Plan Review Details - Permit 19060095
Plan Review Stops For Permit 19060095
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-26 Cont ID  
Sent By dbattles Date 2019-06-26 Time 08:06 Rev Time 0.00
Received By dbattles Date 2019-06-26 Time 08:06 Sent To  
Notes
2019-06-26 08:08:24PLANS WITH DIGITAL SIGNATURE HAVE BEEN VERIFIED AND
 ATTACHED TO THE PERMIT FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By dbattles Date 2019-06-25 Time 08:08 Rev Time 0.00
Received By dbattles Date 2019-06-25 Time 08:08 Sent To  
Notes
2019-06-25 08:12:12RE STAMP WILL BE NEEDED ON APPROVED PLANS PER
 ELECTRICAL COMMENTS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-27 Cont ID  
Sent By fgiaquin Date 2019-06-27 Time 07:02 Rev Time 0.00
Received By fgiaquin Date 2019-06-27 Time 06:45 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-20 Cont ID  
Sent By fgiaquin Date 2019-06-20 Time 07:23 Rev Time 0.00
Received By fgiaquin Date 2019-06-20 Time 07:07 Sent To B
Notes
2019-06-20 07:11:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EVERY SIGNATURE ON PLAN IS A COPY. PHYSICAL WET
 SIGNATURE REQUIRED FROM DESGIN PROFESSIONAL ON ALL
 SEALS. PLEASE SEE THE REQUIREMENTS FOR SIGNATURES AND
 SEALS BELOW.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-27 Cont ID  
Sent By fgiaquin Date 2019-06-27 Time 07:02 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By dbattles Date 2019-06-25 Time 08:12 Rev Time 0.00
Received By dbattles Date 2019-06-04 Time 13:58 Sent To  
Notes
2019-06-05 13:58:55ROUTED TO ZONING INBOX

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-06-25 Cont ID  
Sent By dbattles Date 2019-06-25 Time 08:07 Rev Time 0.00
Received By dbattles Date 2019-06-25 Time 08:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-07 Cont ID  
Sent By hmtribou Date 2019-06-07 Time 09:20 Rev Time 0.00
Received By hmtribou Date 2019-06-07 Time 09:20 Sent To E
Notes
2019-06-07 09:22:10SOLAR COLLECTOR PANELS MUST BE MOUNTED PARALLEL TO
 ROOFS SURFACE NO GREATER THAN 12? ABOVE THE ROOFS
 SURFACE.