev Time 0.00
Received By shill Date 2019-06-28 Time 10:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By dbattles Date 2019-07-17 Time 11:03 Rev Time 0.00
Received By dbattles Date 2019-07-17 Time 11:03 Sent To  
Notes
2019-07-17 11:04:22NO CHANGE IN OCCUPANY OR ADDITION OF SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By skennedy Date 2019-08-30 Time 10:06 Rev Time 0.00
Received By skennedy Date 2019-08-30 Time 10:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By cmontell Date 2019-07-19 Time 14:44 Rev Time 0.00
Received By cmontell Date 2019-07-19 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-08-29 Cont ID  
Sent By jesmith Date 2019-08-29 Time 13:28 Rev Time 0.00
Received By jesmith Date 2019-08-29 Time 13:18 Sent To  
Notes
2019-08-29 13:28:19PLUMBING APPROVED
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By jesmith Date 2019-08-29 Time 08:06 Rev Time 0.00
Received By jesmith Date 2019-08-29 Time 08:05 Sent To  
Notes
2019-08-29 08:06:04PLUMBING APPROVED
2019-08-26 07:10:11NO NOTE
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-20 Cont ID  
Sent By jesmith Date 2019-08-20 Time 11:54 Rev Time 0.00
Received By jesmith Date 2019-08-20 Time 11:53 Sent To  
Notes
2019-08-20 11:54:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
  
 1. SECOND REQUEST; PER FBC PL 608.1, SPECIFY AND
 PROVIDE BACKFLOW PREVENTION DEVICE IN THE WATER SERVICE
 DOWNSTREAM OF WATER METER. IT IS THE POSITION OF THIS
 OFFICE, THAT EACH INDIVIDUAL UNIT IS A SEPARATE ENTITY
 AND IS REQUIRED TO PROVIDE PROTECTION TO THE BUILDING
 POTABLE WATER SYSTEM FROM POTENTIAL CROSS CONNECTIONS
 THAT MAY ARISE IN A GIVEN UNIT. PLEASE CONTACT MR. TIM
 LARGE, CHIEF PLUMBING INSPECTOR AT 561-805-6692 IF
 ADDITIONAL CLARIFICATION IS REQUIRED.
 2. ADDITIONAL CLARIFICATION REQUIRED; PROVIDE NOTE ON
 PLAN SHEET P-100: PROVIDE TRAP PRIMERS AT ALL FLOOR
 DRAINS. SEE TRAP PRIMER DETAIL ON P-501.
 3. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE MUST
 INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481 (NO DIGITAL SIGNATURE ON PLANS SUBMITTED.)
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060311 701 S ROSEMARY AVE # 140
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By gjohnson Date 2019-07-18 Time 16:47 Rev Time 0.00
Received By gjohnson Date 2019-07-18 Time 15:11 Sent To  
Notes
2019-07-24 11:25:141ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
  
 1. SHT. A-710 SHOW COMPLIANCE WITH THE FOLLOWING:
 A) THE CENTER OF THE TOILET PAPER DISPENSER SHALL BE
 7"-9" FROM THE FRONT OF THE TOILET DETAIL #5 SHOWS
 111/2" PER FBC ACC 604.7
 B)GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,PER FBC ACC 609.4
 C) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE
 SPRUNG TO RETURN TO A LIFTED POSITION.PER FBC ACC 604.4
 D)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. PER FBC ACC 603.3
  
 2.ISOLATION BACKFLOW REQUIRED ON WATER SERVICE TO UNIT.
 PER FBC PL 608.1
  
 3. SHOW REQUIRED TRAP PRIMER ON FLOOR DRAIN. FBC PL
 1002.4.1
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2019-08-30 Cont ID  
Sent By skennedy Date 2019-08-30 Time 10:07 Rev Time 0.00
Received By skennedy Date 2019-08-30 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-08-30 Cont ID  
Sent By dbattles Date 2019-08-30 Time 08:41 Rev Time 0.00
Received By dbattles Date 2019-08-30 Time 08:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-08-26 Cont ID  
Sent By jpearson Date 2019-08-26 Time 07:11 Rev Time 0.00
Received By jpearson Date 2019-08-26 Time 07:11 Sent To  
Notes
2019-08-26 07:11:13107.2.1 FBC[AMENDED] SHEETS UPLOADED INTO DRAWINGS
 FOLDER ARE NOT DIGITALLY SIGNED.
  
 UPON APPROVAL OF ALL REVIEWS BESIDES SIGNATURE REVIEW
 PLEASE UPLOAD PDF OF PLANS WITH DIGITAL SIGNATURE TO
 THE SIGNATURES FOLDER IN PROJECTDOX, OR PROVIDE ONE
 PAPER SET TO THE FRONT COUNTER THAT ARE SIGNED AND
 SEALED FOR SIGNATURE VERIFICATION. THIS SET WILL BE
 RETAINED BY DEVELOPMENT SERVICES FOR SIGNATURE RECORD.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-08-16 Cont ID  
Sent By dbattles Date 2019-08-16 Time 09:02 Rev Time 0.00
Received By dbattles Date 2019-08-16 Time 09:02 Sent To  
Notes
2019-08-16 09:14:19107.2.1 FBC[AMENDED] SHEETS UPLOADED INTO DRAWINGS
 FOLDER ARE NOT DIGITALLY SIGNED.
  
 UPON APPROVAL OF ALL REVIEWS BESIDES SIGNATURE REVIEW
 PLEASE UPLOAD PDF OF PLANS WITH DIGITAL SIGNATURE TO
 THE SIGNATURES FOLDER IN PROJECTDOX, OR PROVIDE ONE
 PAPER SET TO THE FRONT COUNTER THAT ARE SIGNED AND
 SEALED FOR SIGNATURE VERIFICATION. THIS SET WILL BE
 RETAINED BY DEVELOPMENT SERVICES FOR SIGNATURE RECORD.
  
  
  
  
2019-08-16 08:17:56NEW SHEETS NOT DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By dbattles Date 2019-07-17 Time 11:10 Rev Time 0.00
Received By dbattles Date 2019-07-17 Time 11:10 Sent To  
Notes
2019-07-17 11:05:01ANY SHEETS PROVIDED FOR RE-SUBMITTAL TO ADDRESS
 COMMENTS TO BE DIGITALLY SIGNED.
2019-07-14 11:30:15ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By eschneid Date 2019-08-29 Time 16:36 Rev Time 0.25
Received By eschneid Date 2019-08-29 Time 16:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-08-06 Cont ID  
Sent By eschneid Date 2019-08-06 Time 11:48 Rev Time 0.25
Received By eschneid Date 2019-08-06 Time 11:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By eschneid Date 2019-07-05 Time 14:18 Rev Time 0.50
Received By eschneid Date 2019-07-05 Time 14:18 Sent To  
Notes
2019-07-05 14:21:08FAILED
  
 1) THE CITYPLACE RETAIL MANAGEMENT STAMP IS REQUIRED ON
 THE PLANS, OR A LETTER FROM THEM APPROVING THE PLANS IS
 REQUIRED.
  
 2) THE MECHANICAL PLANS LIST TWO NEW AIR HANDLER UNITS.
 PLEASE CLARIFY IF THESE ARE BEING INSTALLED ON THE ROOF
 OF THE BUILDING. IF SO, YOU NEED TO PROVIDE SITE LINE
 DRAWINGS TO SHOW THAT THEY ARE SCREENED FROM VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]