Plan Review Details - Permit 19060130
Plan Review Stops For Permit 19060130
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 18:56 Rev Time 0.00
Received By shill Date 2019-07-09 Time 18:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 10:38 Rev Time 0.00
Received By shill Date 2019-07-03 Time 10:38 Sent To  
Notes
2019-07-03 10:45:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 4. NON IMPACT PRODUCT APPROVAL WAS SUBMITTED. IMPACT
 PROTECTION IS REQUIRED, FBC B 1609.1.2. IF REMOVABLE
 IMPACT PROTECTION IS PROPOSED, APPROVAL BY THE BUILDING
 OFFICIAL IS REQUIRED. IF IMPACT GLASS OR NON-REMOVABLE
 SHUTTERS ARE NOT PROPOSED, PLEASE SEND ME AN EMAIL
 PRIOR TO RESUBMITTING.
  
 THE FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED (HAS
 BOTH IMPACT AND NON IMPACT OPTIONS), BUT THE
 INSTALLATION INSTRUCTIONS AND EVALUATION REPORT
 UPLOADED PREVIOUSLY IS FOR NON IMPACT GLASS. IMPACT
 PROTECTION IS REQUIRED. IMPACT GLASS IS GENERALLY
 REQUIRED FOR COMMERCIAL AND MULTI FAMILY.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-24 Cont ID  
Sent By shill Date 2019-06-24 Time 10:43 Rev Time 0.00
Received By shill Date 2019-06-24 Time 10:43 Sent To  
Notes
2019-06-24 10:59:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, THE FLOOR PLAN PROVIDED IS A PHOTOGRAPH.
 PROVIDE A SCANNED DOCUMENT AS THIS IS DIFFICULT TO
 READ.
  
 2. FBC 107, PROVIDE A FLOOR PLAN WHICH HAS ALL TEXT
 ORIENTED IN THE SAME DIRECTION AS THIS IS DIFFICULT TO
 READ.
  
 3. FBC B 1609, PROVIDE THE FLORIDA STATE PRODUCT
 APPROVAL COVER SHEET.
  
 4. NON IMPACT PRODUCT APPROVAL WAS SUBMITTED. IMPACT
 PROTECTION IS REQUIRED, FBC B 1609.1.2. IF REMOVABLE
 IMPACT PROTECTION IS PROPOSED, APPROVAL BY THE BUILDING
 OFFICIAL IS REQUIRED. IF IMPACT GLASS OR NON-REMOVABLE
 SHUTTERS ARE NOT PROPOSED, PLEASE SEND ME AN EMAIL
 PRIOR TO RESUBMITTING.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 18:56 Rev Time 0.00
Received By shill Date 2019-07-03 Time 12:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 10:45 Rev Time 0.00
Received By shill Date 2019-07-02 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-24 Cont ID  
Sent By shill Date 2019-06-24 Time 10:59 Rev Time 0.00
Received By shill Date 2019-06-05 Time 15:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2019-06-24 Cont ID  
Sent By shill Date 2019-06-24 Time 10:59 Rev Time 0.00
Received By shill Date 2019-06-24 Time 10:59 Sent To  
Notes
***NONE***