Plan Review Details - Permit 19060265
Plan Review Stops For Permit 19060265
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 08:01 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 08:01 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By jpearson Date 2019-06-20 Time 08:37 Rev Time 0.00
Received By jpearson Date 2019-06-20 Time 08:37 Sent To M
Notes
2019-06-20 08:36:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. THE FAN SPECIFIED COULD NOT BE FOUND ON THE COMPANY
 WEBSITE. FOR THE COMPARABLE MODELS LISTED, THE RV125,
 RV150, AND RV200, THE SPEC SHEETS DO NOT SHOW THIS
 BEING SUPPLIED WITH A CORD. ADDITIONALLY, A CORD AND
 RECEPTACLE ABOVE A FIXED CEILING IS NOT PERMITTED PER
 CODE. A FIXED WIRING METHOD WITH A DISCONNECT WITHIN
 SIGHT WILL BE REQUIRED. PROVIDE CORRECTION. NEC 400.8,
 422.30 (SPEC SHEET PROVIDED, BUT THE CORD AND
 RECEPTACLE IS STILL SHOWN. A CODE REFERENCE PERMITTING
 THIS INSTALLATION AS SHOWN WAS NOT PROVIDED.
 ADDITIONALLY, THE RESPONSE LETTER STATES THERE IS A
 TIMER TO BE INSTALLED, BUT THIS IS NOT SHOWN ON THE
 PLAN. PROVIDE DETAILS AND CORRECTIONS.)
 3. MECHANICAL REVIEWER TO ADDRESS MOUNTING OF UNIT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-12 Cont ID  
Sent By jpearson Date 2019-06-12 Time 08:40 Rev Time 0.00
Received By jpearson Date 2019-06-12 Time 08:40 Sent To I
Notes
2019-06-11 15:52:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THIS BUILDING IS A TYPE 1 BUILDING, ROMEX IS NOT
 PERMITTED. PROVIDE CORRECTION. NEC 334.12(A)(1), 334.10
 2. THE FAN SPECIFIED COULD NOT BE FOUND ON THE COMPANY
 WEBSITE. FOR THE COMPARABLE MODELS LISTED, THE RV125,
 RV150, AND RV200, THE SPEC SHEETS DO NOT SHOW THIS
 BEING SUPPLIED WITH A CORD. ADDITIONALLY, A CORD AND
 RECEPTACLE ABOVE A FIXED CEILING IS NOT PERMITTED PER
 CODE. A FIXED WIRING METHOD WITH A DISCONNECT WITHIN
 SIGHT WILL BE REQUIRED. PROVIDE CORRECTION. NEC 400.8,
 422.30
 3. SPEC SHEET FOR THE ABOVE MENTIONED MODELS STATES
 THAT THE FAN MUST BE MOUNTED IN VERTICAL POSITION. THE
 SUBMITTED PLAN SHOWS THE FAN MOUNTED HORIZONTALLY.
 PROVIDE CLARIFICATION OR CORRECTIONS AS NEEDED. PROVIDE
 INSTALLATION INSTRUCTIONS FOR RV100. NEC 110.3; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-06-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-24 Time 14:48 Sent To  
Notes
2019-06-25 14:48:54RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-20 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-17 Time 14:30 Sent To  
Notes
2019-06-18 14:30:37RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-06 Time 13:20 Sent To  
Notes
2019-06-07 13:20:17ROUTED TO MECH<5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-06-11 Cont ID  
Sent By cmontell Date 2019-06-11 Time 09:32 Rev Time 0.00
Received By cmontell Date 2019-06-11 Time 09:32 Sent To  
Notes
***NONE***