Plan Review Details - Permit 19060208
Plan Review Stops For Permit 19060208
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By jbrooks Date 2019-09-10 Time 09:55 Rev Time 0.00
Received By jbrooks Date 2019-09-10 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By jbrooks Date 2019-06-25 Time 09:44 Rev Time 0.00
Received By jbrooks Date 2019-06-25 Time 09:44 Sent To  
Notes
2019-06-25 09:44:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 RESULTS: DENIED
 1. FBC B 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 2. FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS
 DESCRIBED IN SECTION 504 SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 8. IN ADDITION TO THE
 REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 7.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By pleduc Date 2019-08-30 Time   Rev Time 0.00
Received By pleduc Date 2019-08-30 Time 10:28 Sent To B
Notes
2019-08-30 10:29:37THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-07 Cont ID  
Sent By pleduc Date 2019-06-07 Time   Rev Time 0.00
Received By pleduc Date 2019-06-07 Time 13:44 Sent To B
Notes
2019-06-07 13:55:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO ADDRESS NOR SUITE NUMBER ON THE
 SUBMITTED DRAWINGS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
 PLEASE PROVIDE THE ADDRESS AND SUITE NUMBER ON EACH
 PLAN SHEET FOR CALRIFICATION AND IDENTIFICATION
 PURPOESE.
  
  
  
 2) THERE ARE NO INDICATIONS OF A FIRE ALARM OR FIRE
 SPRINKLER SYSTEM.
  
 PER NFPA 1
  
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
 (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION DOCUMENTS ON SITE.
  
  
 PLEASE PROVIDE APPLICABLE DETAILS AND A NOTE STATING
 ALL WORK ON THESE SYSTEMS SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-10 Cont ID  
Sent By jbrooks Date 2019-09-10 Time 09:56 Rev Time 0.00
Received By jbrooks Date 2019-08-28 Time 13:19 Sent To  
Notes
2019-08-29 13:19:52RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By jbrooks Date 2019-06-25 Time 09:50 Rev Time 0.00
Received By jbrooks Date 2019-06-05 Time 15:24 Sent To  
Notes
2019-06-06 15:24:30ROUTED TO FIRE INBOX